SUNSET DREAM HOMES, INC | BIN | C | 01/31/2024 | | BRIANB | BRIANB | | BIN | C | 7982681 |
SUNSET DREAM HOMES, INC | BFR | C | 01/31/2024 | observed corrections from previous inspection | BRIANB | BRIANB | | BFR | C | 7982677 |
SUNSET DREAM HOMES, INC | BSP | P | 01/31/2024 | Engineer letter on file for framing modifications / | ERIKK | ERIKK | | BSP | P | 7982295 |
SUNSET DREAM HOMES, INC | BFR | R | 01/24/2024 | 1. Need design professional clarification of location changes of garage windows from rear wall to east and west walls / 2. Missing blocking at garage door brackets / 3. Missing roof jack for B vent for dry in / 4. Need clarification for use of hangers with titen screws in place of beam pockets of LVL beams at stair opening / 5. Hangers missing shear nails at front porch double beam / Rear cover lid okay // Note: Still need to inspect deck frame and front and rear porch posts as BSP at later date / Need fire protection of floor material installation certificate and test report by final | TRENTP | TRENTP | | BFR | R | 7976294 |
SUNSET DREAM HOMES, INC | BLA | P | 11/29/2023 | Lath for house okay, inspection comment states lath to be done on deck columns at later date | TRENTP | TRENTP | | BLA | P | 7930099 |
SUNSET DREAM HOMES, INC | BFI | C | 10/09/2023 | Engineer observation of foundation insulation on file | ANGELW | ANGELW | | BFI | C | 7881144 |
SUNSET DREAM HOMES, INC | BFI | R | 10/06/2023 | No foundation insulation observed | ANGELW | ANGELW | | BFI | R | 7880634 |
SUNSET DREAM HOMES, INC | BFD | C | 10/06/2023 | Soils report on file / Engineer observation of foundation drain and damp proofing on file | ANGELW | ANGELW | | BFD | C | 7879743 |
SUNSET DREAM HOMES, INC | BFT | C | 10/05/2023 | open hole on file -- 3000 PSF -- usable -- 10% / footing and foundation observation on file - ufer noted / foundation design on file (bearing capacity verified) / | ANGELW | ANGELW | | BFT | C | 7878291 |
SUNSET DREAM HOMES, INC | BFN | C | 10/05/2023 | open hole on file -- 3000 PSF -- usable -- 10% / footing and foundation observation on file - ufer noted / foundation design on file (bearing capacity verified) / | ANGELW | ANGELW | | BFN | C | 7878289 |
SUNSET DREAM HOMES, INC | BFN | P | 10/04/2023 | Provide foundation design with verifiable bearing pressure / open hole on file -- 3000 PSF -- usable -- 10% / footing and foundation observation on file - ufer noted / | ANGELW | ANGELW | | BFN | P | 7875910 |
SUNSET DREAM HOMES, INC | BFT | P | 10/04/2023 | Provide foundation design with verifiable bearing pressure / open hole on file -- 3000 PSF -- usable -- 10% / footing and foundation observation on file - ufer noted / | ANGELW | ANGELW | | BFT | P | 7875909 |
SUNSET DREAM HOMES, INC | BFT | P | 09/12/2023 | Changed to BFT / Still need footing observation / Soils report on file | TRENTP | TRENTP | | BFT | P | 7853307 |
SUNSET DREAM HOMES, INC | BFD | P | 09/12/2023 | Need to complete BFT and BFN / Engineer letter for perimeter drain on file -- Damp proofing noted / Only last two pages of soils report provided, need to provide full soils report | TRENTP | TRENTP | | BFD | P | 7853102 |
