THOMAS GENERAL CONTRACTORS, INC. | B= | C | 11/02/2023 | All other required Final inspections are complete. (This is a computer generated result) | LONNYS | LONNYS | | B= | C | 7906639 |
THOMAS GENERAL CONTRACTORS, INC. | B= | P | 09/12/2023 | building final OK pending P= and E=. Additional Inspections Required (computer generated): R & R DITCHING, INC Plumbing Final Inspection is not Completed yet. | LONNYS | LONNYS | | B= | P | 7854020 |
THOMAS GENERAL CONTRACTORS, INC. | BFR | P | 08/31/2023 | framing corrections OK pending other required inspections | LONNYS | LONNYS | | BFR | P | 7843972 |
THOMAS GENERAL CONTRACTORS, INC. | BFR | P | 07/17/2023 | SFRM data and observation on file | LONNYS | LONNYS | | BFR | P | 7798955 |
THOMAS GENERAL CONTRACTORS, INC. | BFR | P | 07/13/2023 | door and wall framing corrections OK / still need to provide SFRM repair documentation / still need to inspect all new floor penetrations when ready and provide fire stop details for inspection | LONNYS | LONNYS | | BFR | P | 7796912 |
THOMAS GENERAL CONTRACTORS, INC. | BFR | P | 07/07/2023 | Remove 2x4 combustible wood stud from entry door framing due to type of I-A constructions and not done per detail 5/A4.1. / Replace SFRM where removed for new framing and provide 3rd party observation letter. / Missing vertical bracing every 4' o.c. / Attach plumbing to permit. / Complete other rough inspections. / Reviewed Accessible Elements / | ERAMIREZ | ERAMIREZ | | BFR | P | 7792307 |
RJE ELECTRICAL INC. | E= | C | 09/12/2023 | | BRIAN | BRIAN | | E= | C | 7853927 |
RJE ELECTRICAL INC. | ER | C | 08/31/2023 | ceiling--ok / | BRIAN | BRIAN | | ER | C | 7843880 |
RJE ELECTRICAL INC. | ER | P | 07/07/2023 | walls ok / verify height in break room on final / Discussed accessibility requirements with contractor / | BRIAN | BRIAN | | ER | P | 7792165 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 08/24/2023 | TEST AND BALANCE REPORT RECEIVED - SEE IMAGES | MARKB | MARKB | | H= | C | 7836136 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 08/23/2023 | FINAL PENDING - Provide test and balance report. ABOVE CEILING DUCT, GRILLS AND THERMOSTATS COMPLETE. | MARKB | MARKB | | H= | P | 7835189 |
R & R DITCHING, INC | P= | C | 11/02/2023 | Need Hammer Arrestor @ Dishwasher H20 Supply Line | TRAVISR | TRAVISR | | P= | C | 7906638 |
R & R DITCHING, INC | P= | R | 09/12/2023 | No Change / Still Need Plans Revised | TRAVISR | TRAVISR | | P= | R | 7853210 |
R & R DITCHING, INC | PTO | P | 07/20/2023 | Need plan revision for water pipe sizing, NOTE/ Rest o.k. | CODYP | CODYP | | PTO | P | 7804102 |
R & R DITCHING, INC | PTO | T | 07/19/2023 | PAID (REC#1970888) NOT READY /
DWV & H20 Not Piped Per Plan / H20 Not On Test / Water Lines Look Unfinished Out Of Wall / Need To Properly Secure Water Lines / Need To Protect All Pex Lines Through Metal Studs / Water Heater Not Accessible / | TRAVISR | TRAVISR | | PTO | T | 7802523 |
R & R DITCHING, INC | XPS | T | 10/24/2023 | PAID (REC#2003577): PLAN SPLICE FEE: $50 by: SHANEN for Plumbing: Revised sheet P.1. | SHANEN | SHANEN | | XPS | T | 7897120 |