MITCHELL WORKZ, LLC | BFR | R | 03/28/2024 | FRAME - PARTIAL / Classrooms 217-223 - Missing bracing at 4' O.C. at top of walls. / As-built condition of walls, doors, and door locations at walls W3-B at new work area "C" on page A2.20C do not match approved design, need to revise design or build per plan. / Missing wall framing at door #220 by reception in hallway per approved design on new work area "B" on page A2.20B. / Reviewed accessible elements with contractor on-site. / Reviewed wall framing and revised wall framing with contractor on-site. | MATTHEWA | MATTHEWA | | BFR | R | 8035990 |
MITCHELL WORKZ, LLC | B= | P | 04/07/2023 | PARTIAL FINAL - Pending all other required inspections / Classrooms 224 - 233 ( 10 ) and Conference Room 215 OK / All other classrooms have not been constructed yet -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), CARDINAL ELECTRIC LLC Electrical Final Inspection is not Completed yet, TOLIN MECHANICAL SYSTEMS COMPANY, LLC Mechanical Final Inspection is not Completed yet. | ADAML | ADAML | | B= | P | 7710235 |
MITCHELL WORKZ, LLC | B= | P | 04/07/2023 | PARTIAL FINAL - Pending all other required inspections / Classrooms 224 - 233 ( 10 ) and Conference Room 215 OK / All other classrooms have not been constructed yet -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), CARDINAL ELECTRIC LLC Electrical Final Inspection is not Completed yet, TOLIN MECHANICAL SYSTEMS COMPANY, LLC Mechanical Final Inspection is not Completed yet. | ADAML | ADAML | | B= | P | 7710236 |
MITCHELL WORKZ, LLC | B= | R | 04/05/2023 | Field canceled prior to inspection. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), CARDINAL ELECTRIC LLC Electrical Final Inspection is not Completed yet, TOLIN MECHANICAL SYSTEMS COMPANY, LLC Mechanical Final Inspection is not Completed yet. | ERAMIREZ | ERAMIREZ | | B= | R | 7708179 |
MITCHELL WORKZ, LLC | B= | R | 03/27/2023 | Can not request a building final prior to completing MEP rough inspections / Also, the kicker bracing that was noted on the previous frame inspection has not been verified / Spoke to contractor via phone / No inspections performed. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), CARDINAL ELECTRIC LLC Electrical Final Inspection is not Completed yet, TOLIN MECHANICAL SYSTEMS COMPANY, LLC Mechanical Final Inspection is not Completed yet. | ADAML | ADAML | | B= | R | 7698552 |
MITCHELL WORKZ, LLC | B= | R | 03/27/2023 | Can not request a building final prior to completing MEP rough inspections / Also, the kicker bracing that was noted on the previous frame inspection has not been verified / Spoke to contractor via phone / No inspections performed. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yet (Contact: 719-385-5982), CARDINAL ELECTRIC LLC Electrical Final Inspection is not Completed yet, TOLIN MECHANICAL SYSTEMS COMPANY, LLC Mechanical Final Inspection is not Completed yet. | ADAML | ADAML | | B= | R | 7698553 |
MITCHELL WORKZ, LLC | BFR | P | 01/13/2023 | Missing vertical bracing every 4' per plans. / Attach mechanical to permit. / Complete other rough inspections. / | ERAMIREZ | ERAMIREZ | | BFR | P | 7635321 |
CARDINAL ELECTRIC LLC | E= | R | 09/27/2023 | Not Ready | BRETC | BRETC | | E= | R | 7870377 |
