WELLS & WEST GENERAL CONTRACTORS, INC. | B= | C | 06/30/2022 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 7431141 |
WELLS & WEST GENERAL CONTRACTORS, INC. | B= | P | 06/24/2022 | SFRM okay, complete all final inspections. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), PEAK HEATING & AIR CONDITIONING, INC. Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 7424862 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 05/06/2022 | obtain and complete mechanical attachment and inspection / Complete all required inspections, reviewed accessible elements . | NATHAN | NATHAN | | BFR | P | 7367424 |
PROCOM ELECTRICAL SERVICES, INC. | E= | C | 06/23/2022 | | BRIAN | BRIAN | | E= | C | 7423234 |
PROCOM ELECTRICAL SERVICES, INC. | ER | R | 06/16/2022 | ceiling ok ----do not cover ceiling until fire alarm is complete / | BRIAN | BRIAN | | ER | R | 7414524 |
PROCOM ELECTRICAL SERVICES, INC. | EP | P | 06/03/2022 | went over tap rules and clearances for transformer /will need ocp on load side conductors from transformer next to the transformer / | BRIAN | BRIAN | | EP | P | 7399025 |
PROCOM ELECTRICAL SERVICES, INC. | ER | P | 05/05/2022 | walls ok except where the floor box feeds tie into the power / rest of walls ok / | BRIAN | BRIAN | | ER | P | 7365947 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | C | 06/30/2022 | TEST AND BALANCE REPORT RECEIVED - SEE IMAGES | MARKB | MARKB | | H= | C | 7431140 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 06/23/2022 | FINAL PENDING - Provide test and balance report. MONOCOAT TO BE LOOKED AT BY BUILDING INSPECTOR. TRANSFER GRILL AND STAT IN 601 COMPLETE. | MARKB | MARKB | | H= | P | 7422840 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 06/17/2022 | FINAL PENDING-- ENGINEER TO ADDRESS THE REMOVAL OF FLOOR/CEILING MONOCOAT FOR HANGARS/STRAPPING THROUGHOUT REMODEL, VERIFICATION OF TF-1 (NO LABEL FOR LISTING OR MODEL FOR INSPECTION), DOOR GRILL TO BE INSTALLED PER NOTE #6 & THERMOSTAT INSTALLED IN TELE DATA ROOM #601, TEST AND BALANCE REPORT. Note / All flex/grills/diffusers ok, Thermostats verified except Room #601. | PAULO | PAULO | | H= | P | 7415465 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | C | 06/17/2022 | ABOVE CEILING DUCT-- Note / All supply air duct/flex/grills and diffusers ok, All return air grills ok. | PAULO | PAULO | | HD | C | 7415393 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 06/07/2022 | ABOVE CEILING DUCT - FLEX, DIFFUSERS & GRILLS COMPLETE EXCEPT IN 601, 602, 603 & 604 have no access because of wet floor. | MARKB | MARKB | | HD | P | 7402405 |
DRUMMOND PLUMBING LLC | P= | C | 06/23/2022 | | TRAVISR | TRAVISR | | P= | C | 7423130 |
DRUMMOND PLUMBING LLC | PTO | P | 05/11/2022 | Need To Get Letter From Engineer For Trap Guard @ Trap Instead Of Trap Primer /
Note: Rest OK | TRAVISR | TRAVISR | | PTO | P | 7371393 |