FAITH ENTERPRISES INCORPORATED | E= | C | 12/29/2023 | Wiring and disconnects for two boilers replacing one ok - complete | CHIPO | CHIPO | | E= | C | 7956362 |
FAITH ENTERPRISES INCORPORATED | EE | L | 10/23/2023 | Renewed for $50.00 at 10/23/2023 4:16:57 PM (Receipt#2001255) | NELIDA | NELIDA | | EE | L | 7896796 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | H= | C | 10/10/2022 | CORRECTION MADE - SEE IMAGES | MARKB | MARKB | | H= | C | 7544509 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | H= | P | 09/29/2022 | OK TO FINAL WITH PICTURES OF MEDIUM PRESSURE LABELS AND SUPPLY/RETURN PIPING INSULATION / | MATTM | MATTM | | H= | P | 7534118 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | HWP | C | 09/29/2022 | 2X 65 LB TEST OK FOR SUPPLY/RETURN PIPING IN MECHANICAL ROOM / OK TO WRAP / | MATTM | MATTM | | HWP | C | 7534114 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | H= | P | 09/26/2022 | FINAL PENDING - Need electrical contractor attached to permit. Install medium pressure stickers on gas piping in mechanical room. COMBUSTION AIR, CONDENSATE PIPING AND BOILER VENT CONNECTIONS COMPLETE. | MARKB | MARKB | | H= | P | 7529812 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | HC | C | 09/22/2022 | REPLACED 1 BOILER WITH 2 - 3,000,000 BTU/HR BOILERS | MARKB | MARKB | | HC | C | 7527140 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | HI | C | 09/22/2022 | EXISTING 2 PSI GAS SYSTEM 60 PSI PRESSURE TEST ON WELDED GAS PIPE OK. Still need regulators and labels installed.
| MARKB | MARKB | | HI | C | 7527137 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | HI | P | 09/21/2022 | --NEED ELECTRICAL CONTRACTOR ATTACHED TO PERMIT. --Further research required to determine what existing gas pressure in building is. 10 PSI PRESSURE TEST ON THREADED GAS PIPE OK. Still need 60 psi pressure test on welded pipe. | MARKB | MARKB | | HI | P | 7525453 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | HV | P | 08/29/2022 | --CONTRACTOR TO CORRECT PERMIT SCOPE: Permit scopes needs to include 2 boiler replacements, 1 vent & 2 gas piping outlets. BOILER VENT - 10" CAT4 COMMON VENT OK FOR SUPPORT IN CHASE TO ROOF. Still need to complete condensate piping, wall vent thimble & combustion air piping in chase. | MARKB | MARKB | | HV | P | 7498836 |