GORDON CONSTRUCTION COMPANY, INC | B= | C | 08/14/2024 | | JANE | JANE | | B= | C | 8179775 |
GORDON CONSTRUCTION COMPANY, INC | B= | P | 07/15/2024 | Temp CO: need zoning. ( Expires: 8/14/2024 12:00:00 AM) | JANE | JANE | | B= | P | 8146467 |
GORDON CONSTRUCTION COMPANY, INC | BE | T | 07/15/2024 | PAID (REC#2085257): tco | JANE | JANE | | BE | T | 8146445 |
GORDON CONSTRUCTION COMPANY, INC | B= | P | 07/11/2024 | Final items corrected pending all other finals. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yetRequest inspection through PPRBD system or contact 719-385-5982 for zoning questions, External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977). | ADAML | ADAML | | B= | P | 8144025 |
GORDON CONSTRUCTION COMPANY, INC | B= | P | 07/10/2024 | FINAL ITEMS - 201/202 - Both units missing interior hand rails on lower two flights / 202- Stair window needs to be tempered / All other final items OK pending all other required finals -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yetRequest inspection through PPRBD system or contact 719-385-5982 for zoning questions, External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977). | ADAML | ADAML | | B= | P | 8142304 |
GORDON CONSTRUCTION COMPANY, INC | B= | P | 07/10/2024 | Air Leakage Testing Report ( Blower Door ) on file for all units -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yetRequest inspection through PPRBD system or contact 719-385-5982 for zoning questions, External Agency Inspection N= by ENGINEERING is not Completed yet (Contact: City Engineering Inspections 719-385-5977). | ADAML | ADAML | | B= | P | 8141874 |
GORDON CONSTRUCTION COMPANY, INC | BIN | P | 06/18/2024 | Per previous discussion attic insulation will be verified at final / Provide ladder at access at that time | ADAML | ADAML | | BIN | P | 8120676 |
GORDON CONSTRUCTION COMPANY, INC | BIN | P | 06/12/2024 | Missing attic accesses in ceiling of attic space above 201/202 in all buildings / Provide ladder at final to inspect insulation in attic | ADAML | ADAML | | BIN | P | 8114860 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 05/16/2024 | Consult only / No inspections | ADAML | ADAML | | BSP | P | 8086229 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 04/17/2024 | Deck posts - One of the landing posts does not have full bearing on pier / All other framing OK / 001 - Drywall OK on rated soffit | ADAML | ADAML | | BSP | P | 8055650 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 04/04/2024 | METAL SOFFIT FRAMING / UNIT 001 / Observed framing at unit referenced. | MATTHEWA | MATTHEWA | | BSP | P | 8043382 |
GORDON CONSTRUCTION COMPANY, INC | BSP | R | 04/02/2024 | Not ready for metal soffit framing in 001 | ADAML | ADAML | | BSP | R | 8039719 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 03/22/2024 | PENETRATIONS AT CEILINGS / ALL UNITS / Observed penetrations at areas referenced. / Still need to inspect framing and gyp at dropped plumbing in unit 001. | MATTHEWA | MATTHEWA | | BSP | P | 8031026 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 03/20/2024 | 001- Will need to inspect framing and both layers drywall for rated drop in living area due to plumbing / All other units OK for 2nd layer drywall on ceilings | ADAML | ADAML | | BSP | P | 8027376 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 03/18/2024 | 1st layer drywall OK on ceilings and drywall OK on walls | ADAML | ADAML | | BSP | P | 8024737 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 03/12/2024 | RC on ceilings corrected | ADAML | ADAML | | BSP | P | 8021317 |
GORDON CONSTRUCTION COMPANY, INC | BSP | R | 03/11/2024 | Inspection for RC field cancelled per Rick | ADAML | ADAML | | BSP | R | 8020001 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 03/08/2024 | RC / ALL UNITS / Incomplete fastening at RC at floor ceiling assemblies per L589. / Reviewed L589, U305, U341, and RC installation with Gordon rep. | MATTHEWA | MATTHEWA | | BSP | P | 8018310 |
GORDON CONSTRUCTION COMPANY, INC | BIN | P | 03/08/2024 | INSULATION / CRAWL SPACE / Observed insulation at crawl space walls. | MATTHEWA | MATTHEWA | | BIN | P | 8018301 |
