INNOVATIVE CONSTRUCTION, INC. | B= | C | 08/16/2023 | | ERAMIREZ | ERAMIREZ | | B= | C | 7828570 |
INNOVATIVE CONSTRUCTION, INC. | B= | P | 05/25/2023 | Missing tempered glazing from offices to test lab area. Rest okay pending other final inspections. -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), DUKES ELECTRIC, INC Electrical Final Inspection is not Completed yet, RIAL HEATING AND AIR CONDITIONING, INC. Mechanical Final Inspection is not Completed yet, TRI-STAR MECHANICAL Plumbing Final Inspection is not Completed yet. | ERAMIREZ | ERAMIREZ | | B= | P | 7755376 |
INNOVATIVE CONSTRUCTION, INC. | BFR | P | 04/19/2023 | engineer letter for 3rd party structural steel welding and bolting on file / frame OK pending other required inspections | LONNYS | LONNYS | | BFR | P | 7720199 |
INNOVATIVE CONSTRUCTION, INC. | BFR | P | 04/18/2023 | provide 3rd party observation for all structural steel welding and bolt / interior light gauge steel framing at OHD infill framing OK | LONNYS | LONNYS | | BFR | P | 7719193 |
INNOVATIVE CONSTRUCTION, INC. | BFN | C | 04/10/2023 | All required paperwork on file. | ERAMIREZ | ERAMIREZ | | BFN | C | 7711045 |
INNOVATIVE CONSTRUCTION, INC. | BSP | P | 04/10/2023 | Open hole with pilaster observation on file. | ERAMIREZ | ERAMIREZ | | BSP | P | 7711044 |
INNOVATIVE CONSTRUCTION, INC. | BFR | P | 04/04/2023 | Engineer letters on file for open hole 2500 psf and East footing / Per letter the West footing corrections still need to be noted as completed and observed in a separate letter | ADAML | ADAML | | BFR | P | 7706071 |
INNOVATIVE CONSTRUCTION, INC. | BFR | P | 04/03/2023 | still need to provide open hole and eng observation letter for footings, pending completion of all other required inspections, interior non rated, non bearing framing okay | BOBF | BOBF | | BFR | P | 7705357 |
INNOVATIVE CONSTRUCTION, INC. | BFR | P | 03/08/2023 | Pending all other required inspections / Provide open hole and 3rd party observation for two new footings per 5 S1 by OH door / All metal framing OK throughout except for framing by OH door that still needs to be constructed / Reviewed accessible elements | ADAML | ADAML | | BFR | P | 7681187 |
DUKES ELECTRIC, INC | E= | C | 05/26/2023 | up load pictures of the two missing panel covers with the panel schedule filled out | CRAIGS | CRAIGS | | E= | C | 7756051 |
DUKES ELECTRIC, INC | ER | C | 05/26/2023 | | CRAIGS | CRAIGS | | ER | C | 7756050 |
STILSON ELECTRIC SYSTEMS, INC. | E= | C | 05/25/2023 | FIRE ALARM INSPECTION: | JOHNN | JOHNN | | E= | C | 7754428 |
STILSON ELECTRIC SYSTEMS, INC. | ER | C | 05/25/2023 | FIRE ALARM INSPECTION: | JOHNN | JOHNN | | ER | C | 7754422 |
STILSON ELECTRIC SYSTEMS, INC. | E= | C | 05/25/2023 | FIRE ALARM INSPECTION: | JOHNN | JOHNN | | E= | C | 7754423 |
DUKES ELECTRIC, INC | EP | P | 05/08/2023 | PANELS HP 1 and LP1 and SEC 2 and CMP - 6 all ok note verify labeling per RBD handout | CRAIG | CRAIG | | EP | P | 7738046 |
DUKES ELECTRIC, INC | ER | P | 05/08/2023 | xfmr A and xfmr for lighting control panel ok | CRAIG | CRAIG | | ER | P | 7738043 |
