INNOVATIVE CONSTRUCTION, INC. | B= | C | 10/14/2022 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 7551230 |
INNOVATIVE CONSTRUCTION, INC. | B= | P | 10/11/2022 | With completed required inspections B= okay. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), CRONEN PLUMBING AND HEATING, INC. Plumbing Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 7547124 |
INNOVATIVE CONSTRUCTION, INC. | BSP | P | 05/19/2022 | Ceiling grid wires OK | ADAML | ADAML | | BSP | P | 7382619 |
INNOVATIVE CONSTRUCTION, INC. | BFR | P | 03/01/2022 | Attach plumbing and mechanical and complete required inspections / Light gauge metal framing OK / Contact inspector for any accessibility related questions | ADAML | ADAML | | BFR | P | 7286335 |
INTERMOUNTAIN POWER SERVICES INC | E= | C | 05/19/2022 | | LOGANP | LOGANP | | E= | C | 7383066 |
INTERMOUNTAIN POWER SERVICES INC | E= | P | 05/09/2022 | Address MC whip coil in conference room / Blank quad above break room | BRETC | BRETC | | E= | P | 7369245 |
INTERMOUNTAIN POWER SERVICES INC | ER | C | 05/06/2022 | All corrections made / Ceilings - Ok / Pictures sent to phone | BRETC | BRETC | | ER | C | 7367568 |
STILSON ELECTRIC SYSTEMS, INC. | E= | C | 05/06/2022 | FIRE ALARM INSPECTION: | BRETC | BRETC | | E= | C | 7366419 |
STILSON ELECTRIC SYSTEMS, INC. | ER | C | 05/06/2022 | FIRE ALARM INSPECTION: Corrections made | BRETC | BRETC | | ER | C | 7366412 |
INTERMOUNTAIN POWER SERVICES INC | ER | P | 05/06/2022 | Plenum ceiling - Need to verify Low Volt wire to Occupancy Censors is plenum rated / ---------- At VAV kicker and light grid wire won't let VAV door open 90 degrees | BRETC | BRETC | | ER | P | 7366410 |
STILSON ELECTRIC SYSTEMS, INC. | ER | P | 05/02/2022 | FIRE ALARM INSPECTION: No FA ceiling boxes mounted to grid, they are hanging above grid - Do not close grid | BRETC | BRETC | | ER | P | 7358972 |
INTERMOUNTAIN POWER SERVICES INC | ER | P | 05/02/2022 | At VAV kicker and light grid wire won't let VAV door open 90 degrees | BRETC | BRETC | | ER | P | 7358968 |
INTERMOUNTAIN POWER SERVICES INC | ER | P | 02/28/2022 | Fire alarm contractor to attach to permit / All walls only - Ok | BRETC | BRETC | | ER | P | 7283816 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | C | 10/06/2022 | | MATTM | MATTM | | H= | C | 7542667 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 05/24/2022 | TEST AND BALANCE REPORT DOES NOT SHOW REQUIRED VENTILATION / | MATTM | MATTM | | H= | P | 7386578 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 05/20/2022 | FINAL PENDING - Provide test and balance report. OTHER CORRECTIONS MADE. | MARKB | MARKB | | H= | P | 7384358 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 05/16/2022 | 6 INCH OFF VAV-5 IS EXISTING NON-CONFORMING / OPEN OFFICE (ROOM 121) SOUTH SIDE---TWO 8 INCH TAKE OFF's NO INSTALLED PER PLAN LOCATION / REMOVE ABANDONED FIRE DAMPER FROM 14x12 DUCT ON VAV-5 SYSTEM / NEED TEST AND BALANCE REPORT / | MATTM | MATTM | | HD | P | 7377726 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | R | 05/09/2022 | 6 INCH OFF VAV-5 SERVING HALLWAY NOT SHOWN ON PLANS / OPEN OFFICE (ROOM 121) SOUTH SIDE---TWO 8 INCH TAKE OFFS NOT INSTALLED PER PLAN LOCATION / REMOVE ABANDONED FIRE DAMPER FROM 14X12 DUCT ON VAV-5 SYSTEM / MEDIUM PRESSURE DUCT TO VAV-6 NOT INSTALLED / NO THERMOSTATS, FLEX OR DIFFUSERS AT THIS TIME / NEED TEST AND BALANCE REPORT / | MATTM | MATTM | | HD | R | 7369070 |
CRONEN PLUMBING AND HEATING, INC. | P= | C | 10/14/2022 | Correction complete via image | FRANKM | FRANKM | | P= | C | 7551229 |
CRONEN PLUMBING AND HEATING, INC. | P= | R | 10/13/2022 | No access (2:46pm-3:46pm) / message mailbox full @ call ahead | FRANKM | FRANKM | | P= | R | 7550051 |
CRONEN PLUMBING AND HEATING, INC. | P= | P | 09/02/2022 | Insulate H2O , rest ok | FRANKM | FRANKM | | P= | P | 7505897 |
CRONEN PLUMBING AND HEATING, INC. | P= | R | 05/13/2022 | no one on site to show inspector location, don't see any room numbers, could not find any sinks completed | JOSEPHD | JOSEPHD | | P= | R | 7375338 |
CRONEN PLUMBING AND HEATING, INC. | P= | R | 05/10/2022 | no ready for final, wrong permit called in? | JOSEPHD | JOSEPHD | | P= | R | 7369835 |
CRONEN PLUMBING AND HEATING, INC. | P= | R | 05/03/2022 | Not ready. | DANR | DANR | | P= | R | 7360742 |
CRONEN PLUMBING AND HEATING, INC. | PTO | C | 03/11/2022 | AAV AT SINK ON FINAL | LEE | LEE | | PTO | C | 7298905 |
INTERMOUNTAIN POWER SERVICES INC | XES | T | 05/18/2022 | PAID (REC#1867994): PLAN SPLICE FEE: $50 by: SHELBY for Electrical: Revised one line///VAV 6 | SHELBY | SHELBY | | XES | T | 7380976 |