EXECUTIVE CUSTOM CONSTRUCTION, INC. | B= | C | 09/13/2022 | | ADAML | ADAML | | B= | C | 7515508 |
EXECUTIVE CUSTOM CONSTRUCTION, INC. | BFR | P | 05/27/2022 | Attach mechanical and complete rough / Light gauge metal framing for new offices OK / Reviewed accessible elements | ADAML | ADAML | | BFR | P | 7393067 |
BIBLE ELECTRIC, INC. | E= | C | 08/29/2022 | | BRETC | BRETC | | E= | C | 7498837 |
COLORADO ELECTRICAL SYSTEMS, LLC | E= | C | 08/22/2022 | FIRE ALARM INSPECTION: All ceiling rough - OK | BRETC | BRETC | | E= | C | 7491182 |
COLORADO ELECTRICAL SYSTEMS, LLC | ER | C | 08/22/2022 | FIRE ALARM INSPECTION: All ceiling rough - OK | BRETC | BRETC | | ER | C | 7491181 |
BIBLE ELECTRIC, INC. | ESL | C | 07/28/2022 | 2 floor boxes / 2 - 1" pvc | BRETC | BRETC | | ESL | C | 7462859 |
BIBLE ELECTRIC, INC. | ER | C | 06/21/2022 | Ceilings - Ok | BRETC | BRETC | | ER | C | 7419728 |
BIBLE ELECTRIC, INC. | ER | P | 05/25/2022 | All walls only - Ok | BRETC | BRETC | | ER | P | 7388339 |
NIELSEN MECHANICAL CONTRACTORS, LLC | H= | C | 08/30/2022 | STAMPED ENGINEER LETTER RECEIVED APPROVING ALL THERMOSTAT LOCATIONS. SEE IMAGES / MECHANICAL FINAL OK / | LIDO | LIDO | | H= | C | 7500190 |
NIELSEN MECHANICAL CONTRACTORS, LLC | H= | P | 08/25/2022 | HAD CONVERSATION WITH THE MECHANICAL CONTRACTOR ABOUT THE FOLLOWING. PLAN SPLICE DOES NOT SHOW HP-2(E) THERMOSTAT IN THE CORRECT LOCATION. REFER TO THE FOLLOWING NOTES / FINAL PENDING: HP-2 (E) THERMOSTAT WAS THE ONLY THERMOSTAT RELOCATED. PLAN SHOWS THERMOSTAT TO BE RELOCATED TO ELECTRICAL ROOM WALL, THERMOSTAT WAS INSTALLED IN SOUTH EAST OFFICE. INSTALL WHERE THE PLANS SHOWS OR PROVIDE DOCUMENTATION FROM ENGINEER SHOWING NEW LOCATION / | LIDO | LIDO | | H= | P | 7495962 |
NIELSEN MECHANICAL CONTRACTORS, LLC | H= | P | 08/15/2022 | TEST AND BALANCE REPORT RECEIVED. SEE IMAGES / FINAL PENDING : SEE NOTES DATED 8/12/22 / | LIDO | LIDO | | H= | P | 7482027 |
NIELSEN MECHANICAL CONTRACTORS, LLC | H= | P | 08/12/2022 | ALL SECONDARY PROTECTION FOR EXISTING EQUIPMENT INSTALLED / FINAL PENDING: HP-2 (E) THERMOSTAT WAS THE ONLY THERMOSTAT RELOCATED. PLAN SHOWS THERMOSTAT TO BE RELOCATED TO ELECTRICAL ROOM WALL, THERMOSTAT WAS INSTALLED IN SOUTH EAST OFFICE. INSTALL WHERE THE PLANS SHOWS OR PROVIDE DOCUMENTATION FROM ENGINEER SHOWING NEW LOCATION / NEED TO REVIEW TEST AND BALANCE REPORT/ | LIDO | LIDO | | H= | P | 7481863 |
NIELSEN MECHANICAL CONTRACTORS, LLC | H= | P | 08/11/2022 | TEST AND BALANCE REPORT IS BEING REVIEWED / | LIDO | LIDO | | H= | P | 7479011 |
NIELSEN MECHANICAL CONTRACTORS, LLC | H= | P | 07/07/2022 | FINAL PENDING : DEMOED SECONDARY PROTECTION FOR THE EXISTING FAN COIL UNITS WILL NEED TO BE RE INSTALLED / TOP OF ALL RELOCATED THERMOSTATS TO NO GREATER THAN 48" ABOVE THE FLOOR. OK TO INSTALL A LOCK BOX / NEED TEST AND BALANCE REPORT / | LIDO | LIDO | | H= | P | 7438589 |
NIELSEN MECHANICAL CONTRACTORS, LLC | HD | C | 07/07/2022 | SECONDARY PROTECTION FOR THE EXISTING FAN COIL UNITS THAT WAS REMOVED DURING DEMO WILL NEED TO BE RE INSTALLED / DUCT INSTALLED PER PLAN SPLICE DATED 7/6/22 / ALL SUPPLY FLEX DUCT, REGISTERS OK / ALL RETURN AIR LAY IN GRILLS REGISTERS OK / | LIDO | LIDO | | HD | C | 7438575 |
NIELSEN MECHANICAL CONTRACTORS, LLC | HD | P | 06/30/2022 | DUCT NOT INSTALLED PER THE APPROVED PLANS / INSTALL PER PLAN OR NEED REVISED AND APPROVED PLANS / NEED TO RE INSPECT ALL / SECONDARY PROTECTION FOR THE EXISTING FAN COIL UNITS WILL NEED TO BE RE INSTALLED /
| LIDO | LIDO | | HD | P | 7431609 |
NIELSEN MECHANICAL CONTRACTORS, LLC | XMS | P | 08/24/2022 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised T-Stat location | JUSTINC | JUSTINC | | XMS | P | 7494548 |
NIELSEN MECHANICAL CONTRACTORS, LLC | XMS | T | 07/06/2022 | PAID (REC#1880561): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Layout revised | JUSTINC | JUSTINC | | XMS | T | 7435962 |