NUNN CONSTRUCTION, INC. | BSP | P | 05/14/2024 | West BHS Doghouse - 1nd layer 5/8 drywall OK on walls and ceiling EXCEPT around new fire shutter and behind fire shutter controls ( Both of these to be finished at a later date ) | ADAML | ADAML | | BSP | P | 8084321 |
NUNN CONSTRUCTION, INC. | BSP | P | 05/13/2024 | West BHS Doghouse - 1st layer 5/8 drywall OK on walls and ceiling EXCEPT around new fire shutter and behind fire shutter controls ( Both of these to be finished at a later date ) | ADAML | ADAML | | BSP | P | 8082971 |
NUNN CONSTRUCTION, INC. | BSP | P | 05/02/2024 | WEST BHS DOG HOUSE// 1st layer gyp attachment replacement at existing rated assembly OK per note | LONNYS | LONNYS | | BSP | P | 8072615 |
NUNN CONSTRUCTION, INC. | BFR | P | 04/16/2024 | North west area exterior grid X and hard lid framing OK pending other required inspections | LONNYS | LONNYS | | BFR | P | 8054645 |
NUNN CONSTRUCTION, INC. | BIN | P | 02/20/2024 | ENCLOSED BAG ROOM 101 - 2" R10 rigid and hat channel OK at thermal walls | LONNYS | LONNYS | | BIN | P | 8000788 |
NUNN CONSTRUCTION, INC. | BFR | R | 02/14/2024 | inspection request for incorrect permit | LONNYS | LONNYS | | BFR | R | 7995877 |
NUNN CONSTRUCTION, INC. | BFR | P | 01/05/2024 | Oversized Baggage Screening - Metal framing OK around exterior only pending all other required inspections | ADAML | ADAML | | BFR | P | 7961484 |
NUNN CONSTRUCTION, INC. | BIN | P | 01/03/2024 | observed 2" R10 rigid continuous insulation room 102 oversized baggage - all walls OK | LONNYS | LONNYS | | BIN | P | 7959031 |
NUNN CONSTRUCTION, INC. | BSP | P | 11/08/2023 | Baggage Enclosure - 2nd layer drywall OK on outside and inside walls and interior lid / Provide observation for concrete on top of enclosure | ADAML | ADAML | | BSP | P | 7913307 |
NUNN CONSTRUCTION, INC. | BSP | P | 11/07/2023 | Baggage Enclosure - 2nd layer drywall on outside and inside walls lacks screw attachment at bottom plate all the way around the enclosure / 2nd layer drywall on interior lid lacks screw attachment 12" oc and within 2" of butt joints per GA FC2116 / | ADAML | ADAML | | BSP | P | 7911882 |
NUNN CONSTRUCTION, INC. | BFR | P | 11/03/2023 | Baggage Enclosure - Per RFI 60 changing to a UL V489 - 1st layer drywall OK on outside and inside walls and interior lid / Provide observation for concrete lid on top side | ADAML | ADAML | | BFR | P | 7909042 |
NUNN CONSTRUCTION, INC. | BFR | P | 10/27/2023 | Baggage enclosure framing OK per S3.2 for walls and hard lid / Note** The UL U419 2 hour assembly for the walls is a Proprietary USG drywall listing | ADAML | ADAML | | BFR | P | 7902300 |
NUNN CONSTRUCTION, INC. | BIN | P | 10/26/2023 | Qualified third party energy inspection documentation must be presented at time of final building (B=) inspection | INTERNET | INTERNET | | BIN | P | 7900017 |
NUNN CONSTRUCTION, INC. | BSP | P | 08/08/2023 | Field cancelled per Keith / Unable to access today | ADAML | ADAML | | BSP | P | 7820618 |
GONZALES ELECTRIC, LLC | ER | P | 05/10/2024 | west side doghouse 2 new lights and 1 switch ------------- existing circuit | CRAIG | CRAIG | | ER | P | 8080513 |
INTERMOUNTAIN ELECTRIC, INC. | ER | P | 04/30/2024 | East side ok---conveyer controllers ok | JIMMY | JIMMY | | ER | P | 8069925 |
INTERMOUNTAIN ELECTRIC, INC. | ER | L | 04/26/2024 | Hour call ahead at 2 pm-- called call ahead # twice-- no answer-- left at 3:01 | JIMMY | JIMMY | | ER | L | 8066784 |
GONZALES ELECTRIC, LLC | ER | P | 04/15/2024 | 2 lights on west side ---------------- 1 light on east side only ok | CRAIG | CRAIG | | ER | P | 8052538 |
GONZALES ELECTRIC, LLC | ER | P | 03/12/2024 | South Tugway ceilings and walls ok | JIMMY | JIMMY | | ER | P | 8021796 |
GONZALES ELECTRIC, LLC | ER | P | 02/20/2024 | 102 ceilings ok | JIMMY | JIMMY | | ER | P | 8000693 |
