AXIS ELECTRICAL SERVICES, LLC. | E= | C | 12/07/2022 | | BRIAN | BRIAN | | E= | C | 7602912 |
AXIS ELECTRICAL SERVICES, LLC. | E= | R | 11/28/2022 | need to bond the disconnect and transformers / elevator #3 / | BRIAN | BRIAN | | E= | R | 7593196 |
AXIS ELECTRICAL SERVICES, LLC. | ER | P | 09/01/2022 | elevator 2--ok / changed feeder / | BRIAN | BRIAN | | ER | P | 7503619 |
AXIS ELECTRICAL SERVICES, LLC. | ER | R | 08/30/2022 | elevator # 2 --- feeds from wrong location , need to splice plans or switch where it feeds from / need OCP to match the AIC rating / rest of the install ok on #1 / | BRIAN | BRIAN | | ER | R | 7500385 |
AXIS ELECTRICAL SERVICES, LLC. | ER | P | 05/20/2022 | Elevator 1- #1 125amp breaker, disco and transformer ok --- 2 mini split 20amp ok | JIMMY | JIMMY | | ER | P | 7383628 |
KONE, INC. | HE= | C | 12/09/2022 | ELEVATORS #1, #2 AND #3 MODERNIZATION COMPLETE - CSFD INSPECTION REPORT UPLOADED TO PERMIT. | ROBERTV | ROBERTV | | HE= | C | 7605981 |
KONE, INC. | HE= | P | 11/28/2022 | (ELEVATOR #3) -- NEED TO TEST FIRE SERVICE WITH GROUP AND LOBBY STATUS PANEL. NEED "TWO-WAY COMMUNICATION INSIDE" LABELS ON FRONT OF CONTROLLER DOORS........ REMAINING ITEMS FOR ELEVATOR #1 AND #2 ARE COMPLETED. | ROBERTV | ROBERTV | | HE= | P | 7593557 |
KONE, INC. | HE= | P | 08/31/2022 | (ELEVATOR #2) -- OK FOR PUBLIC USE -- ITEMS NEEDED BY FINAL: FIRE SERVICE TESTING AND OPERATION AS GROUP. ELEVATOR RELATED FIRE ALARM DEVICES NEED TO BE OK BY CSFD. NEED TO TEST AND INSPECT LOBBY STATUS PANEL. | DUSTINS | DUSTINS | | HE= | P | 7502985 |
PRECISE MECHANICAL SERVICES, INC. | H= | C | 07/15/2022 | CORRECTIONS MADE SEE IMAGES | JERRYF | JERRYF | | H= | C | 7447251 |
PRECISE MECHANICAL SERVICES, INC. | H= | P | 07/14/2022 | MECHANICALLY FASTEN FLEXIBLE CONDENSATE DRAIN TO PVC - CANNOT USE TAPE (CONTRACTOR CAN ATTACH PICTURES TO NEXT INSPECTION REQUEST) | JERRYF | JERRYF | | H= | P | 7446209 |
KONE, INC. | HE= | P | 06/17/2022 | (ELEVATOR #1) - OK FOR PUBLIC USE.....ITEMS THAT NEED TO BE COMPLETED BY FINAL: TOP OF CAR 4" TOE BOARD PANEL ON SIDES MORE THAN 12" FROM HOISTWAY (A17.1 - 2.10.2.3). CROSSHEAD #1 IDENTIFICATION (A17.1 - 2.29.1.2(g). NEED TO CHECK SECURING OF ADDED COUNTERWEIGHTS WHEN COMPLETED (A17.1 - 2.21). CROSS HEAD DATA TAG TO REFLECT DATA OF APPROVED INSTALLATION. LOBBY STATUS PANEL TESTING AND OPERATION. FIRE SERVICE TESTING AND OPERATION AS GROUP. DOOR LOCK MONITORING TESTING. 3D DOOR REOPENING DEVICE TESTING WITH MANUFACTURERS WRITTEN TESTING PROCEDURES. (See Images for Suspension Member Factor of Safety Calcs from Kone Engineering RV) | ROBERTV | ROBERTV | | HE= | P | 7415775 |
KONE, INC. | HE= | P | 06/16/2022 | (ELEVATOR #1) - NEED ENGINEERING FACTOR OF SAFETY CALCS FOR REDUCING COUNT OF TOTAL SUSPENSION MEMBERS FROM 5 TO 4 BEFORE CAR CAN BE USED FOR PUBLIC USE......ITEMS THAT NEED TO BE COMPLETED BY FINAL: 48" CAR PLATFORM TOE GUARD PER (A17.1 - 8.7.2.27.5(j), 2.19.2.2(b) and 2.15.9.2(a). TOP OF CAR 4" TOE BOARD PANEL ON SIDES MORE THAN 12" FROM HOISTWAY (A17.1 - 2.10.2.3). CROSSHEAD #1 IDENTIFICATION (A17.1 - 2.29.1.2(g). NEED TO CHECK SECURING OF ADDED COUNTERWEIGHTS WHEN COMPLETED (A17.1 - 2.21). CROSS HEAD DATA TAG TO REFLECT DATA OF APPROVED INSTALLATION. LOBBY STATUS PANEL | ROBERTV | ROBERTV | | HE= | P | 7414618 |
AXIS ELECTRICAL SERVICES, LLC. | XES | T | 05/16/2022 | PAID (REC#1867148): PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Revised one line | SHELBY | SHELBY | | XES | T | 7377310 |
PRECISE MECHANICAL SERVICES, INC. | XMS | T | 04/05/2022 | PAID (REC#1876570) PLAN SPLICE FEE: $50 by: DALEH for Mechanical: CLOUDS | DALEH | DALEH | | XMS | T | 7327076 |