CARDINAL ELECTRIC LLC | ER | R | 09/27/2023 | Ceiling rough ok, FA not complete ---------do not close ceiling-------------- / Center offices ceiling lights only - 203,204,205, 209, 210, 211,212&213 only | BRETC | BRETC | | ER | R | 7870363 |
CARDINAL ELECTRIC LLC | ER | R | 09/20/2023 | grid: not ready, missing support wires on fixtures/ please check all rooms before next inspection to avoid trip fee. | JOHNN | JOHNN | | ER | R | 7862753 |
CARDINAL ELECTRIC LLC | E= | P | 04/07/2023 | marked on plans in green / large open area and hallway around the classes / | BRIAN | BRIAN | | E= | P | 7710398 |
CARDINAL ELECTRIC LLC | ER | R | 04/04/2023 | Electrical Rough ok, FA not complete ---------------do not white out ceiling / conference room ok --------------- / | BRIAN | BRIAN | | ER | R | 7706841 |
CARDINAL ELECTRIC LLC | E= | R | 03/29/2023 | all inside class rooms, grid/ CHECK old floor outlet wiring LATER/ | JOHNN | JOHNN | | E= | R | 7701448 |
CARDINAL ELECTRIC LLC | E= | R | 03/28/2023 | need ceiling tiles out of each class room for grid inspection/ many open boxes/ properly support mc cables, ko seals/ need re inspect/ all demo floor outlets: need to see feed capped off in box in ceiling below/ all receps need to be TR per 406:12,4 | JOHNN | JOHNN | | E= | R | 7700464 |
CARDINAL ELECTRIC LLC | ER | P | 03/14/2023 | Conference room walls only - Ok | BRETC | BRETC | | ER | P | 7687090 |
CARDINAL ELECTRIC LLC | ER | P | 01/18/2023 | Fire alarm is working on attaching to permit, was told all fire alarm will be in ceilings per EC. | BRETC | BRETC | | ER | P | 7637451 |
CARDINAL ELECTRIC LLC | ER | R | 01/12/2023 | Fire Alarm needs to attach to permit / Electrical Rough ok, FA not complete ---------------do not sheetrock--------------- / Inner walls only - Ok | BRETC | BRETC | | ER | R | 7633657 |
TOLIN MECHANICAL SYSTEMS COMPANY, LLC | H= | C | 10/19/2023 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES FINAL FOR MECHANICAL CONTRACTOR | BILLS | BILLS | | H= | C | 7892518 |
TOLIN MECHANICAL SYSTEMS COMPANY, LLC | H= | P | 10/16/2023 | NEED REVISED TEST AND BALANCE REPORT. ALL RE-LOCATED SUPPLY AIRS (5) INSTALLED AS PER APPROVED PLANS (ROOMS #223, 224, 225, AND CORRIDOR BETWEEN ROOMS #222 AND 225 DOORWAYS). | BILLS | BILLS | | H= | P | 7889023 |
TOLIN MECHANICAL SYSTEMS COMPANY, LLC | HSP | P | 09/21/2023 | Test and balance report provided does not match mechanical scope on plans. Only small part of scope on plans has been inspected and not approved See notes on balance report for diffusers not connected to correct systems. | MARKB | MARKB | | HSP | P | 7863437 |
TOLIN MECHANICAL SYSTEMS COMPANY, LLC | H= | P | 04/05/2023 | FINAL PENDING - Room 221 is missing supply inside door. Missing supply in corridor at room 223. Room 222 has an extra supply. Provide test and balance report. | MARKB | MARKB | | H= | P | 7708288 |
TOLIN MECHANICAL SYSTEMS COMPANY, LLC | HD | P | 03/16/2023 | ABOVE CEILING DUCT - DIFFUSER AND GRILL LOCATIONS DO NOT MATCH PLAN IN ROOMS 220, 221, 222, 223 OR CORRIDOR OUTSIDE OF THESE ROOMS. | MARKB | MARKB | | HD | P | 7689532 |
TOLIN MECHANICAL SYSTEMS COMPANY, LLC | HD | P | 03/08/2023 | FOR FINAL - Contractor still needs to finish relocating grills in area "A". Provide test and balance report. | MARKB | MARKB | | HD | P | 7681666 |