KGM2 CONSTRUCTION ENTERPRISES, INC | B= | C | 05/24/2023 | All other required Final inspections are complete. (This is a computer generated result) | BRIANB | BRIANB | | B= | C | 7753948 |
KGM2 CONSTRUCTION ENTERPRISES, INC | B= | P | 05/24/2023 | pending other final inspections. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2). | BRIANB | BRIANB | | B= | P | 7753706 |
KGM2 CONSTRUCTION ENTERPRISES, INC | BFR | P | 02/02/2023 | pending other rough inspections / discussed accessible elements with site rep | BRIANB | BRIANB | | BFR | P | 7651781 |
KGM2 CONSTRUCTION ENTERPRISES, INC | BE | P | 10/28/2022 | | JANE | JANE | | BE | P | 7566169 |
MEYER ELECTRIC | E= | C | 05/05/2023 | Electrical ok / | ROB | ROB | | E= | C | 7737201 |
MEYER ELECTRIC | E= | L | 05/04/2023 | Left voice mail at 2:26 that I would be 30 to 45 minutes / Nobody on site / Was at site 2:20 / | ROB | ROB | | E= | L | 7736238 |
MEYER ELECTRIC | E= | T | 05/02/2023 | PAID (REC#1951775): Not ready / | ROB | ROB | | E= | T | 7733346 |
MEYER ELECTRIC | E= | R | 04/27/2023 | support the can termination boxes to the same grid wire you drop to tie the can back to the structure --- fix the 4#6 in 1/2 " connector ---- fill out the panel schedule | CRAIGS | CRAIGS | | E= | R | 7729264 |
MEYER ELECTRIC | E= | R | 04/21/2023 | Need to address panel. Multiple MCC conductors in panel. --- 1/2" connector with 4x #6 coming through it. --- Water heater flex is broken --- Need proper working clearance for water heater disconnect. --- Double landed ground in water heater disconnect. --- Washer receptacle still needs to be GFCI protected. --- Need to paper work showing flat cans are rated to for commercial use. --- Need to support termination boxes for can lights. | AARONR | AARONR | | E= | R | 7724193 |
MEYER ELECTRIC | E= | L | 04/20/2023 | locked 11:24----- no answer at call ahead number | MATTHEW | MATTHEW | | E= | L | 7722139 |
MEYER ELECTRIC | E= | R | 03/30/2023 | HWH wire in cable needs to be identified as phase conductors / New circuits added to panel need to be 22k breakers / Washer/Dryer need GFCI protection / Cannot use ceiling grid wire for electrical support wire / Dryer has #12 wire,should be #10 / | ROB | ROB | | E= | R | 7703132 |
MEYER ELECTRIC | E= | R | 03/29/2023 | Door locked. --- Gave call ahead. | AARONR | AARONR | | E= | R | 7702012 |
MEYER ELECTRIC | ER | R | 03/28/2023 | NOT READY | CRAIG | CRAIG | | ER | R | 7700146 |
MEYER ELECTRIC | ER | L | 01/25/2023 | Partial rough only -- Walls ok / ----------------------- Need to support LED Drivers, J-boxes, Cable, and Recess Fixtures above grid ceiling / Need KO seals in drivers / NOTE: All new breakers need to be 22k / All GFCI recpts required to be fully accessible / | ROB | ROB | | ER | L | 7644310 |
MEYER ELECTRIC | ER | T | 11/21/2022 | PAID (REC#1917402): Not ready / Need past inspection notes | BRETC | BRETC | | ER | T | 7589738 |
MEYER ELECTRIC | E= | L | 11/04/2022 | Not ready-----Do not sheetrock /Need rough before final, will need to see in boxes that have been trimmed cable needs strapping ect. / | ROB | ROB | | E= | L | 7573385 |
MEYER ELECTRIC | EE | L | 11/03/2022 | Renewed online for Half Fee at Nov 3 2022 3:09PM (RECEIPT #: 1912151) | WEBSITE | WEBSITE | | EE | L | 7572305 |
ALL HEATING & COOLING LLC | H= | C | 01/24/2023 | DRYER VENT AND EXHAUST FAN OK / TIMER AND RPM/CFM CONTROL ON WALL. | NICKE | NICKE | | H= | C | 7643289 |
FLACO'S PLUMBING, LLC | P= | C | 05/19/2023 | | CODYP | CODYP | | P= | C | 7749791 |
FLACO'S PLUMBING, LLC | P= | P | 05/11/2023 | Can not use accordion tail piece on sinks unless they have listing and are smooth bore, Missing p traps and mixing valves at both hair washing sinks, Missing insulation on hot water piping in water heater room, Back sink p trap is too deep, NOTE/ Rest o.k. | CODYP | CODYP | | P= | P | 7741876 |
FLACO'S PLUMBING, LLC | PTO | C | 12/09/2022 | | CODYP | CODYP | | PTO | C | 7606011 |
FLACO'S PLUMBING, LLC | PTO | P | 09/16/2022 | Water piping under sized, need plan revision for removal of back right sink, Correct scope of work, NOTE/ Rest o.k. | CODYP | CODYP | | PTO | P | 7520342 |
FLACO'S PLUMBING, LLC | PB | C | 08/01/2022 | corrections made / ok | ANTHONYT | ANTHONYT | | PB | C | 7466378 |
FLACO'S PLUMBING, LLC | PB | P | 07/26/2022 | Can not have san tees on its back, Need pipe wrap on risers and piping in concrete, Need proper bedding around piping, Need to see tie in to existing 3" Re inspect all | CODYP | CODYP | | PB | P | 7459802 |
FLACO'S PLUMBING, LLC | XPS | P | 11/07/2022 | PLAN SPLICE: (No Fee) by: SHANEN for Plumbing: Delta 2 revisions: Adjusted sheet P1.0 and P2.0. | SHANEN | SHANEN | | XPS | P | 7574377 |
MEYER ELECTRIC | XES | T | 11/03/2022 | PAID (REC#1912151): PLAN SPLICE FEE: $50 by: DANIELG for Electrical: Delta revision 2. As built. | DANIELG | DANIELG | | XES | T | 7571549 |
KGM2 CONSTRUCTION ENTERPRISES, INC | XBS | P | 11/03/2022 | PLAN SPLICE: (No Fee) by: MICHAELA for Construction: Eliminate one sink. | MICHAELA | MICHAELA | | XBS | P | 7571193 |