WELLS & WEST GENERAL CONTRACTORS, INC. | B= | C | 03/07/2024 | All other required Final inspections are complete. (This is a computer generated result) | BRIANB | BRIANB | | B= | C | 8016574 |
WELLS & WEST GENERAL CONTRACTORS, INC. | B= | P | 02/08/2024 | pending other final inspections. Additional Inspections Required (computer generated): NATCO ELECTRIC, INC. Electrical Final Inspection is not Completed yet, PEAK HEATING & AIR CONDITIONING, INC. Mechanical Final Inspection is not Completed yet, DRUMMOND PLUMBING LLC Plumbing Final Inspection is not Completed yet. | BRIANB | BRIANB | | B= | P | 7990705 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 11/13/2023 | Hard lid framing ok / | ERIKK | ERIKK | | BFR | P | 7917045 |
WELLS & WEST GENERAL CONTRACTORS, INC. | BFR | P | 10/19/2023 | Need other rough inspections completed / Frame ok / Reviewed Accessible Elements / | ERIKK | ERIKK | | BFR | P | 7893276 |
NATCO ELECTRIC, INC. | E= | C | 02/12/2024 | Corrections made | BRETC | BRETC | | E= | C | 7993400 |
NATCO ELECTRIC, INC. | E= | P | 01/25/2024 | Two built in microwaves on one 20 amp circuit, need 2 circuits for wattage, built in microwaves will need breaker locks installed / Label panel 5RB + arc flash & handle ties, panel - Ok / Water heater - Ok | BRETC | BRETC | | E= | P | 7977199 |
NATCO ELECTRIC, INC. | ER | C | 12/11/2023 | Leave ceiling open around water heater in ceiling, Need #10 and correct brkr to W/H / Rest of ceilings - Ok | BRETC | BRETC | | ER | C | 7941467 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 12/08/2023 | FIRE ALARM INSPECTION: | BRETC | BRETC | | E= | C | 7940192 |
SPECIAL SYSTEMS DESIGN,LLC | ER | C | 12/08/2023 | FIRE ALARM INSPECTION: | BRETC | BRETC | | ER | C | 7940189 |
NATCO ELECTRIC, INC. | ER | P | 11/08/2023 | Front area hall ceiling only - OK / Abandoned FA cable removed / Pictures sent to phone | BRETC | BRETC | | ER | P | 7912108 |
NATCO ELECTRIC, INC. | ER | P | 11/06/2023 | Need to address open FA wiring at entry, do not cover that area / Ok up to 4 ceiling can lights in hallway | BRETC | BRETC | | ER | P | 7909537 |
SPECIAL SYSTEMS DESIGN,LLC | ER | P | 10/19/2023 | FIRE ALARM INSPECTION: 5 devices in walls ok | CRAIG | CRAIG | | ER | P | 7892825 |
NATCO ELECTRIC, INC. | ER | P | 10/19/2023 | marked on plans E.2 walls only | CRAIG | CRAIG | | ER | P | 7892822 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | C | 02/28/2024 | T-STAT IN ROOM 311 WAS NOTE RELOCATED / MECHANICAL FINAL OK / | LIDO | LIDO | | H= | C | 8009353 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 01/25/2024 | FINAL PENDING: ROOM 311 T-STAT INSTALLED OVER 48" ABOVE THE FLOOR. LOWER T-STAT OR OK TO INSTALL LOCK BOX / SERVER ROOM # 315 MISSING LINE VOLTAGE T-STAT. UNDER CUT DOOR 3/4" AS PER NOTE 1 / | LIDO | LIDO | | H= | P | 7977887 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | P | 01/25/2024 | TAB report, see images / On site inspection scheduled for today. | SAMS | SAMS | | H= | P | 7977186 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | C | 12/06/2023 | ALL ABOVE CEILING OK / | LIDO | LIDO | | HD | C | 7937856 |
PEAK HEATING & AIR CONDITIONING, INC. | H= | R | 11/22/2023 | NOT READY FOR FINAL / | LIDO | LIDO | | H= | R | 7926110 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 11/22/2023 | NOT READY / PLYWOOD REPLACED WITH PLENUM RATED MATERIAL TO SUPPORT EXPANSION TANK OK / | STEPHANIEV | STEPHANIEV | | HD | P | 7926106 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 11/15/2023 | THIS HAS AN ABOVE CEILING PLENUM RETURN, ALL NEW MATERIALS INSTALLED IN PLENUM MUST BE PLENUM RATED. / PLYWOOD USED TO SUPPORT WATER HEATER EXPANSION TANK IS NOT PLENUM RATED AND WILL NEED TO REPLACED WITH PLENUM RATED MATERIAL / | STEPHANIEV | STEPHANIEV | | HD | P | 7919509 |
PEAK HEATING & AIR CONDITIONING, INC. | HD | P | 11/15/2023 | ABOVE CEILING DUCT ROUGH: (N) VAV1,2,4 AND 5 - INSTALL ALL END CAPS FOR L/P DUCT TRUNK LINE / LOW PRESSURE (L/P) SUPPLY TRUNK LINE AND LATERAL RUN OUTS OK. OK TO INSULATE (vav's and m/p duct not installed) / (E) VAV-3 AND 6 - LOW PRESSURE SUPPLY TRUNK LINE AND LATERAL RUN OUTS OK. OK TO INSULATE / | LIDO | LIDO | | HD | P | 7919480 |
DRUMMOND PLUMBING LLC | P= | C | 03/07/2024 | engineers letter ok ( see images ). | TAYLOR | TAYLOR | | P= | C | 8016573 |
DRUMMOND PLUMBING LLC | P= | R | 03/01/2024 | need engineers stamp on approved letter. | TAYLOR | TAYLOR | | P= | R | 8010947 |
DRUMMOND PLUMBING LLC | P= | P | 02/06/2024 | still need engineers letter as previously noted, rest ok. | TAYLOR | TAYLOR | | P= | P | 7988401 |
DRUMMOND PLUMBING LLC | PTO | C | 02/06/2024 | | TAYLOR | TAYLOR | | PTO | C | 7988394 |
DRUMMOND PLUMBING LLC | P= | L | 02/02/2024 | field cancelled. | TAYLOR | TAYLOR | | P= | L | 7985291 |
DRUMMOND PLUMBING LLC | P= | R | 01/29/2024 | Need PTO items complete prior to this inspection | ADRIANM | ADRIANM | | P= | R | 7980024 |
DRUMMOND PLUMBING LLC | PTO | P | 01/19/2024 | test required for DWV after adding VTR, need engineers letter for Rheem water heater. | TAYLOR | TAYLOR | | PTO | P | 7972097 |
DRUMMOND PLUMBING LLC | PTO | P | 11/14/2023 | -Need letter from engineer of record accepting AAV @ sink in lieu of extending vent through roof , rest ok -OK on water heater install | FRANKM | FRANKM | | PTO | P | 7918462 |
DRUMMOND PLUMBING LLC | PTO | P | 11/10/2023 | -Need letter from engineer of record accepting AAV @ sink in lieu of extending vent through roof / permanently cap abandoned VTR / insulate H2O -OK on in wall & overhead DWV only pending engineer letter Note : no water heater & associated piping @ this time | FRANKM | FRANKM | | PTO | P | 7915724 |