HENSEL PHELPS CONSTRUCTION CO | B= | C | 01/25/2023 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 7643853 |
HENSEL PHELPS CONSTRUCTION CO | B= | P | 11/11/2022 | With completed required inspections B= okay. Additional Inspections Required (computer generated): BIBLE ELECTRIC, INC. Electrical Final Inspection is not Completed yet, CONVERGINT TECHNOLOGIES, LLC Electrical Final Inspection is not Completed yet, HEATING & PLUMBING ENGINEERS, INC Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 7580639 |
HENSEL PHELPS CONSTRUCTION CO | BFR | P | 09/15/2022 | Reviewed Accessible Elements / 3rd party observation for steel and CMU by final, light steel stud framing and hard lids okay with completed required inspections. | NATHAN | NATHAN | | BFR | P | 7518718 |
HENSEL PHELPS CONSTRUCTION CO | BSP | P | 09/15/2022 | Plans attached. Frame inspection to follow. | NATHAN | NATHAN | | BSP | P | 7517647 |
CONVERGINT TECHNOLOGIES, LLC | E= | C | 01/25/2023 | FIRE ALARM INSPECTION: | BRIAN | BRIAN | | E= | C | 7643852 |
CONVERGINT TECHNOLOGIES, LLC | ER | C | 01/25/2023 | FIRE ALARM INSPECTION: | BRIAN | BRIAN | | ER | C | 7643844 |
BIBLE ELECTRIC, INC. | E= | C | 12/13/2022 | | BRIAN | BRIAN | | E= | C | 7609323 |
BIBLE ELECTRIC, INC. | E= | P | 11/09/2022 | need grate bonding around pool / need gfci breakers on washer and dryer / rest ok | BRIAN | BRIAN | | E= | P | 7578040 |
BIBLE ELECTRIC, INC. | ER | P | 10/27/2022 | office ceiling--ok / | BRIAN | BRIAN | | ER | P | 7564811 |
BIBLE ELECTRIC, INC. | ER | R | 10/26/2022 | the grid support wires need to be supporting the lights not just attached with lots of slack / can not tie grid wires to the fire sprinkler pipes / open j boxes / unsupported mc cables /. some support wires not even attached to the grid / complete ceiling reinspection / | BRIAN | BRIAN | | ER | R | 7562906 |
BIBLE ELECTRIC, INC. | ER | P | 09/20/2022 | rest of the walls and sauna --ok / still need pic of the bonding to the water lines next to hot tub / | BRIAN | BRIAN | | ER | P | 7522767 |
BIBLE ELECTRIC, INC. | ER | P | 09/16/2022 | hard lid ceilings--ok / note need water bib bond for the spa / verify on next inspection / | BRIAN | BRIAN | | ER | P | 7520302 |
CONVERGINT TECHNOLOGIES, LLC | ER | P | 09/14/2022 | FIRE ALARM INSPECTION: hard lids and walls ok / | BRIAN | BRIAN | | ER | P | 7516854 |
BIBLE ELECTRIC, INC. | ER | R | 09/14/2022 | need to remove the j boxes above the hard lid or add access doors / recept to close to hot tub / | BRIAN | BRIAN | | ER | R | 7516846 |
BIBLE ELECTRIC, INC. | ER | P | 09/09/2022 | wall rough in for office, storage, laundry, and men's and women's bath and shower areas okay | CHIPO | CHIPO | | ER | P | 7511460 |
BIBLE ELECTRIC, INC. | ESL | C | 08/09/2022 | | BRIAN | BRIAN | | ESL | C | 7475924 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 01/17/2023 | ENGINEER LETTER RECEIVED FOR TEST AND BALANCE REPORT. | MARKB | MARKB | | H= | C | 7635781 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 01/17/2023 | NO ATTACHMENT TO INSPECTION REQUEST FOUND | MARKB | MARKB | | H= | P | 7635528 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 12/22/2022 | FINAL PENDING - Provide revised test and balance report. REST OK. | MARKB | MARKB | | H= | P | 7618792 |
HEATING & PLUMBING ENGINEERS, INC | H= | L | 12/01/2022 | Site locked contractor not on site. Spoke with Audie by phone - Will accept pictures of exhaust fan access and sign at sauna. | MARKB | MARKB | | H= | L | 7597437 |
