RAINE BUILDING LLC. | B= | C | 08/21/2023 | All other required Final inspections are complete. (This is a computer generated result) | ADAML | ADAML | | B= | C | 7832624 |
RAINE BUILDING LLC. | B= | P | 08/18/2023 | Final items OK pending all other finals. Additional Inspections Required (computer generated): HARRIS ELECTRIC GROUP Electrical Final Inspection is not Completed yet, JOHNSON BROTHER'S PLUMBING & HEATING LLC Plumbing Final Inspection is not Completed yet. | ADAML | ADAML | | B= | P | 7830988 |
RAINE BUILDING LLC. | BFR | C | 07/12/2023 | bathrooms existing except new framed door at back bathroom/ steel stud framing ok/ reviewed accessible elements | SHAUN | SHAUN | | BFR | C | 7796340 |
HARRIS ELECTRIC GROUP | E= | C | 08/21/2023 | Correction made with front counter recep, show window recep, and GFCI protection - complete | CHIPO | CHIPO | | E= | C | 7832623 |
HARRIS ELECTRIC GROUP | E= | P | 08/18/2023 | Need to GFCI protect ALL receptacles within 6' of sinks. --- Need one additional show window receptacle. --- Need receptacle at front counter completed. | AARONR | AARONR | | E= | P | 7831341 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 08/16/2023 | FIRE ALARM INSPECTION: F/A OK | CRAIGS | CRAIGS | | E= | C | 7827804 |
SPECIAL SYSTEMS DESIGN,LLC | ER | C | 08/16/2023 | FIRE ALARM INSPECTION: FA/ above ceiling OK | CRAIGS | CRAIGS | | ER | C | 7827801 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 08/16/2023 | FIRE ALARM INSPECTION: FA/ above ceiling OK | CRAIGS | CRAIGS | | E= | C | 7827802 |
HARRIS ELECTRIC GROUP | ER | C | 08/16/2023 | above ceiling OK | CRAIGS | CRAIGS | | ER | C | 7827797 |
HARRIS ELECTRIC GROUP | ER | P | 07/14/2023 | front pony wall OK | CRAIGS | CRAIGS | | ER | P | 7797975 |
HARRIS ELECTRIC GROUP | ER | P | 07/12/2023 | all walls except the front pony wall OK | CRAIGS | CRAIGS | | ER | P | 7796124 |
HARRIS ELECTRIC GROUP | ESL | C | 06/22/2023 | 2 -- conduits under slab OK -- data/ power | CRAIGS | CRAIGS | | ESL | C | 7778994 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | H= | C | 08/16/2023 | TEST AND BALANCE REPORT RECEIVED - SEE IMAGES | MARKB | MARKB | | H= | C | 7827577 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | H= | P | 08/11/2023 | PARTIAL PENDING TAB REPORT | JERRYF | JERRYF | | H= | P | 7824424 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | HD | P | 08/11/2023 | NOTE / ABOVE CEILING SA / RA / EXHAUST MAINS / RUN OUTS / GRILLES / CONTROLS ARE COMPLETE / | JERRYF | JERRYF | | HD | P | 7824417 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | P= | C | 08/21/2023 | See image. | DANR | DANR | | P= | C | 7831539 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | P= | P | 08/18/2023 | Missing AAV KS sink by drinking fountain /Photo upload requested. If unfamiliar with uploading photos for an inspection, please click the following link: https://youtu.be/QS0hdGSBA6o / rest okay. | DANR | DANR | | P= | P | 7830517 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | PTO | C | 07/12/2023 | | CODYP | CODYP | | PTO | C | 7795856 |
JOHNSON BROTHER'S PLUMBING & HEATING LLC | PB | C | 07/06/2023 | | DANR | DANR | | PB | C | 7790497 |