ALEXANDHER BUILDING CO, INC. | B= | C | 07/24/2023 | | ERAMIREZ | ERAMIREZ | | B= | C | 7805720 |
ALEXANDHER BUILDING CO, INC. | B= | P | 07/06/2023 | Temp CO: extension ( Expires: 8/5/2023 12:00:00 AM) | JANE | JANE | | B= | P | 7790360 |
ALEXANDHER BUILDING CO, INC. | BE | T | 06/28/2023 | PAID (REC#1965729): TCO | JANE | JANE | | BE | T | 7785387 |
ALEXANDHER BUILDING CO, INC. | B= | P | 06/02/2023 | Temp CO: needs finals. ( Expires: 7/2/2023 12:00:00 AM) | JANE | JANE | | B= | P | 7761938 |
ALEXANDHER BUILDING CO, INC. | B= | T | 06/02/2023 | PAID (REC#1959006): TCO. Additional Inspections Required (computer generated): EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, AIRTECH MECHANICAL, INC. Mechanical Final Inspection is not Completed yet. | JANE | JANE | | B= | T | 7761711 |
ALEXANDHER BUILDING CO, INC. | B= | P | 05/31/2023 | Building final OK pending other internal/external finals /. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: rdassero@springsgov.com or 385-5982, x2), External Agency Inspection FHZ= by FIREDEPT is not Completed yet, EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, AIRTECH MECHANICAL, INC. Mechanical Final Inspection is not Completed yet. | ERAMIREZ | ERAMIREZ | | B= | P | 7758116 |
ALEXANDHER BUILDING CO, INC. | B= | P | 04/26/2023 | Missing isle shelving to check for accessibility route and checkout counters. / Complete other final inspections. / -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection FHZ= by FIREDEPT is not Completed yet, EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, AIRTECH MECHANICAL, INC. Mechanical Final Inspection is not Completed yet. | ERAMIREZ | ERAMIREZ | | B= | P | 7727369 |
ALEXANDHER BUILDING CO, INC. | BFR | P | 03/27/2023 | Attach electrical and mechanical to permit. / Complete other rough inspections. / Reviewed Accessible Elements due to change of Occupancy, the following items will need to be addressed by final: both bathrooms sink height to be a maximum of 34" (currently 35"), woman accessible bathroom flush control to be on open side, men's primary door to restroom to have a minimum of 18" on pull side and service counter height to be a maximum from floor to top of counter 36" (currently 44"). / Framing okay for interior non-bearing walls and new overhead door opening pending other rough inspections. / | ERAMIREZ | ERAMIREZ | | BFR | P | 7698699 |
EL PASO ELECTRIC, LLC. | E= | C | 06/06/2023 | MC installed ok / | MIGUEL | MIGUEL | | E= | C | 7763263 |
EL PASO ELECTRIC, LLC. | E= | P | 05/25/2023 | can not use SO chord for permanent wiring to outlets on top of shelve North of paint station / rest ok / | MIGUEL | MIGUEL | | E= | P | 7755141 |
EL PASO ELECTRIC, LLC. | E= | R | 05/08/2023 | not ready / | MIGUEL | MIGUEL | | E= | R | 7738711 |
EL PASO ELECTRIC, LLC. | ER | P | 05/08/2023 | N. W wall and S. wall ok / still waiting on N.E. and E. walls and multiple exit signs and frog eyes / | MIGUEL | MIGUEL | | ER | P | 7738708 |
EL PASO ELECTRIC, LLC. | E= | R | 04/27/2023 | not ready / | MIGUEL | MIGUEL | | E= | R | 7729472 |
EL PASO ELECTRIC, LLC. | E= | R | 04/21/2023 | not ready / | MIGUEL | MIGUEL | | E= | R | 7723393 |
EL PASO ELECTRIC, LLC. | ER | P | 04/21/2023 | MC and conduit at sales and paint booth only / | MIGUEL | MIGUEL | | ER | P | 7723385 |
AIRTECH MECHANICAL, INC. | H= | C | 07/21/2023 | TAB REPORT ACCEPTED | NICKE | NICKE | | H= | C | 7804459 |
AIRTECH MECHANICAL, INC. | H= | P | 07/19/2023 | ATTACHED REVISED TEST & BALANCE REPORT (REJECTED) NEEDS TO REFLECT THE ENTIRE SPLICED VENTILATION SCHEDULE (7-7-23/M0.2) FOR ALL RTU's & AHU's. FINAL PENDING-- TEST & BALANCE REPORT. | PAULO | PAULO | | H= | P | 7801826 |
AIRTECH MECHANICAL, INC. | H= | P | 06/26/2023 | Received Test & Balance Report (REJECTED/MISSING OUTSIDE AIR VALUES FOR AHU-1&2, RTU-1,2&3, RTU-1 OUTSIDE AIR IS OUTSIDE THE 10% +/- ALLOWED (EQUIPMENT SCHEDULE SHOWS 500 CFM's). ENIGNEER TO CLARIFY CFM's FOR RTU-1&2 & OUTSIDE AIR AS THE EQUIPMENT SCHEDULE SHOWS DIFFERENT VALUES THAN THE OUTSIDE AIR SCHEDULE. | PAULO | PAULO | | H= | P | 7781731 |
AIRTECH MECHANICAL, INC. | H= | P | 06/05/2023 | CONTRACTOR MOVED DATE OF TAB REPORT. FINAL PENDING-- TEST & BALANCE REPORT. | PAULO | PAULO | | H= | P | 7762179 |
AIRTECH MECHANICAL, INC. | H= | P | 06/02/2023 | FINAL PENDING-- TEST & BALANCE REPORT. | PAULO | PAULO | | H= | P | 7761893 |
AIRTECH MECHANICAL, INC. | H= | P | 04/06/2023 | FINAL PENDING-- TEST & BALANCE REPORT. Note / Flex & Diffuser ok. | PAULO | PAULO | | H= | P | 7709185 |
AIRTECH MECHANICAL, INC. | XMS | T | 07/07/2023 | PAID (REC#1970654): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised ventilation | JUSTINC | JUSTINC | | XMS | T | 7791804 |