HEATING & PLUMBING ENGINEERS, INC | H= | R | 11/30/2022 | Still need revised test and balance report. Still need site visit. | MARKB | MARKB | | H= | R | 7595772 |
HEATING & PLUMBING ENGINEERS, INC | H= | R | 11/11/2022 | TEST AND BALANCE REPORT DOES NOT SHOW REQUIRED OUTSIDE AIR IN ROOM 104 / | MATTM | MATTM | | H= | R | 7580126 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 11/08/2022 | RECEIVED LETTER FOR SAUNA TRANSFERS, SEE IMAGES / Provide test and balance report / Install "Warning Notice" per the 2015 IMC section 914.5.1 / ok to attach picture to next inspection request / | MATTM | MATTM | | H= | P | 7575481 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 11/04/2022 | Provide test and balance report / Need to address: Sauna transfers do not match size listed on plans. Both transfers are shown on the approve plans going into room 100. One transfer is currently going into the bathroom. / Install "Warning Notice" per the 2015 IMC section 914.5.1 / | MATTM | MATTM | | H= | P | 7572960 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 11/01/2022 | Provide test and balance report / Missing thermostat / Need to address: Sauna transfers do not match size listed on plans. Both transfers are shown on the approve plans going into room 100. One transfer is currently going into the bathroom. Provide installation instructions for Sauna. Sauna installation will need to comply with the 2015 IMC section 914. Sauna thermostat not installed at this time. | MATTM | MATTM | | H= | P | 7568920 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 10/07/2022 | ABOVE CEILING DUCT - FLEX. DIFFUSERS AND TRANSFER COMPLETE IN CONFERENCE AND MEDICAL ROOMS. | MARKB | MARKB | | HD | P | 7543867 |
HEATING & PLUMBING ENGINEERS, INC | HSP | R | 09/26/2022 | CANNOT ACCEPT UN APPROVED PLANS - ALL PLAN SPLICES MUST BE APPROVED THROUGH RBD PLAN REVIEW. | MARKB | MARKB | | HSP | R | 7529132 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 09/16/2022 | ABOVE CEILING DUCT - SUPPLY/EXHAUST DUCT BETWEEN GRID LINES L & M INSTALLED PER SPLICE OK TO COVER. | MARKB | MARKB | | HD | P | 7519674 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 09/09/2022 | ----ENGINEER TO ADDRESS: Exhaust duct and fan for EF-4 between grid lines L & M not installed per plan.---- ABOVE CEILING DUCT - ROUGH SUPPLY/EXHAUST/DRYER DUCT BETWEEN GRID LINES M & N INSTALLED PER PLAN OK TO COVER. No grills at this time. | MARKB | MARKB | | HD | P | 7511681 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 08/25/2022 | --WILL NEED A MECHANICAL CONTRACTOR TO CLAIM SAUNA. Sauna not installed at this time. --AM TOLD THERE WILL BE A MECHANICAL SPLICE FOR EF-4 FAN AND DUCT. ABOVE CEILING DUCT - LOW PRESSURE MAINS/BRANCHES FOR EXISTING VAV INSTALLED PER PLAN OK NOT WRAP. Concealed volume dampers will be cable operated. | MARKB | MARKB | | HD | P | 7495504 |
HEATING & PLUMBING ENGINEERS, INC | P= | C | 11/09/2022 | | CODYP | CODYP | | P= | C | 7578023 |
HEATING & PLUMBING ENGINEERS, INC | P= | P | 11/09/2022 | Hand shower and control for hand shower on slide bar need to be in control range for both accessible showers, NOTE/ Rest o.k. | CODYP | CODYP | | P= | P | 7577345 |