SUNSET DREAM HOMES, INC | BFT | P | 09/12/2023 | Need to provide footing observation and full soils report, only last two pages of report provided / Open hole on file, 3000 - usable - 10% / Note: Need to complete BFN | TRENTP | TRENTP | | BFT | P | 7853098 |
SUNSET DREAM HOMES, INC | BFI | P | 03/27/2023 | AUTHORIZED INSPECTION BY ENGINEER | JACKIEP | JACKIEP | JACKIEP | BFI | P | 7698467 |
SUNSET DREAM HOMES, INC | BFD | P | 03/27/2023 | AUTHORIZED INSPECTION BY ENGINEER | JACKIEP | JACKIEP | JACKIEP | BFD | P | 7698466 |
SUNSET DREAM HOMES, INC | BFT | P | 03/27/2023 | AUTHORIZED INSPECTION BY ENGINEER | JACKIEP | JACKIEP | JACKIEP | BFT | P | 7698465 |
SUNSET DREAM HOMES, INC | BFN | P | 03/27/2023 | AUTHORIZED INSPECTION BY ENGINEER | JACKIEP | JACKIEP | JACKIEP | BFN | P | 7698464 |
LENZ ELECTRIC, INC. | ES | C | 02/12/2024 | Residential Underground: 200-amp 3 Wire New Residence ok NEED METER SEAL / | GREGM | GREGM | | ES | C | 7993334 |
LENZ ELECTRIC, INC. | ES | R | 02/09/2024 | ufer gec must land on neutral bar of disconnect install bond jumpers that are provided to bond system | BRET | BRET | | ES | R | 7992446 |
LENZ ELECTRIC, INC. | ES | R | 01/19/2024 | Residential Underground: NOT READY ----- | GREGM | GREGM | | ES | R | 7972064 |
LENZ ELECTRIC, INC. | ER | C | 01/19/2024 | ER OK ------ #1 TO SUB PANEL --- #6CU RANGE BASEMENT----- REV UFER ---- NO MCC --- #10 A/C COOK TOP MAIN LEVEL -----P | GREGM | GREGM | | ER | C | 7972062 |
LENZ ELECTRIC, INC. | EUG | C | 08/21/2023 | 4/0 urd | TOMC | TOMC | | EUG | C | 7832122 |
GENE'S HEATING AND AIR LLC | H= | P | 04/24/2024 | NEED 2-LB LETTER FROM GAS PURVEYOR / MISSING MEDIUM PRESSURE STICKERS ON HOUSE RISER / INSTALL THE FURNACE 120V SWITCHES (X2) / CONTRACTOR TO ATTACH PICTURE OF CORRECTION TO AN INSPECTION REQUEST ONCE THE 2-LB LETTER HAS BEEN ATTACHED. Whole house ventilation being achieved through exhaust fan located in powder room / NOTE / Finished basement / Direct vent furnace x2 / Outside air with damper to furnace return x2 / A/C complete / Mechanical room meets 50 to 1 for combustion air / | BILLS | BILLS | | H= | P | 8063036 |
GENE'S HEATING AND AIR LLC | H= | P | 04/16/2024 | 2LB LETTER OF APPROVAL IS REQUIRED / MISSING MEDIUM PRESSURE STICKERS ON HOUSE RISER / MISSING BOTH FURNACE TERMINATIONS (Ensure they are a minimum of 12'' above grade) / INSTALL THE FURNACE GAS GROMMETS (X2) / INSTALL THE FURNACE 120V SWITCHES (X2) / LABEL WHOLE HOUSE VENTILATION SWITCH / OK TO ATTACH PICTURE OF CORRECTION TO AN INSPECTION REQUEST / Whole house ventilation being achieved through exhaust fan located in powder room / NOTE / Finished basement / Direct vent furnace x2 / Outside air with damper to furnace return x2 / A/C complete / Mechanical room meets 50 to 1 for combustion air / | SAMS | SAMS | | H= | P | 8053996 |
O.M.A.G.M., INC. | HC | C | 01/30/2024 | RELEASE 2 LB METER | SAMS | SAMS | | HC | C | 7981595 |