GORDON CONSTRUCTION COMPANY, INC | BIN | P | 03/06/2024 | INSULATION / ALL UNITS / Observed insulation per approved design. / Still need to inspect RC and crawl space insulation. / Need to provide 3rd party installer certificate for blown in insulation. | MATTHEWA | MATTHEWA | | BIN | P | 8016343 |
GORDON CONSTRUCTION COMPANY, INC | BFR | P | 02/29/2024 | Frame items completed / Do not need a structural steel letter for the beam in 001 because they are just thru bolts | ADAML | ADAML | | BFR | P | 8009899 |
GORDON CONSTRUCTION COMPANY, INC | BFR | P | 02/29/2024 | Engineer letter on file for stair landing ledgers / Will perform site visit for remaining items | ADAML | ADAML | | BFR | P | 8009617 |
GORDON CONSTRUCTION COMPANY, INC | BFR | R | 02/27/2024 | Field canceled per Rick | ADAML | ADAML | | BFR | R | 8007187 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 02/26/2024 | DECKS AND HOLD DOWNS / ALL UNITS / Observed deck framing per approved design. / Observed all hold downs per approved design. | MATTHEWA | MATTHEWA | | BSP | P | 8006695 |
GORDON CONSTRUCTION COMPANY, INC | BFR | P | 02/23/2024 | FRAME / ALL UNITS / Unit 001 - Need to complete fire blocking. / Unit 101 - Need to complete fire blocking. / Unit 102 - Need to complete fire blocking. / Unit 201 - 1) Need to complete fire blocking. 2) Unable to locate ledger fastening requirements at ledger at stair landing. / Unit 202 - 1) Unable to locate ledger fastening requirements at ledger at stair landing. / Unit 103 - 1) Need to complete fire blocking. 2) Unable to locate ledger fastening requirements. 3) Missing MTS strap at T15Y truss at common wall above stairs. / Still need to inspect interior hold downs and decks. / Need to provide 3rd party observation letter for structural steel, welding, and bolting. | MATTHEWA | MATTHEWA | | BFR | P | 8004313 |
GORDON CONSTRUCTION COMPANY, INC | BSP | R | 02/08/2024 | Inspection changed from BFR to BSP. / Reviewed trusses pending stamp on approved plans with contractor over phone. / No inspection performed. | MATTHEWA | MATTHEWA | | BSP | R | 7990443 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 02/06/2024 | Observed deck piers per approved design. | MATTHEWA | MATTHEWA | | BSP | P | 7988793 |
GORDON CONSTRUCTION COMPANY, INC | BIN | P | 11/07/2023 | Insulation OK in party walls / This does not include stair walls or the small rated wall on the rear 2nd story for the shared deck ) | ADAML | ADAML | | BIN | P | 7911027 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 10/31/2023 | Porch lids and posts OK | ADAML | ADAML | | BSP | P | 7904475 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 10/18/2023 | Exterior shear nailing and straps OK | ADAML | ADAML | | BSP | P | 7891856 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 09/27/2023 | 2nd Floor - OSB OK on both inside faces of common wall | ADAML | ADAML | | BSP | P | 7869523 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 09/19/2023 | 1st floor common wall shear wall- plywood attached to inside face of each wall 6"o.c. ok/ discussed separation of units at crawl space | SHAUN | SHAUN | | BSP | P | 7861542 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 09/13/2023 | Inspection was for floor beams and connections however none of the steel columns are installed yet so we will still have to verify those as well as the steel beam splices per 9 S001 / Joist hangers and anchor bolts OK | ADAML | ADAML | | BSP | P | 7855172 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 05/11/2023 | Discussed drainage requirement per soil / On site walk around foundation perimeter / Training with ShaunT | FERNANDOH | FERNANDOH | | BSP | P | 7742109 |
GORDON CONSTRUCTION COMPANY, INC | BFD | P | 05/11/2023 | drain around portions of walkout and to daylight at south west corner/ dampproofing ok/ training with FernandoH | SHAUN | SHAUN | | BFD | P | 7742108 |
GORDON CONSTRUCTION COMPANY, INC | BFN | C | 04/27/2023 | | SHAUN | SHAUN | | BFN | C | 7728302 |
GORDON CONSTRUCTION COMPANY, INC | BFT | C | 04/27/2023 | open hole on file -- 2,400 PSF -- 10% / footing and foundation observation on file - ufer noted / foundation design on file (bearing capacity verified) | SHAUN | SHAUN | | BFT | C | 7728296 |