DUKES ELECTRIC, INC | ER | P | 04/10/2023 | all walls,ok/ Looked at A transformer: needs sec disco within 25' of transformer, also need #2cu to cold water, has #4, label where fed from/ | JOHNN | JOHNN | | ER | P | 7711207 |
DUKES ELECTRIC, INC | ER | P | 03/16/2023 | Need north east wall -----------FA will be cut into walls | BRETC | BRETC | | ER | P | 7688939 |
DUKES ELECTRIC, INC | ER | R | 03/13/2023 | All walls minus North East walls / -------------------Electrical Rough ok, FA not complete ---------------do not sheetrock--------------- / | BRETC | BRETC | | ER | R | 7685075 |
DUKES ELECTRIC, INC | ESL | C | 02/27/2023 | 4 - 1" PVC in center / 7 - 1" PVC floor boxes | BRETC | BRETC | | ESL | C | 7670951 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 06/07/2023 | SMOKE DUCT DETECTORS, EXISTING REMOTE INDICATORS AND THERMOSTATS CONFIRMED. | MARKB | MARKB | | H= | C | 7765907 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 05/24/2023 | FINAL PENDING - Need to complete on site inspections per previous inspection notes. ENGINEER APPROVED TEST AND BALANCE REPORT RECEIVED - SEE IMAGES | MARKB | MARKB | | H= | P | 7752915 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 03/24/2023 | FOR FINAL - Need to confirm smoke duct detector with indication are installed. Need to see all thermostats installed. Provide test ad balance report. NEW EXPOSED DUCT AND DIFFUSERS ARE INSTALLED PER PLAN | MARKB | MARKB | | HD | P | 7697892 |
TRI-STAR MECHANICAL | P= | C | 06/14/2023 | P=ok | FRANKM | FRANKM | | P= | C | 7771643 |
TRI-STAR MECHANICAL | PTO | C | 03/23/2023 | -OK on DWV & H2O to S1 sink in kitchenette 152 Note AAV @ S1 sink | FRANKM | FRANKM | | PTO | C | 7696542 |
TRI-STAR MECHANICAL | PTO | P | 03/23/2023 | SPLICE FOR RELOCATED FIXTURES APPROVED | LEE | LEE | | PTO | P | 7695720 |
TRI-STAR MECHANICAL | PTO | P | 02/15/2023 | INSPECTED DWV AND H20 FOR FUTURE D/F AND UTILITY SINK -- ((( WILL NEED PLANS REVISED TO SHOW THEESE FIXTURES ON A DIFFERENT WALL ))) -- COMMON AAV IN WALL ABOVE FIXTURES | LEE | LEE | | PTO | P | 7662761 |
TRI-STAR MECHANICAL | PB | C | 02/15/2023 | FOR 2" DRAIN TO BREAK SINK | LEE | LEE | | PB | C | 7662759 |
DUKES ELECTRIC, INC | XES | T | 04/27/2023 | PAID (REC#1952623): PLAN SPLICE FEE: $50 by: DANIELG for Electrical: Revised one-line, panel schedule, and updated floor plan. | DANIELG | DANIELG | | XES | T | 7729231 |
DUKES ELECTRIC, INC | XES | P | 02/23/2023 | PLAN SPLICE: (No Fee) by: DANIELG for Electrical: As built. | DANIELG | DANIELG | | XES | P | 7668565 |
TRI-STAR MECHANICAL | XPS | T | 02/23/2023 | PAID (REC#1939344): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta 2 revisions: Adjusted sheet P1.0. | SHANEN | SHANEN | | XPS | T | 7668307 |
RIAL HEATING AND AIR CONDITIONING, INC. | XMS | P | 02/23/2023 | PLAN SPLICE: (No Fee) by: JUSTINC for Mechanical: Revised backgrounds and layout with CFM | JUSTINC | JUSTINC | | XMS | P | 7668293 |
INNOVATIVE CONSTRUCTION, INC. | XBS | T | 02/23/2023 | PAID (REC#1935209): PLAN SPLICE FEE: $50 by: DANM for Construction: Reconfigured office area layout | DANM | DANM | | XBS | T | 7668286 |