BRYAN CONSTRUCTION, INC. | B= | C | 09/29/2022 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 7534025 |
BRYAN CONSTRUCTION, INC. | B= | P | 09/22/2022 | With completed required inspections B= okay. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), RYBA ELECTRIC, INC. Electrical Final Inspection is not Completed yet, HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 7526601 |
BRYAN CONSTRUCTION, INC. | BFR | P | 08/24/2022 | With completed required inspections frame okay. | NATHAN | NATHAN | | BFR | P | 7494331 |
RYBA ELECTRIC, INC. | E= | C | 09/28/2022 | | BRIAN | BRIAN | | E= | C | 7533487 |
RYBA ELECTRIC, INC. | ER | P | 09/16/2022 | floor box rough in ---ok / pics / | BRIAN | BRIAN | | ER | P | 7519223 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 09/13/2022 | FIRE ALARM INSPECTION: | BRIAN | BRIAN | | E= | C | 7515319 |
SPECIAL SYSTEMS DESIGN,LLC | ER | C | 09/13/2022 | FIRE ALARM INSPECTION: 3 devices / | BRIAN | BRIAN | | ER | C | 7515314 |
RYBA ELECTRIC, INC. | ER | P | 08/25/2022 | walls and some ceilings--see plans / | BRIAN | BRIAN | | ER | P | 7495688 |
HVAC SOLUTIONS, INC. | H= | C | 09/27/2022 | CORRECTION MADE | MARKB | MARKB | | H= | C | 7531476 |
HVAC SOLUTIONS, INC. | H= | P | 09/21/2022 | FINAL PENDING - Return grills in open office areas not installed or not installed in locations shown on plans. Missing transfer between rooms 910 & 911. Missing return grill in room 911. ABOVE CEILING DUCT - FLEX, DIFFUSERS AND CONTROLS COMPLETE. | MARKB | MARKB | | H= | P | 7524728 |
HARMON - BONDED PLUMBING & HEATING, INC. | H= | C | 09/21/2022 | I.T. CONDENSATE PIPING COMPLETE. | MARKB | MARKB | | H= | C | 7524716 |
HVAC SOLUTIONS, INC. | HSP | P | 08/30/2022 | TEST AND BALANCE REPORT RECEIVED - SEE IMAGES | MARKB | MARKB | | HSP | P | 7500103 |
HARMON - BONDED PLUMBING & HEATING, INC. | HSP | P | 08/10/2022 | NOBODY ON SITE. CONDENSATE PIPING NOT COMPLETE. | MARKB | MARKB | | HSP | P | 7478515 |
HARMON - BONDED PLUMBING & HEATING, INC. | HWP | C | 07/28/2022 | ROUGH CONDENSATE PIPING COMPLETE. Still need connections to mini-split and under sink. | MARKB | MARKB | | HWP | C | 7463443 |
HVAC SOLUTIONS, INC. | HD | P | 07/22/2022 | ABOVE CEILING DUCT - SUPPLY MAINS/BRANCHES COMPLETE FOR VAV'S 10-5, 6-22, 10-21, 8-15, 10-16, 10-13 & 12-9. Still need to complete diffusers, grills, thermostats, AC-1 and provide test and balance report. | MARKB | MARKB | | HD | P | 7456463 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | C | 09/22/2022 | | TRAVISR | TRAVISR | | P= | C | 7525638 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | P | 09/21/2022 | Need Vacuum Relief Valve Above Water Heater For Side Inlet / Rest OK / Submit Photo With Inspection Request To Complete | TRAVISR | TRAVISR | | P= | P | 7524298 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | P | 08/10/2022 | Waiting On Photos To Complete / Insulation @ Water Piping | TRAVISR | TRAVISR | | PTO | P | 7477418 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | P | 07/27/2022 | Need Splice For DWV Tie In / Rest OK | TRAVISR | TRAVISR | | PTO | P | 7461448 |
BRYAN CONSTRUCTION, INC. | XBS | T | 08/23/2022 | PAID (REC#1893570): PLAN SPLICE FEE: $50 by: MICHAELA for Construction: Remove doors | MICHAELA | MICHAELA | | XBS | T | 7491643 |
SPECIAL SYSTEMS DESIGN,LLC | XES | T | 08/22/2022 | PAID (REC#1893383): PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised power - see summary of changes. | BERTHA | BERTHA | | XES | T | 7490590 |
BRYAN CONSTRUCTION, INC. | XPS | T | 07/15/2022 | PAID (REC#1883544): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta 4 revisions: Adjusted sheet P0.1. | SHANEN | SHANEN | | XPS | T | 7448781 |