BLEVINS CONSTRUCTION & REMODELING | B= | C | 10/04/2023 | All other required Final inspections are complete. (This is a computer generated result) | LONNYS | LONNYS | | B= | C | 7877145 |
BLEVINS CONSTRUCTION & REMODELING | B= | P | 09/13/2023 | building final OK pending H=, zoning and fire. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), External Agency Inspection Z= by ZONING is not Completed yetRequest inspection through PPRBD system or contact 719-385-5982 for zoning questions, THAYER MECHANICAL SERVICES, LLC Mechanical Final Inspection is not Completed yet. | LONNYS | LONNYS | | B= | P | 7855039 |
BLEVINS CONSTRUCTION & REMODELING | BFR | P | 06/19/2023 | Complete other rough inspections. / Reviewed Accessible Elements / | ERAMIREZ | ERAMIREZ | | BFR | P | 7775321 |
RAVENWOOD ELECTRIC LLC | E= | C | 08/30/2023 | 2 ac units ok 1--20 1--25 amp --ok / | BRIAN | BRIAN | | E= | C | 7843046 |
STILSON ELECTRIC SYSTEMS, INC. | E= | C | 05/04/2023 | FIRE ALARM INSPECTION: cables and boxes ok / | MIGUEL | MIGUEL | | E= | C | 7735356 |
STILSON ELECTRIC SYSTEMS, INC. | ER | C | 05/04/2023 | FIRE ALARM INSPECTION: cables and boxes ok / | MIGUEL | MIGUEL | | ER | C | 7735355 |
STILSON ELECTRIC SYSTEMS, INC. | E= | R | 05/02/2023 | FIRE ALARM INSPECTION: door locked / | MIGUEL | MIGUEL | | E= | R | 7732712 |
STILSON ELECTRIC SYSTEMS, INC. | ER | R | 05/02/2023 | FIRE ALARM INSPECTION: door locked / | MIGUEL | MIGUEL | | ER | R | 7732708 |
RAVENWOOD ELECTRIC LLC | ER | C | 05/01/2023 | corrections made / | MIGUEL | MIGUEL | | ER | C | 7731190 |
RAVENWOOD ELECTRIC LLC | ER | R | 04/28/2023 | drop octagon box in hardlid in bedroom for drywall and add receptacle in bedroom north wall to meet wall spacing / existing panel / Photo upload requested. If unfamiliar with uploading photos for an inspection, please click the following link: https://youtu.be/QS0hdGSBA6o / | MIGUEL | MIGUEL | | ER | R | 7730331 |
THAYER MECHANICAL SERVICES, LLC | H= | C | 09/29/2023 | SPLICE ON FILE AND MAKEUP AIR COMPLETE. | MARKB | MARKB | | H= | C | 7872872 |
THAYER MECHANICAL SERVICES, LLC | H= | P | 09/21/2023 | STILL NEED ENGINEER TO ADDRESS PREVIOUS INSPECT COMMENTS WITH PLAN SPLICE. | MARKB | MARKB | | H= | P | 7864137 |
THAYER MECHANICAL SERVICES, LLC | H= | R | 09/12/2023 | ----NEED ENGINEER AND MANUFACTURER TO ADDRESS: Uncased fan coil units have been boxed in and return duct out to common area. what size does blower box have to be to provide required air flow? How providing makeup air to laundry closet?---- Need to label dryer box with duct length. | MARKB | MARKB | | H= | R | 7853966 |
THAYER MECHANICAL SERVICES, LLC | HD | P | 06/07/2023 | ----ENGINEER TO ADDRESS: to GET AWAY FROM THE CEILING SPACE BEING A PLENUM, THE CONTRACTOR BOXED IN THE BLOWERS ON THE FAN COIL UNIT AND DUCTED THE RETURN. WILL NEED AN ENGINEERED DETAIL FOR RETURN BOX AND DUCT SIZES.---- | MARKB | MARKB | | HD | P | 7765345 |
THAYER MECHANICAL SERVICES, LLC | HSP | P | 05/15/2023 | MINI-SPLIT INSULATION IS RATED ASTM E84 PER MANUFACTURER SPEC SHEET PROVIDED - SEE IMAGES | MARKB | MARKB | | HSP | P | 7743826 |
THAYER MECHANICAL SERVICES, LLC | HRP | P | 05/08/2023 | CONTRACTOR NEEDS PAPERWORK OF BLACK LINE INSULATION TO SHOW FLAME/SPREAD INDEX FOR INSTALLATION IN RETURN AIR PLENUM. Note / 250 lb. test ok x2 (PENDING ABOVE NOTES ADDRESSED) / Support ok. | PAULO | PAULO | | HRP | P | 7738181 |
THAYER MECHANICAL SERVICES, LLC | HD | P | 05/01/2023 | Contractor needs address all non-plenum rated materials in new plenum's. Will need pressure test on hydronic and refrigeration piping. ABOVE CEILING IS INSTALLED PER PLAN. | MARKB | MARKB | | HD | P | 7732019 |
PLUMBING AND GAS, LLC | P= | C | 08/28/2023 | See images. | DANR | DANR | | P= | C | 7840032 |
PLUMBING AND GAS, LLC | P= | P | 08/23/2023 | Need approved band on water heater exhaust pipe / rest okay. Photo upload requested. If unfamiliar with uploading photos for an inspection, please click the following link: https://youtu.be/QS0hdGSBA6o / | DANR | DANR | | P= | P | 7834702 |
PLUMBING AND GAS, LLC | PTO | C | 05/01/2023 | WATER HEATER VENT PRESSURE TEST OK | TRAVISR | TRAVISR | | PTO | C | 7731247 |
PLUMBING AND GAS, LLC | PTO | P | 04/10/2023 | Need Further Review For Existing Water Heater Vent / ( Does Previously Installed Vent Needs Tested ) Water Lines To Mechanical Units Inspected On Test @ 50 Psi Mechanical Permit Needs To Attach - Rest OK
Need To Insulate Hot 1" & 3/4" Water Lines Per Plans | TRAVISR | TRAVISR | | PTO | P | 7711403 |
THAYER MECHANICAL SERVICES, LLC | XMS | T | 09/25/2023 | PAID (REC#1992712): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised layout | JUSTINC | JUSTINC | | XMS | T | 7866346 |