HAMMER HOMES, INC. | BLA | C | 04/15/2024 | | TRENTP | TRENTP | | BLA | C | 8052880 |
HAMMER HOMES, INC. | BIN | R | 03/27/2024 | Need to complete foundation inspections / Insulation okay, all certificates and evaluation reports on file / Will inspect attic insulation at final, need air leakage test results by final | TRENTP | TRENTP | | BIN | R | 8034742 |
HAMMER HOMES, INC. | BFR | R | 03/27/2024 | Need to complete foundation inspections / Rest okay | TRENTP | TRENTP | | BFR | R | 8034739 |
HAMMER HOMES, INC. | BSP | P | 03/27/2024 | Installers certificates for spray foam, blown in, and DC315 on file / Evaluation report on file for spray foam insulation | TRENTP | TRENTP | | BSP | P | 8034222 |
HAMMER HOMES, INC. | BSP | P | 03/27/2024 | Evaluation report on file for DC315 | TRENTP | TRENTP | | BSP | P | 8034219 |
HAMMER HOMES, INC. | BFR | R | 03/22/2024 | Still need to complete items 1 and 2 from previous inspection / Rest okay / Note: Will inspect front porch posts as BSP at later date when ready | TRENTP | TRENTP | | BFR | R | 8030665 |
HAMMER HOMES, INC. | BFR | R | 03/20/2024 | 1. Need to complete foundation inspections / 2. Missing roof jacks for dry in / 3. Missing bearing block at north bearing point for T03E / 4. Missing VTCRs at multiple overframe V trusses / 5. Missing fireblocking at bottom of steel post in bedroom 2 / 6. Unable to confirm ST18 at house bearing point for north rear porch cover beam, rest of rear porch lid and posts okay / 7. Front porch missing post, front porch lid okay / Crawlspace, no deck | TRENTP | TRENTP | | BFR | R | 8027816 |
HAMMER HOMES, INC. | BSP | R | 03/06/2024 | Inspection stopped and changed to BSP after too many items / Contractor to review all notes, plan callouts and hardware requirements / House not dried in / Need to complete foundation inspections / Multiple exterior frame items covered without history of inspection | TRENTP | TRENTP | | BSP | R | 8015881 |
HAMMER HOMES, INC. | BSP | P | 03/06/2024 | Engineered truss designs on file | TRENTP | TRENTP | | BSP | P | 8015392 |
HAMMER HOMES, INC. | BSP | P | 12/01/2023 | EZ flow drain instructions on file | TRENTP | TRENTP | | BSP | P | 7932705 |
HAMMER HOMES, INC. | BFI | C | 11/30/2023 | R10 installed at garage / Note: Need to complete other foundation inspections | TRENTP | TRENTP | | BFI | C | 7932190 |
HAMMER HOMES, INC. | BFD | P | 11/30/2023 | Need to complete other foundation inspections / Need to provide EZ flow drain installation instructions / Drain around usable to day light at northwest, dampproofing okay / Drain ok / Contractor to backfill per requirements of Soils Report / | TRENTP | TRENTP | | BFD | P | 7932187 |
HAMMER HOMES, INC. | BFN | P | 11/30/2023 | Engineer letter on file states exterior piers were not inspected, need to provide observation or request inspection / Engineer letter for foundation on file -- Eufer noted / Foundation design on file (Bearing Capacity Verified) / | TRENTP | TRENTP | | BFN | P | 7931088 |
HAMMER HOMES, INC. | BFT | P | 11/21/2023 | Still need to provide footing observation / Open hole on file, 3500 psf | TRENTP | TRENTP | | BFT | P | 7924477 |
HAMMER HOMES, INC. | BFT | P | 11/16/2023 | Changed to BFT / Need to provide open hole and footing observation / Soil report and update letter on file, usable - 5% / Foundation design on file, need to verify bearing capacity | TRENTP | TRENTP | | BFT | P | 7920331 |
DUKES ELECTRIC, INC | ER | C | 02/26/2024 | 1 - 4/0 SER , 1 - #2 SER , 1 - # 6 CU , 2 - # 10 , irreversible ufer , no mcc , no central vac , crawl space | TOMC | TOMC | | ER | C | 8006624 |
DUKES ELECTRIC, INC | EUG | C | 12/13/2023 | 4/0-4/0-4/0 | BRET | BRET | | EUG | C | 7943697 |
RTB PROPERTIES LLC | HC | C | 03/05/2024 | RELEASE METER | SAMS | SAMS | | HC | C | 8014450 |
RTB PROPERTIES LLC | HRR | C | 03/05/2024 | By final provide the duct leakage report and the mechanical exhaust readings. | SAMS | SAMS | | HRR | C | 8014448 |
