GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 03/26/2024 | provide 3rd structural steel welding and bolting observation to complete BFR / rest of building final OK -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): MECHONE, INC. Mechanical Final Inspection is not Completed yet. | LONNYS | LONNYS | | B= | P | 8033439 |
ENCORE ELECTRIC, INC. | E= | C | 12/11/2023 | ok per pic | BRIAN | BRIAN | | E= | C | 7940848 |
ENCORE ELECTRIC, INC. | E= | R | 11/14/2023 | need plans spliced to show cooler feed coming from the correct panel / need placard stating the # of branch circuits and feeders feeding unit / need 30 amp breaker / good pics ok / | BRIAN | BRIAN | | E= | R | 7918676 |
ENCORE ELECTRIC, INC. | ER | C | 11/14/2023 | feeder to new panel / 100 amp #2 cu--ok / rtu--ok / | BRIAN | BRIAN | | ER | C | 7918669 |
MECHONE, INC. | H= | C | 04/25/2024 | ENGINEER LETTER FOR DUCT AND CORRECTION MADE - SEE IMAGES | MARKB | MARKB | | H= | C | 8064405 |
MECHONE, INC. | H= | P | 03/06/2024 | FINAL PENDING - ENGINEER TO ADDRESS: Note 2 on plan sheet M112 wants 10' of stainless duct installed but galvanize duct is installed. Install label for fire/smoke damper on access door. FIRE/SMOKE DAMPER ANGLES COMPLETE. DUCT COMPLETE. AHU-27 ON ROOF COMPLETE. | MARKB | MARKB | | H= | P | 8015880 |
OLSON PLUMBING & HEATING COMPANY | H= | C | 03/01/2024 | LOW PRESSURE STEAM AND CONDENSATE PIPING/INSULATION UNDER OPERATING PRESSURE COMPLETE TO HUMIDIFIER. | MARKB | MARKB | | H= | C | 8011282 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 11/28/2023 | STILL NEED LPS & LPC TO HUMIDIFIER INSTALLED.
50 lb. test x4 Note / Hot & Chilled Water piping installed per plans. | PAULO | PAULO | | HWP | P | 7929581 |
MECHONE, INC. | HD | P | 10/31/2023 | Roof Top Inspection-- ENGINEER TO ADDRESS CHANGE OF SIZING TO OUTSIDE AIR DUCT (INSTALLED/56"X24") PLANS CALL FOR 50"X24". CONTRACTOR- STILL NEED TIE INS FOR SUPPLY & RETURN AIR TO 2nd FLOOR, INSULATION & WEATHER PROTECTION, VERIFY NOTE #4 ON SHEET M113, NOTE 8 FOR AHU-27 VERIFIED FROM EQUIPMENT SCHEDULE.D Note / All Supply/Return duct installed per plans, Outside Air installation ok (M113)(OK TO INSULATE). | PAULO | PAULO | | HD | P | 7904628 |
MECHONE, INC. | HD | P | 10/19/2023 | ANNULAR SPACE AROUND FIRE DAMPER IN CONCRETE FLOOR OK. Will need angles installed large enough to cover maximum annular space allowed. | MARKB | MARKB | | HD | P | 7893098 |
OLSON PLUMBING & HEATING COMPANY | P= | C | 11/28/2023 | | CODYP | CODYP | | P= | C | 7928789 |
ENCORE ELECTRIC, INC. | XES | P | 01/08/2024 | PLAN SPLICE: (No Fee) by: DANIELG for Electrical: Revised one-line diagram. As built changes. | DANIELG | DANIELG | | XES | P | 7962032 |
OLSON PLUMBING & HEATING COMPANY | XMS | T | 12/13/2023 | PAID (REC#2016239): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised piping | JUSTINC | JUSTINC | | XMS | T | 7943595 |
OLSON PLUMBING & HEATING COMPANY | XMS | T | 11/21/2023 | PAID (REC#2010355): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Revised piping | JUSTINC | JUSTINC | | XMS | T | 7925443 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | XES | P | 10/05/2023 | PLAN SPLICE: (No Fee) by: DANIELG for Electrical: As builts. | DANIELG | DANIELG | | XES | P | 7878821 |
MECHONE, INC. | XMS | T | 10/04/2023 | PAID (REC#1995133): PLAN SPLICE FEE: $50 by: JUSTINC for Mechanical: Added FSD's | JUSTINC | JUSTINC | | XMS | T | 7877235 |