O.M.A.G.M., INC. | HO | C | 01/30/2024 | OK TO COVER / By final provide the 2 lb letter of approval and install the regulators and medium pressure stickers / 10 lb test ok / Added 90' of 3/4'' PE with tracer wire from meter to house / | SAMS | SAMS | | HO | C | 7981592 |
GENE'S HEATING AND AIR LLC | HC | C | 01/05/2024 | RELEASE METER | SAMS | SAMS | | HC | C | 7961100 |
GENE'S HEATING AND AIR LLC | HRR | C | 01/05/2024 | | SAMS | SAMS | | HRR | C | 7961098 |
GENE'S HEATING AND AIR LLC | HRR | P | 01/03/2024 | Multiple supply and return ducts undersized, install per plan / Verify furnace vent terminations clearance to grade at final / Whole house ventilation being achieved through exhaust fan located in powder room / Verify whole house ventilation switch location at final / NOTE / Finished basement / Outside air with damper to furnace return x 2 / Direct vent furnace x 2 / A/C rough, coil and lineset. x 1 / | CASEYM | CASEYM | | HRR | P | 7958899 |
ROCKY MOUNTAIN RADIANT HEATING & PLUMBING, INC. | HI | C | 12/19/2023 | Need 2lb approval letter from gas provider by final / Verify one regulator in north mechanical room and one regulator in south mechanical room at final / Verify medium pressure stenciling on all exposed gas line at final /
10 lb test ok / 3/4 inch main / 2 x furnace / 1 water heater / 2 x range / 2 x fireplace / One 1/2" stub at north wall for 60K BBQ / | CASEYM | CASEYM | | HI | C | 7949113 |
WESTERN FIREPLACE SUPPLY, INC. | HV | C | 12/05/2023 | Main level fireplace clearance to combustibles and vent termination ok. / Non-combustible materials installed / Basement fireplace clearance to combustibles and vent termination ok. / Non-combustible materials installed / | CASEYM | CASEYM | | HV | C | 7935474 |
ROCKY MOUNTAIN RADIANT HEATING & PLUMBING, INC. | PTO | C | 12/19/2023 | THREE VTR -- AAV @ BAR -- DRAFT HOOD W/H | LEE | LEE | | PTO | C | 7949087 |
ROCKY MOUNTAIN RADIANT HEATING & PLUMBING, INC. | PB+ | C | 12/13/2023 | FLOOR DRAIN AT NEW WATER HEATER LOCATION OK | LEE | LEE | | PB+ | C | 7944181 |
ROCKY MOUNTAIN RADIANT HEATING & PLUMBING, INC. | PWO | C | 09/19/2023 | | LEE | LEE | | PWO | C | 7861324 |
ROCKY MOUNTAIN RADIANT HEATING & PLUMBING, INC. | PWO | P | 09/14/2023 | CONNECTION AT WELL HEAD INCOMPLETE -- NEED PRESSURE TEST OR UNCOVER ALL PIPE IN DITCH | LEE | LEE | | PWO | P | 7856908 |
ROCKY MOUNTAIN RADIANT HEATING & PLUMBING, INC. | PB | C | 09/14/2023 | HDPE STUBBED IN THRU WALL | LEE | LEE | | PB | C | 7856904 |
SUNSET DREAM HOMES, INC | XMS | T | 01/04/2024 | PAID (REC#2021927): PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: some duct sizes changed | TCRIPPEN | TCRIPPEN | | XMS | T | 7960121 |
SUNSET DREAM HOMES, INC | XMS | T | 01/04/2024 | PAID (REC#2021927): PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: Some duct sizes changed. | TCRIPPEN | TCRIPPEN | | XMS | T | 7960114 |
SUNSET DREAM HOMES, INC | XMS | T | 12/29/2023 | PAID (REC#2020760): PLAN SPLICE FEE: $50 by: TCRIPPEN for Mechanical: new splice for duct design | TCRIPPEN | TCRIPPEN | | XMS | T | 7956253 |