CUSITECH LLC | B= | C | 08/07/2023 | All other required Final inspections are complete. (This is a computer generated result) | ERAMIREZ | ERAMIREZ | | B= | C | 7818484 |
CUSITECH LLC | B= | P | 08/02/2023 | Building final OK pending other finals /. Additional Inspections Required (computer generated): CUSITECH LLC Electrical Final Inspection is not Completed yet, BULLETPROOF PLUMBING AND HEATING INC. Plumbing Final Inspection is not Completed yet. | ERAMIREZ | ERAMIREZ | | B= | P | 7814892 |
CUSITECH LLC | BSP | P | 07/14/2023 | Pending completion of other required inspections
Inspection for above grid ceiling ok | PAULP | PAULP | | BSP | P | 7798334 |
CUSITECH LLC | BFR | P | 06/08/2023 | Obtain and attach mechanical to permit. / Complete other rough inspections. / Light gauge steel frame okay. / Reviewed Accessible Elements / | ERAMIREZ | ERAMIREZ | | BFR | P | 7766381 |
CUSITECH LLC | E= | C | 08/02/2023 | | BRIAN | BRIAN | | E= | C | 7815426 |
CUSITECH LLC | ES | C | 08/02/2023 | Commercial Service: 200 amp 3-w--ok no action needed / | BRIAN | BRIAN | | ES | C | 7815416 |
CUSITECH LLC | E= | P | 08/01/2023 | need to remove the parallel neutral in disco / 2 recepts in front offices not working / rest ok / | BRIAN | BRIAN | | E= | P | 7814333 |
CUSITECH LLC | ES | C | 08/01/2023 | Commercial Service: 200 amp --3-w --ok no action needed / | BRIAN | BRIAN | | ES | C | 7814326 |
CUSITECH LLC | ER | C | 07/18/2023 | all grid,ok | JOHNN | JOHNN | | ER | C | 7801545 |
CUSITECH LLC | ER | P | 07/14/2023 | rear area:: grid | JOHNN | JOHNN | | ER | P | 7798779 |
CUSITECH LLC | ER | P | 06/07/2023 | all walls,ok | JOHNN | JOHNN | | ER | P | 7765834 |
CUSITECH LLC | ESPR | P | 06/06/2023 | Commercial Service: pre release ok | JOHNN | JOHNN | | ESPR | P | 7764034 |
HVAC SOLUTIONS, INC. | H= | C | 08/02/2023 | TEST AND BALANCE REPORT RECEIVED, SEE IMAGES. FINAL FOR MECHANICAL CONTRACTOR | BILLS | BILLS | | H= | C | 7814646 |
HVAC SOLUTIONS, INC. | H= | P | 08/01/2023 | FINAL PENDING - Provide test and balance report. ATTIC INSULATION, TRANSFER GRILLS AND THERMOSTAT COMPLETE | MARKB | MARKB | | H= | P | 7814368 |
HVAC SOLUTIONS, INC. | HD | P | 07/20/2023 | CORRECTION MADE, SEE IMAGES | BILLS | BILLS | | HD | P | 7802933 |
HVAC SOLUTIONS, INC. | HD | P | 07/17/2023 | MISSING SUPPLY AIR AT OFFICE #102. CONTRACTOR TO ATTACH PICTURES AT NEXT INSPECTION REQUEST. ALL OTHER SUPPLY AND RETURNS IN THE SOUTH WORK AREA OK. OK TO INSULATE. BY FINAL: NEED TEST AND BALANCE REPORT, CONFIRM ALL TRANSFER GRILLES/OPENINGS AND T-STATS. | BILLS | BILLS | | HD | P | 7799506 |
HVAC SOLUTIONS, INC. | HD | P | 06/29/2023 | ALL ATTIC PIPING INSTALLED AS PER PLAN. OK TO INSULATE. MAIN LEVEL NORTH AREA PIPING INSTALLED AS PER PLAN. OK TO INSULATE. | BILLS | BILLS | | HD | P | 7786180 |
BULLETPROOF PLUMBING AND HEATING INC. | P= | C | 08/07/2023 | ENGINEER LETTER FOR AAV | TRAVISR | TRAVISR | | P= | C | 7818483 |
BULLETPROOF PLUMBING AND HEATING INC. | P= | P | 08/01/2023 | Plan Splice Does Not Mention Any DWV / Original Plans Call For VTR @ Sink / Rest Ok | TRAVISR | TRAVISR | | P= | P | 7813894 |
BULLETPROOF PLUMBING AND HEATING INC. | PTO | P | 06/07/2023 | DWV & H20 Not Piped Per Plan /
Whats There - 3/4" DCW To Under Break Sink With Insta Hot 3" DWV Until 2" For 12' Up To Sink With AAV
Note: Need To See DCW Tie In By Final | TRAVISR | TRAVISR | | PTO | P | 7765282 |
BULLETPROOF PLUMBING AND HEATING INC. | PTO | R | 06/06/2023 | No Contractor On Site /
DWV Lost Test DWV & H20 Not Piped Per Plan Re- Inspect All / Unable To See All Work / No Escort | TRAVISR | TRAVISR | | PTO | R | 7763929 |
HVAC SOLUTIONS, INC. | XMS | T | 06/19/2023 | PAID (REC#1963505): PLAN SPLICE FEE: $50 by: DALEH for Mechanical: clouds | DALEH | DALEH | | XMS | T | 7775255 |
CUSITECH LLC | XBS | T | 06/19/2023 | PAID (REC#1963316): PLAN SPLICE FEE: $50 by: CGIECK for Construction: Design change | CGIECK | CGIECK | | XBS | T | 7775221 |
BULLETPROOF PLUMBING AND HEATING INC. | XPS | T | 06/19/2023 | PAID (REC#1973457): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Delta 2 revisions: Adjusted sheet P-W-101 and P-601. | SHANEN | SHANEN | | XPS | T | 7774962 |
CUSITECH LLC | XES | T | 05/16/2023 | PAID (REC#1954799): PLAN SPLICE FEE: $50 by: BERTHA for Electrical: Revised power plan. Revised one-line. Revised schedules. | BERTHA | BERTHA | | XES | T | 7745132 |