BRYAN CONSTRUCTION, INC. | B= | C | 02/23/2024 | | LONNYS | LONNYS | | B= | C | 8004667 |
BRYAN CONSTRUCTION, INC. | B= | P | 02/12/2024 | restroom missing international sign of accessibility / restroom door handle installed backwards / rest OK pending other required inspections -- Schedule a new Building Final when above items are complete. Additional Inspections Required (computer generated): HARMON - BONDED PLUMBING & HEATING, INC. Plumbing Final Inspection is not Completed yet. | LONNYS | LONNYS | | B= | P | 7993417 |
BRYAN CONSTRUCTION, INC. | BEN= | C | 02/12/2024 | no BEN= required
| LONNYS | LONNYS | | BEN= | C | 7993415 |
BRYAN CONSTRUCTION, INC. | BSP | P | 12/06/2023 | site visit to verify laundry partition is non rated / laundry wall is non rated partition no penetration protection required | LONNYS | LONNYS | | BSP | P | 7937705 |
BRYAN CONSTRUCTION, INC. | BFR | P | 11/17/2023 | interior light gauge steel wall framing OK pending other required inspections / reviewed ramps and other accessible elements with site rep | LONNYS | LONNYS | | BFR | P | 7922740 |
BIBLE ELECTRIC, INC. | E= | C | 02/08/2024 | ok per pics | BRIAN | BRIAN | | E= | C | 7990341 |
BIBLE ELECTRIC, INC. | E= | C | 02/08/2024 | corrections made | BRIAN | BRIAN | | E= | C | 7990330 |
BIBLE ELECTRIC, INC. | E= | P | 02/07/2024 | need working clearance on water heater or install 60 amp breaker and breaker lock and remove the disco / rest ok / | BRIAN | BRIAN | | E= | P | 7989486 |
BIBLE ELECTRIC, INC. | E= | R | 01/30/2024 | went over lighting controls and recepts / need gfci protection in laundry and any recept within 6' of sink in exam room / | BRIAN | BRIAN | | E= | R | 7981836 |
BIBLE ELECTRIC, INC. | ER | C | 01/26/2024 | rest of grid ceilings | BRIAN | BRIAN | | ER | C | 7978945 |
FIRE ALARM SERVICES, INC. | E= | C | 01/19/2024 | FIRE ALARM INSPECTION: | BRIAN | BRIAN | | E= | C | 7972624 |
BIBLE ELECTRIC, INC. | ER | P | 01/16/2024 | ceilings except south west 2 rooms / need fire alarm / | BRIAN | BRIAN | | ER | P | 7969149 |
BIBLE ELECTRIC, INC. | ER | P | 12/27/2023 | reception desk--ok / | BRIAN | BRIAN | | ER | P | 7954120 |
BIBLE ELECTRIC, INC. | ER | P | 10/25/2023 | elect ok / still need fire alarm / missing reception area rest ok / WALLS only | BRIAN | BRIAN | | ER | P | 7898996 |
COLORADO SHEET METAL CO., INC. | H= | C | 02/07/2024 | TEST AND BALANCE REPORT RECEIVED - SEE IMAGES | MARKB | MARKB | | H= | C | 7989052 |
COLORADO SHEET METAL CO., INC. | HD | P | 01/24/2024 | BACK-DRAFT DAMPER INSTALLED ON DRYER DUCT - SEE IMAGES | MARKB | MARKB | | HD | P | 7976059 |
COLORADO SHEET METAL CO., INC. | H= | P | 01/23/2024 | FINAL PENDING - Complete exhaust duct tie in at main for room 114. Need to verify thermostat is installed and operation for transfer fan. Install back-draft damper on dryer duct. Provide test and balance report. | MARKB | MARKB | | H= | P | 7974973 |
COLORADO SHEET METAL CO., INC. | HD | P | 01/12/2024 | THIS INSPECTION WAS FOR ABOVE CEILING DUCT WORK. CONFIRM EXHAUST FAN TIE ENDS AND TERMINATION AT FINAL. NOTE / ABOVE CEILING SUPPLY RUNS AND DIFFUSERS (((OK)))) | NICKE | NICKE | | HD | P | 7966950 |
COLORADO SHEET METAL CO., INC. | HSP | P | 12/14/2023 | ON SITE DISCUSSION ABOUT EXHAUST TERMINATION. MAY NEED TO CONSULT WITH STRUCTURAL ENGINEER OR BUILDING INSPECTOR IF CORE DRILLING STRUCTURAL MEMBERS. | MARKB | MARKB | | HSP | P | 7945586 |
COLORADO SHEET METAL CO., INC. | HD | P | 12/07/2023 | DRYER DUCT IN WALL OK TO COVER - Still need to complete dryer duct above ceiling to the outdoors. | MARKB | MARKB | | HD | P | 7938253 |
COLORADO SHEET METAL CO., INC. | HD | P | 12/05/2023 | DRYER DUCT - Need building inspector to verify if this dryer box is in a rated wall and requires additional protection. Duct seams need to be sealed with UL 181 mastic or tape. Will need to reinspect after building inspection. | MARKB | MARKB | | HD | P | 7935484 |
COLORADO SHEET METAL CO., INC. | HD | P | 10/11/2023 | --Need plumbing contractor attached to permit. ABOVE CEILING DUCT - SUPPLY MAINS/BRANCHES FOR VAV'S 1, 2 & 3 INSTALLED PER PLAN OK TO WRAP. No flex, diffusers or exhaust at this time. | MARKB | MARKB | | HD | P | 7884640 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | C | 02/23/2024 | | TRAVISR | TRAVISR | | P= | C | 8003916 |
HARMON - BONDED PLUMBING & HEATING, INC. | P= | P | 02/08/2024 | Need Plans To Reflect Notes Made @ PTO Inspection Need Undersink Guards @ Restroom Need Flush Handle @ Tank To Open Side / Rest Ok | TRAVISR | TRAVISR | | P= | P | 7990489 |
HARMON - BONDED PLUMBING & HEATING, INC. | PTO | P | 11/02/2023 | Need Plans To Reflect Multiple Areas Of DWV Tie In Instead Of 1 As Plans Call For Need Plans To reflect Use OF AAV's In Lieu Of VTR Tie In Need Plans To Reflect H20 Tie In Not Per Plan Need In Ceiling H20 Insulated Per Plans
Above Floor DWV & H20 OK | TRAVISR | TRAVISR | | PTO | P | 7906632 |
HARMON - BONDED PLUMBING & HEATING, INC. | PB | P | 11/02/2023 | Need Plans To Reflect Multiple Areas Of DWV Tie In Instead Of 1 As Plans Call For Need Plans To reflect Use OF AAV's In Lieu Of VTR Tie In Need Plans To Reflect H20 Tie In Not Per Plan
Under Floor DWV & H20 OK
| TRAVISR | TRAVISR | | PB | P | 7906631 |