GORDON CONSTRUCTION COMPANY, INC | BSP | P | 04/26/2023 | complete foundation inspections/ dampproofing ok | SHAUN | SHAUN | | BSP | P | 7728052 |
GORDON CONSTRUCTION COMPANY, INC | BFI | C | 04/25/2023 | 24" R-10 at walkout ok | SHAUN | SHAUN | | BFI | C | 7725890 |
BJ COMPANY, LLC | E= | C | 07/09/2024 | FIRE ALARM INSPECTION: Fire Alarm E= - OK / | DAVIDRO | DAVIDRO | | E= | C | 8141264 |
WINTERS ELECTRIC, INC. | E= | C | 07/08/2024 | Unit 001 water heater electrical - OK / E= - OK / | DAVIDRO | DAVIDRO | | E= | C | 8139993 |
WINTERS ELECTRIC, INC. | E= | P | 07/02/2024 | Unit 001 water heater not complete / Outside receptacles - OK /
AC Units: 001: Min 15.1, Max 25, 20 amp breaker / 101: Min 15.1, Max 25, 20 amp breaker / 102: Min 15.1, Max 25, 20 amp breaker / 103: Min 15.1, Max 25, 20 amp breaker / 201: Min 15.6, Max 25, 20 amp breaker / 202: Min 15.6, Max 25, 20 amp breaker / | DAVIDRO | DAVIDRO | | E= | P | 8136668 |
WINTERS ELECTRIC, INC. | E= | P | 06/06/2024 | 2602 Units: 101, 102, 103, 201, 202 - OK / Units 001, House need to be inspected still / At final, confirm all data plate covers have been installed / | DAVIDRO | DAVIDRO | | E= | P | 8110117 |
WINTERS ELECTRIC, INC. | ER | C | 04/12/2024 | Units 001, 102, 103, 201, 202 for building 2602 - OK | DAVIDRO | DAVIDRO | | ER | C | 8051736 |
WINTERS ELECTRIC, INC. | ESP | C | 03/07/2024 | Unit 001 is labeled as a walkout basement, will need GFCI protection / | DAVIDRO | DAVIDRO | | ESP | C | 8017850 |
WINTERS ELECTRIC, INC. | ES | C | 03/07/2024 | Commercial Service: 400A 3PH Commercial service / OK to set meter for units 101, 102, 103, 201, 202, 001 and House / | DAVIDRO | DAVIDRO | | ES | C | 8017848 |
WINTERS ELECTRIC, INC. | EP | C | 01/30/2024 | Panels for units ok | CHIPO | CHIPO | | EP | C | 7981389 |
WINTERS ELECTRIC, INC. | ER | P | 01/30/2024 | Still need drop ceiling areas and service wall where feeders needs to go out - rough in for other areas ok | CHIPO | CHIPO | | ER | P | 7981385 |
BJ COMPANY, LLC | ER | C | 01/30/2024 | FIRE ALARM INSPECTION: Fire alarm rough in for units ok | CHIPO | CHIPO | | ER | C | 7981382 |
CBA MECHANICAL LLC | H= | C | 06/07/2024 | FINAL FOR MECHANICAL CONTRACTOR | BILLS | BILLS | | H= | C | 8111075 |
CBA MECHANICAL LLC | HD | P | 04/15/2024 | ABOVE CEILING/BELOW PRE-ROCK SUPPLY, RETURN EXHAUST AND DRYER DUCT OK IN UNITS 001, 101, 102, 103, 202 & 201. | MARKB | MARKB | | HD | P | 8052961 |
CBA MECHANICAL LLC | HRP | P | 01/22/2024 | LINESET PRESSURE TESTS (6) OK | BILLS | BILLS | | HRP | P | 7973796 |
CBA MECHANICAL LLC | HD | P | 01/19/2024 | UNIT #103-- DUCT ROUGH OK. ALL OTHER UNITS-- ABOVE PRE-ROCK PIPING AND ROOF PENETRATIONS OK AT ALL UNITS. | BILLS | BILLS | | HD | P | 7972844 |
CBA MECHANICAL LLC | HRP | P | 01/19/2024 | NO PRESSURE TESTS TODAY. ALL UNITS--- LINESET SUPPORTS, INSULATION, AND NAIL PROTECTION OK. | BILLS | BILLS | | HRP | P | 7972843 |
OSCAR PLUMBING LLC | P= | C | 07/09/2024 | Ok | DANR | DANR | | P= | C | 8140762 |
OSCAR PLUMBING LLC | PTO | C | 03/19/2024 | Hose Bib @ Lower Mechanical Closet OK ( Freeze Pro By Final ) Corrections Made
Still Need Engineer Letter For AAV @ Kitchen's
| TRAVISR | TRAVISR | | PTO | C | 8025783 |
OSCAR PLUMBING LLC | PTO | P | 02/06/2024 | In Unit DWV, H20, & Insulation OK @ Unit - 001, 101, 102, 103
Need To Move Hot H20 Line @ Attic Level Hot H20 @ Lav For Freeze Protection @ Unit - 102 & 103 Need Letter From Engineer For Unit 103 Kitchen Venting Method - VTR Called For On Plans - AAV Instead Hose Bib Incomplete @ Unit 001 | TRAVISR | TRAVISR | | PTO | P | 7987812 |
OSCAR PLUMBING LLC | PB | P | 06/27/2023 | BUILDING 1 -
Under Ground DWV & 4" Stub To Crawl Space OK / Plans Page P4 | TRAVISR | TRAVISR | | PB | P | 7783131 |
GORDON CONSTRUCTION COMPANY, INC | XBS | T | 02/21/2024 | PAID (REC#2036282): PLAN SPLICE FEE: $50 by: BPHILLIPS for Construction: Provided deferred roof trusses. | BPHILLIPS | BPHILLIPS | | XBS | T | 8001341 |
GORDON CONSTRUCTION COMPANY, INC | XBS | T | 02/01/2024 | PAID (REC#2030106): PLAN SPLICE FEE: $50 by: BPHILLIPS for Construction: Removing bedroom window and replacing it with a entry door. | BPHILLIPS | BPHILLIPS | | XBS | T | 7983588 |