GONZALES ELECTRIC, LLC | EP | P | 02/15/2024 | ETUPS5 30 kva xfmr / ETBHS5E 75 kva xfmr / BHS5ME 400 amp 4/w / UPS BYE PASS 100 amp 4/w / BHS5E 225 amp 4/w / BHS5E 100 amp 4/w / BHS-5CW 100 amp 4/w / BHS5MW 200 amp 4/w and ETLCM2 150 amp 4/w note inspection up to MLO or main breaker only in sub panels | CRAIG | CRAIG | | EP | P | 7996758 |
GONZALES ELECTRIC, LLC | ER | P | 01/17/2024 | wall rough screening room 102 | JIMMY | JIMMY | | ER | P | 7970275 |
GONZALES ELECTRIC, LLC | ER | P | 10/31/2023 | Light rough in dog house East ok | JIMMY | JIMMY | | ER | P | 7904384 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | HWP | L | 04/12/2024 | CANCELED BY CONTRACTOR | JERRYF | JERRYF | | HWP | L | 8050541 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | HD | P | 02/21/2024 | THIS INSPECTION WAS ON BDA PAGE 221 FOR UNIT AHU1 AND DUCT. NOTE / SUPPLY RUNS AND RETURNS (((OK))) TO SET CEILING. | NICKE | NICKE | | HD | P | 8001508 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | HD | P | 01/31/2024 | THIS INSPECTION WAS FOR BDA PAGE 174 REVISED SHEET M03.15 - STILL NEED TIE INS AT AHU 1 NOTE / SA MAIN /RUN OUTS ((OK)) / | JERRYF | JERRYF | | HD | P | 7982888 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | H= | P | 11/08/2023 | NOTES CORRECTED AT 8:15 - TAB REPORT WAS ATTACHED TO THE WRONG PERMIT - TAB REPORT REJECTED FOR THIS PERMIT | JERRYF | JERRYF | | H= | P | 7912008 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | HSP | L | 09/21/2023 | THIS INSPECTION WAS FOR UNDER GROUND SLAB PIPING AT EXTERIOR OF BUILDING - NOTIFIED JASON WITH M TECH THAT WE DO NOT INSPECT ANY WORK OUTSIDE THE BUILDING - WILL NEED TO INSPECT TIE INS INSIDE BUILDING WHEN READY | JERRYF | JERRYF | | HSP | L | 7863561 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | XMS | T | 03/13/2024 | PAID (REC#2051786): PLAN SPLICE FEE: $50 by: DALEH for Mechanical: Clouds | DALEH | DALEH | | XMS | T | 8022937 |
NUNN CONSTRUCTION, INC. | XBS | T | 03/13/2024 | PAID (REC#2051786): PLAN SPLICE FEE: $50 by: DANM for Construction: Minor architectural and structural revisions | DANM | DANM | | XBS | T | 8022779 |
INTERMOUNTAIN ELECTRIC, INC. | XES | T | 03/13/2024 | PAID (REC#2051786): PLAN SPLICE FEE: $50 by: DANIELG for Electrical: As built revisions to BHS. | DANIELG | DANIELG | | XES | T | 8022646 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | XMS | T | 01/11/2024 | PAID (REC#2024467): PLAN SPLICE FEE: $50 by: DALEH for Mechanical: clouds | DALEH | DALEH | | XMS | T | 7965407 |
NUNN CONSTRUCTION, INC. | XBS | T | 01/10/2024 | PAID (REC#2024467): PLAN SPLICE FEE: $50 by: DANM for Construction: Architectural and structural revisions | DANM | DANM | | XBS | T | 7965136 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | XMS | T | 12/20/2023 | PAID (REC#2020973): PLAN SPLICE FEE: $50 by: DALEH for Mechanical: RELOCATE GAS | DALEH | DALEH | | XMS | T | 7950660 |
INTERMOUNTAIN ELECTRIC, INC. | XES | P | 12/20/2023 | PLAN SPLICE: (No Fee) by: DANIELG for Electrical: Added overhead door heater. | DANIELG | DANIELG | | XES | P | 7950643 |
NUNN CONSTRUCTION, INC. | XBS | T | 12/20/2023 | PAID (REC#2020973): PLAN SPLICE FEE: $50 by: DANM for Construction: Various architectural and structural revisions | DANM | DANM | | XBS | T | 7950574 |
MTECH MECHANICAL TECHNOLOGIES GROUP, INC. | XMS | T | 12/13/2023 | PAID (REC#2016895): PLAN SPLICE FEE: $50 by: DALEH for Mechanical: Snow melt changes | DALEH | DALEH | | XMS | T | 7944525 |
NUNN CONSTRUCTION, INC. | XBS | T | 12/13/2023 | PAID (REC#2016895): PLAN SPLICE FEE: $50 by: DANM for Construction: Clarification on ceiling type and details in one area | DANM | DANM | | XBS | T | 7944106 |
GONZALES ELECTRIC, LLC | XES | T | 11/30/2023 | PAID (REC#2016895): PLAN SPLICE FEE: $50 by: DANIELG for Electrical: As built changes. | DANIELG | DANIELG | | XES | T | 7932096 |