B&C CONSTRUCTION | B= | P | 08/09/2023 | still need to revise design to reflect as built condition - see comments from BFR inspection / need to complete other final inspections -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): GOLD RUSH PLUMBING Plumbing Final Inspection is not Completed yet, Permit has an open splice that must be approved or canceled. | BRIANB | BRIANB | | B= | P | 7821431 |
B&C CONSTRUCTION | BFR | P | 04/07/2023 | need to revise design to reflect as built condition - to reflect wall layout modifications in break room - counseling room 103 and corridor outside counseling room 104 / observed interior light gauge wall framing / need to attach mechanical to permit and complete other rough inspections / reviewed accessible elements with site rep | BRIANB | BRIANB | | BFR | P | 7710522 |
EAGLE EYE ELECTRIC SERVICES LLC | E= | C | 07/13/2023 | Corrections made. | AARONR | AARONR | | E= | C | 7796483 |
EAGLE EYE ELECTRIC SERVICES LLC | E= | P | 06/29/2023 | Need to add external disconnect for 2x VAV's --- Install KO fillers.............................. Pics ok, upload images with next inspection request. If you encounter problems uploading images, please contact IT at 799-2688 / | AARONR | AARONR | | E= | P | 7786968 |
INTEGRITY FIRE SAFETY SERVICES HOLDINGS, LLC | E= | C | 06/21/2023 | FIRE ALARM INSPECTION: Above ceiling rough OK. | AARONR | AARONR | | E= | C | 7777842 |
INTEGRITY FIRE SAFETY SERVICES HOLDINGS, LLC | ER | C | 06/21/2023 | FIRE ALARM INSPECTION: Above ceiling rough OK. | AARONR | AARONR | | ER | C | 7777841 |
EAGLE EYE ELECTRIC SERVICES LLC | ESP | P | 03/17/2023 | --------------------------------2 VAV's are existing, just need to make sure work under this permit does not make the working clearance to the units any more restrictive than they currently are. Also verify service disconnect in place for each------------------------------ | DEAN | DEAN | | ESP | P | 7690639 |
EAGLE EYE ELECTRIC SERVICES LLC | ER | C | 03/06/2023 | Wall rough OK. --- Units in ceiling will need proper working clearance in front of access doors come ceiling inspection. | AARONR | AARONR | | ER | C | 7678217 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 07/24/2023 | MECHANICAL FINAL--------------------COMPLETE. | TREVORH | TREVORH | | H= | C | 7805847 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 07/24/2023 | TEST AND BALANCE REPORT RECEIVED SEE IMAGES MECHANICAL FINAL PENDING ----------------------------VERIFICATION OF THERMOSTATS. | TREVORH | TREVORH | | H= | P | 7805564 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 05/31/2023 | ALL SUPPLY NEW RIGID DUCT, FLEX DUCT AND REGISTERS OK / ALL RETURN AIR LAY-IN GRILLS OK / FINAL PENDING: NEED THERMOSTATS INSTALLED / NEED TEST AND BALANCE REPORT/ | LIDO | LIDO | | H= | P | 7759068 |
GOLD RUSH PLUMBING | P= | P | 07/11/2023 | RBD approved drawing splice as noted on 6-28-23 still required to complete plumbing permit , rest ok | FRANKM | FRANKM | | P= | P | 7794591 |
GOLD RUSH PLUMBING | P= | P | 07/10/2023 | Terminate water heater T&P to approved location / no hot water / insulate H2O / approved splice as noted on 6-28-23 still required | FRANKM | FRANKM | | P= | P | 7793312 |
GOLD RUSH PLUMBING | PTO | C | 06/28/2023 | Complete PB & Insulate H2O by final | FRANKM | FRANKM | | PTO | C | 7785331 |
GOLD RUSH PLUMBING | PB | C | 04/05/2023 | Splice reflecting current install required @ final (insta-hot wtr htr add / H2O piping revision / sink relocate) Note : AAV @ sink / check overhead H2O insulation @ final | FRANKM | FRANKM | | PB | C | 7707633 |
GOLD RUSH PLUMBING | XPS | P | 12/08/2023 | PLAN SPLICE: (No Fee) by: SHANEN for Plumbing: Clouded revisions only: Adjusted sheet P1. | SHANEN | SHANEN | | XPS | P | 7939496 |
B&C CONSTRUCTION | XBS | T | 12/08/2023 | PLAN SPLICE FEE: $50 by: BPHILLIPS for Construction: Minor floor plan revisions. | BPHILLIPS | BPHILLIPS | | XBS | T | 7939384 |
B&C CONSTRUCTION | XPS | T | 03/30/2023 | PAID (REC#1945214) PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Clouded revisions only: Adjusted sheet P1. | SHANEN | SHANEN | | XPS | T | 7702242 |