GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 05/15/2023 | All other required Final inspections are complete. (This is a computer generated result) | ADAML | ADAML | | B= | C | 7743883 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 04/24/2023 | . Additional Inspections Required (computer generated): COLORADO SHEET METAL CO., INC. Mechanical Final Inspection is not Completed yet. | ADAML | ADAML | | B= | P | 7725350 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 03/08/2023 | Mechanical shaft - 2nd layer drywall OK on 1st and 2nd Floors - Penetration protection OK | ADAML | ADAML | | BSP | P | 7681662 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | P | 02/28/2023 | Mechanical shaft - 1st layer drywall OK 1st and 2nd Floors per UL V455 | ADAML | ADAML | | BSP | P | 7672313 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 02/23/2023 | Mechanical shaft - Metal framing and shaftliner OK 1st and 2nd Floors per UL V455 / Will need an inspection for each layer of drywall | ADAML | ADAML | | BFR | P | 7668329 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BE | L | 01/30/2023 | Renewed for half Fee at 1/30/2023 10:19:28 AM | AMYP | AMYP | | BE | L | 7647891 |
COLORADO SHEET METAL CO., INC. | H= | C | 05/15/2023 | TEST AND BALANCE REPORT RECEIVED - SEE IMAGES | MARKB | MARKB | | H= | C | 7743882 |
COLORADO SHEET METAL CO., INC. | HD | P | 04/19/2023 | FINAL PENDING - Provide test and balance report. SPLICE ON FILE REMOVED RETURN ON 1ST FLOOR, DAMPER ANGLES AND ACCESS DOORS COMPLETE. | MARKB | MARKB | | HD | P | 7721337 |
COLORADO SHEET METAL CO., INC. | HSP | P | 04/19/2023 | LETTER RECEIVED FROM FIRE PROTECTION ENGINEER FOR FIRE/SMOKE DAMPERS INSTALLED THROUGH FLOOR - SEE IMAGES | MARKB | MARKB | | HSP | P | 7720471 |
COLORADO SHEET METAL CO., INC. | HD | P | 02/21/2023 | ----ENGINEER TO ADDRESS: 1st floor return duct shown on plans outside of shaft is now installed inside shaft.---- FIRE/SMOKE DAMPER FRAMING IN SHAFT WALL OK ON 2ND FLOOR AND 1ST FLOOR AROUND RETURN OPENING(no damper installed in 1st floor return opening). | MARKB | MARKB | | HD | P | 7666187 |
COLORADO SHEET METAL CO., INC. | HSP | P | 02/15/2023 | LOOKED AT SHAFT FRAMING FOR FIRE/SMOKE DAMPERS AND WENT OVER MANUFACTURER INSTALL INSTRUCTIONS - framing does not match manufacturer instructions at this time. | MARKB | MARKB | | HSP | P | 7662637 |
COLORADO SHEET METAL CO., INC. | HD | R | 02/01/2023 | 1ST FLOOR: FIRE/SMOKE DAMPER INSTALLATION - 2 dampers in floor do not meet manufacturer instructions for angle or annular space. How protecting space between dampers? Existing Return duct is not protected through new shaft wall and current approved plans show return outside of shaft. | MARKB | MARKB | | HD | R | 7650830 |
COLORADO SHEET METAL CO., INC. | HE | L | 02/01/2023 | Renewed online for Half Fee at Feb 1 2023 8:07AM (RECEIPT #: 1930187) | WEBSITE | WEBSITE | | HE | L | 7649808 |
COLORADO SHEET METAL CO., INC. | HD | L | 01/13/2023 | cancelled by contractor | MARKB | MARKB | | HD | L | 7635070 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 12/22/2022 | HUMIDIFIER NOTES WERE FOUND ON PLAN. CONDENSATE PIPING FOR CRAC UNIT AND HUMIDIFIER ARE COMPLETE. | MARKB | MARKB | | H= | C | 7619063 |
COLORADO SHEET METAL CO., INC. | HD | P | 07/22/2022 | 2ND FLOOR: BELOW CEILING DUCT - STAINLESS DUCT FROM PAIR OF PANTS (see splice) DOWN BOTH SIDE OF HALL WITH DIFFUSERS COMPLETE EXCEPT: Need duct for last 2 diffusers installed on long leg. Still need all inspections on 2 fire/smoke dampers at new shaft. | MARKB | MARKB | | HD | P | 7456921 |
COLORADO SHEET METAL CO., INC. | HD | P | 06/17/2022 | ELECTRICAL CONTRACTOR TO ATTACH TO PERMIT / SHAFT DUCT PER PLANS / Provide damper installation instruction at next inspection. Framing around dampers is incomplete / | MATTM | MATTM | | HD | P | 7415990 |
OLSON PLUMBING & HEATING COMPANY | XMS | T | 07/14/2022 | PAID (REC#1892673): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Layout | JUSTINC | JUSTINC | | XMS | T | 7446139 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XES | T | 07/05/2022 | PAID (REC#1881499): PLAN SPLICE FEE: $50 by: DANIELG for Electrical: Delta revision 4. As built. | DANIELG | DANIELG | | XES | T | 7435434 |