L AND S HOME BUILDERS LLC | B= | C | 07/25/2023 | | RYANF | RYANF | | B= | C | 7807554 |
L AND S HOME BUILDERS LLC | BFR | C | 04/26/2023 | Framing OK / Reviewed smoke and CO requirements with homeowner | ADAML | ADAML | | BFR | C | 7728061 |
TEK ELECTRICAL SERVICES, LLC | E= | C | 07/20/2023 | Corrections made as requested - complete | CHIPO | CHIPO | | E= | C | 7804246 |
TEK ELECTRICAL SERVICES, LLC | E= | R | 07/14/2023 | field cancelled by contractor could not make time frame | TIMA | TIMA | | E= | R | 7798171 |
TEK ELECTRICAL SERVICES, LLC | E= | T | 07/12/2023 | PAID (REC#1969347): still need fireplace on own afci ckt / some recepts in master still not afci / install cover on steamer | TIMA | TIMA | | E= | T | 7795652 |
TEK ELECTRICAL SERVICES, LLC | E= | R | 06/12/2023 | 7500 watt steamer #10 wire and breaker to small and need disconnect at unit / need ckt for fireplace with afci / some recepts in bedroom not afci | TIMA | TIMA | | E= | R | 7768900 |
TEK ELECTRICAL SERVICES, LLC | ER | C | 04/24/2023 | Master bed, bath and closet all ok | JIMMY | JIMMY | | ER | C | 7725270 |
THE FURNACE GUY HEATING & COOLING | H= | C | 05/25/2023 | NOTE / LOUVER DOOR TO WATER HEATER CLOSET / | MATTM | MATTM | | H= | C | 7754773 |
THE FURNACE GUY HEATING & COOLING | HRR | C | 04/25/2023 | OK TO FINAL WITH PICTURES OF WATER HEATER COMBUSTION AIR AND RETURN AIR PATH / NOTE / REMODEL / | MATTM | MATTM | | HRR | C | 7726437 |
PACIFIC PLUMBING, INCORPORATED | P= | C | 07/20/2023 | | JOHNS | JOHNS | | P= | C | 7804071 |
PACIFIC PLUMBING, INCORPORATED | P= | P | 06/05/2023 | steamer not installed per book reqs (page 8), need hammer arrestor @ shut off (quick closing valve), need to run steamer t&p to drain, need slope / air gap @ steamer drain down (w/ 90 down @ termination point), on site inspection required, rest ok | JOHNS | JOHNS | | P= | P | 7762276 |
PACIFIC PLUMBING, INCORPORATED | PTO | C | 04/26/2023 | | JOHNS | JOHNS | | PTO | C | 7727646 |
PACIFIC PLUMBING, INCORPORATED | PTO | P | 04/21/2023 | gc to add elec permit (bath remodel / steamer / etc)
just need to remove 1 tub / shwr from scope (for a total of only 1 tub / shwr), need to add steamer to current scope, and remove water htr (no new water htr installed per home owner)
rest ok for mstr 4 pc bath remodel / steamer only. NOTE: NEED STEAMER INSTALL MANUAL @ FINAL, vtr (existing) | JOHNS | JOHNS | | PTO | P | 7723623 |