HEATING & PLUMBING ENGINEERS, INC | PTO | C | 10/13/2022 | | CODYP | CODYP | | PTO | C | 7548998 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 09/26/2022 | Looked at toilets, new washer box location and ice maker box, See splice, NOTE/ Still need to see tie ins | CODYP | CODYP | | PTO | P | 7529218 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 09/13/2022 | ADA toilet flush valves will be on the wrong side of both toilets, o.k. to attach photo at next inspection request, NOTE/ Will need to see domestic water tie in and vent tie in/ Rest o.k. | CODYP | CODYP | | PTO | P | 7514573 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 09/08/2022 | Looked at over head water lines only. need to see insulation, NOTE/ Over head water lines o.k. | CODYP | CODYP | | PTO | P | 7509845 |
HEATING & PLUMBING ENGINEERS, INC | PB | C | 08/03/2022 | | CODYP | CODYP | | PB | C | 7470432 |
HEATING & PLUMBING ENGINEERS, INC | PB | P | 08/02/2022 | Still 2 traps on the same trap arm, NOTE/ Rest o.k./ See splice for removed ejector pump | CODYP | CODYP | | PB | P | 7468084 |
HEATING & PLUMBING ENGINEERS, INC | PB | P | 08/01/2022 | Plans call for trench drains to tie into ejector pump for indirect drainage, Engineer to address if not piping to plan, 2 traps on the same trap arm at showers, Horizontal dry vent at North shower, Need to install washer box drain, Leak on 4" at South bathroom, Will need to re test piping | CODYP | CODYP | | PB | P | 7466655 |
BIBLE ELECTRIC, INC. | XES | P | 09/22/2022 | PLAN SPLICE: (No Fee) by: DANIELG for Electrical: Delta revision 5. As built. | DANIELG | DANIELG | | XES | P | 7526347 |
HENSEL PHELPS CONSTRUCTION CO | XBS | P | 09/22/2022 | PLAN SPLICE: (No Fee) by: MICHAELA for Construction: Minor revision | MICHAELA | MICHAELA | | XBS | P | 7525570 |
HEATING & PLUMBING ENGINEERS, INC | XMS | T | 09/15/2022 | PAID (REC#1899558): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised exhaust | JUSTINC | JUSTINC | | XMS | T | 7517958 |
BIBLE ELECTRIC, INC. | XES | P | 09/15/2022 | PLAN SPLICE: (No Fee) by: DANIELG for Electrical: Delta revision 4 and 5. As built. | DANIELG | DANIELG | | XES | P | 7517326 |
HEATING & PLUMBING ENGINEERS, INC | XMS | P | 09/09/2022 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Minor layout changes | JUSTINC | JUSTINC | | XMS | P | 7511345 |
HENSEL PHELPS CONSTRUCTION CO | XBS | T | 09/09/2022 | PAID (REC#1899118): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Plan clarifications. | MICHAELA | MICHAELA | | XBS | T | 7511219 |
HENSEL PHELPS CONSTRUCTION CO | XBS | T | 09/06/2022 | PAID (REC#1897424): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revision to reflected ceiling plan - add light soffit | MICHAELA | MICHAELA | | XBS | T | 7506263 |
HENSEL PHELPS CONSTRUCTION CO | XBS | P | 05/25/2022 | PLAN SPLICE: (No Fee) by: MICHAELA for Construction: Revised room name | MICHAELA | MICHAELA | | XBS | P | 7388067 |
HEATING & PLUMBING ENGINEERS, INC | XMS | P | 05/12/2022 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Dryer venting | JUSTINC | JUSTINC | | XMS | P | 7373567 |
BIBLE ELECTRIC, INC. | XES | P | 05/10/2022 | PLAN SPLICE: (No Fee) by: DANIELG for Electrical: As built. | DANIELG | DANIELG | | XES | P | 7371003 |
HEATING & PLUMBING ENGINEERS, INC | XPS | T | 05/10/2022 | PAID (REC#1871974): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Clouded revisions only: Adjusted sheets P1.1, P4.0, P5.0 and P6.0. | SHANEN | SHANEN | | XPS | T | 7369680 |
HENSEL PHELPS CONSTRUCTION CO | XBS | T | 05/10/2022 | PAID (REC#1865597): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Revision to specifications | MICHAELA | MICHAELA | | XBS | T | 7369664 |
BIBLE ELECTRIC, INC. | XES | T | 03/15/2022 | PAID (REC#1857857): PLAN SPLICE FEE: $50 by: DANIELG for Electrical: As built. | DANIELG | DANIELG | | XES | T | 7301429 |