APACHE ELECTRIC AND MAINTENANCE INC | ES | C | 12/05/2023 | Commercial Service: 200 amp,4w, Repair only, no action needed. | JOHNN | JOHNN | | ES | C | 7935250 |
APACHE ELECTRIC AND MAINTENANCE INC | E= | C | 12/05/2023 | | JOHNN | JOHNN | | E= | C | 7935247 |
APACHE ELECTRIC AND MAINTENANCE INC | EE | P | 05/10/2023 | | BRITNEY | BRITNEY | | EE | P | 7740488 |
APACHE ELECTRIC AND MAINTENANCE INC | E= | R | 11/21/2022 | please read all previous comments/ submit 1 line to plan review/ pic of 1 line is not correct. | JOHNN | JOHNN | | E= | R | 7588698 |
APACHE ELECTRIC AND MAINTENANCE INC | E= | P | 11/18/2022 | corrections made / need plan splice approved , no disconnect installed outside and 200 amp main not 225 / ok to final after plan splice is approved / | BRIAN | BRIAN | | E= | P | 7588389 |
APACHE ELECTRIC AND MAINTENANCE INC | E= | R | 11/04/2022 | 1 line does not match as built/ service is 200 amp,3 phase, 120/208 v, with main cb inside/only meter outside/ need cold water grd abnd jumper, 2 grd rods, remove bare grd from nipple, bond nipple 1 end/ brass tag, get with CSU for label on brass tag/ bond neutral in panel, Note: building is on 22nd and midland, west end of property. | JOHNN | JOHNN | | E= | R | 7573546 |
APACHE ELECTRIC AND MAINTENANCE INC | E= | T | 11/03/2022 | PAID (REC#1912012): need EC onsite, open equipment before inspector arrives. | JOHNN | JOHNN | | E= | T | 7571482 |
APACHE ELECTRIC AND MAINTENANCE INC | E= | R | 11/02/2022 | no one on site / no access to inside / complete reinspection needed / need access to inside / | BRIAN | BRIAN | | E= | R | 7570597 |
APACHE ELECTRIC AND MAINTENANCE INC | ES | P | 10/17/2022 | Commercial Service: 200 amp,3w, pre release,ok, EC needs to schedule with CSU | JOHNN | JOHNN | | ES | P | 7551848 |
APACHE ELECTRIC AND MAINTENANCE INC | ES | R | 09/13/2022 | Commercial Service: Contractor to call inspector John Nuss @ 719-290-4058 M, or 719-327-2949 W to discuss scope of work. | CHIPO | CHIPO | | ES | R | 7514132 |