RTB PROPERTIES LLC | HRR | P | 03/04/2024 | Splice submitted for the changed IECC insulation form, see images / Per contractor notes no on site inspection today. | SAMS | SAMS | | HRR | P | 8012622 |
RTB PROPERTIES LLC | HRR | P | 03/01/2024 | No on site inspection today per contractor notes // IECC insulation form must be sent to and approved by the plan review if it is being changed. See images. // Recall inspection when ready. | SAMS | SAMS | | HRR | P | 8010931 |
RTB PROPERTIES LLC | HRR | P | 02/28/2024 | By final provide duct leakage report per IECC R403.3.6 #3. All ducts and equipment are located within building thermal envelope / By final provide readings for all mechanical ventilation systems. Whole House Ventilation must meet minimum CFM's shown on IECC/IRC Ventilation Verification form. Local exhaust must meet the requirements of IRC Table M1505.4.4. Kitchen range hood exhaust reading not required if installation meets IECC R403.6.3 Exception // MORE EFFICIENT HVAC EQUIPMENT PERFORMANCE (IECC R408.2.2) WAS SELECTED ON THE 2021 IECC FORM. CONDENSER LISTED ON HEAT LOSS CALCS DOES NOT MEET MINIMUM REQUIREMENT / PER CONTRACTOR APRILAIR WHOLE HOUSE VENTILATION (OR EQUIVALENT) TO BE INSTALLED BY FINAL. OSA TERMINATION AND INSULATED 6" IN ATTIC OK / GARAGE HEATER NOT INSTALLED AT TIME OF INSPECTION. 4" B-VENT OK / INSULATE FURNACE EXHAUST VENT PIPE IN ATTIC PER MANUFACTURERS INSTALLATION INSTRUCTIONS / OK TO ATTACH PICTURE OF CORRECTION TO AN INSPECTION REQUEST // Whole house ventilation being achieved with dampered outside air duct to furnace return. / Verify whole house ventilation switch location at final / NOTE / CONDITIONED CRAWL SPACE / OUTSIDE AIR WITH DAMPER TO FURNACE RETURN / DIRECT VENT FURNACE / DIRECT VENT WATER HEATER / A/C ROUGH, COIL AND LINESET / | STEPHANIEV | STEPHANIEV | | HRR | P | 8009355 |
CORNERSTONE PLUMBING INC | HI | C | 02/28/2024 | 10 LB TEST OK / | STEPHANIEV | STEPHANIEV | | HI | C | 8009265 |
CORNERSTONE PLUMBING INC | HI | P | 02/27/2024 | LOW TEST 7LBS 1 1/4 inch main / 1 furnace / 1 fireplace / 1 water heater / 1 cooktop / 1 BBQ (1/2''Rigid@90')/ 1 garage heater (3/4''Rigid@35')/ | SAMS | SAMS | | HI | P | 8007348 |
WESTERN FIREPLACE SUPPLY, INC. | HV | C | 02/07/2024 | Main level fireplace clearance to combustibles and vent termination ok. / Non-combustible materials installed / | SAMS | SAMS | | HV | C | 7989872 |
HOMEOWNER | PWO | C | 04/19/2024 | H2O looped in 1" HDPE Note: Need potable water certification by final | PATRICKS | PATRICKS | | PWO | C | 8059280 |
CORNERSTONE PLUMBING INC | PIN | C | 02/23/2024 | | PATRICKS | PATRICKS | | PIN | C | 8004932 |
CORNERSTONE PLUMBING INC | PAV | C | 02/23/2024 | Water heater vent re-connected Note: Direct vent water heater roof terminations/ higher up vent exhaust | PATRICKS | PATRICKS | | PAV | C | 8004930 |
CORNERSTONE PLUMBING INC | PTO | C | 02/23/2024 | Water heater vent reconnected/ need PWO completed and potable water certification by final 2- VTR's/ irrigation stub/ direct vent water heater | PATRICKS | PATRICKS | | PTO | C | 8004922 |
CORNERSTONE PLUMBING INC | PSP | P | 02/23/2024 | Water Heater Plastic Vent by Plumbing Contractor | SYSTEM | SYSTEM | | PSP | P | 8003877 |
CORNERSTONE PLUMBING INC | PAV | P | 02/23/2024 | Test complete see image/ verify water heater vent re-connected at PTO | PATRICKS | PATRICKS | | PAV | P | 8003867 |
CORNERSTONE PLUMBING INC | PSP | P | 02/23/2024 | Water Heater Plastic Vent by Plumbing Contractor | SYSTEM | SYSTEM | | PSP | P | 8003747 |
CORNERSTONE PLUMBING INC | PSP | P | 02/23/2024 | Water Heater Plastic Vent by Plumbing Contractor | SYSTEM | SYSTEM | | PSP | P | 8003725 |
HAMMER HOMES, INC. | XBS | T | 03/01/2024 | PAID (REC#2039127) PLAN SPLICE FEE: $50 by: CGIECK for Construction: update IECC | CGIECK | CGIECK | | XBS | T | 8011926 |