ELDER CONSTRUCTION, INC. | B= | C | 05/02/2024 | All other required Final inspections are complete. (This is a computer generated result) | NATHAN | NATHAN | | B= | C | 8072383 |
ELDER CONSTRUCTION, INC. | B= | P | 04/29/2024 | With all completed required inspections B= okay. Additional Inspections Required (computer generated): External Agency Inspection F= by FIREDEPT is not Completed yet (Contact: 385-5982, x2), EL PASO ELECTRIC, LLC. Electrical Final Inspection is not Completed yet, HVAC SOLUTIONS, INC. Mechanical Final Inspection is not Completed yet. | NATHAN | NATHAN | | B= | P | 8068349 |
ELDER CONSTRUCTION, INC. | BEN= | C | 04/29/2024 | no BEN= required for interior remodel | LONNYS | LONNYS | | BEN= | C | 8067404 |
ELDER CONSTRUCTION, INC. | BFR | P | 03/07/2024 | Attach and complete all other required inspections / Metal framing OK including overhead soffits / Discussed accessible door hardware | ADAML | ADAML | | BFR | P | 8017926 |
EL PASO ELECTRIC, LLC. | E= | C | 04/30/2024 | | JIMMY | JIMMY | | E= | C | 8069867 |
EL PASO ELECTRIC, LLC. | E= | P | 04/26/2024 | Corrections made--all ok. Missing Requirement (computer generated): Contractor has an open splice that must be approved or canceled. | JIMMY | JIMMY | | E= | P | 8066764 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 04/26/2024 | FIRE ALARM INSPECTION: Added and reworked fire alarm ok | JIMMY | JIMMY | | E= | C | 8066763 |
SPECIAL SYSTEMS DESIGN,LLC | ER | C | 04/26/2024 | FIRE ALARM INSPECTION: | JIMMY | JIMMY | | ER | C | 8066756 |
SPECIAL SYSTEMS DESIGN,LLC | E= | C | 04/26/2024 | FIRE ALARM INSPECTION: | JIMMY | JIMMY | | E= | C | 8066757 |
EL PASO ELECTRIC, LLC. | E= | P | 04/25/2024 | Recep by cash register has no power--- all else ok-- signs ok | JIMMY | JIMMY | | E= | P | 8065118 |
EL PASO ELECTRIC, LLC. | ER | P | 04/25/2024 | Fire alarm needs secured to the ceiling grid and supported--- rest of ceiling ok | JIMMY | JIMMY | | ER | P | 8065117 |
EL PASO ELECTRIC, LLC. | ER | R | 04/24/2024 | no answer at call ahead-- Need to remove lights above ceiling grid and safe off / Need all cabling supported so not resting on ceiling grid / Not all hurricane clips of light fixtures connected to the grid / Fire alarm needs to be installed to grid and called in--Open fire alarm box needs to be closed up / Whip for sign just coiled up and not stubbed out--- complete reinspect for ceiling | JIMMY | JIMMY | | ER | R | 8063058 |
EL PASO ELECTRIC, LLC. | ER | P | 03/08/2024 | walls only Discussed NPT connectors with contractor / Discussed accessibility requirements with contractor / | CRAIG | CRAIG | | ER | P | 8018260 |
HVAC SOLUTIONS, INC. | H= | C | 05/02/2024 | NOTE / CONTROLS ((OK)) | NICKE | NICKE | | H= | C | 8072382 |
HVAC SOLUTIONS, INC. | H= | P | 05/02/2024 | PARTIAL PENDING VERIFICATION OF CONTROLS PER PREVIOUS NOTES NOTE / TAB REPORT RECEIVED / SEE IMAGES / | JERRYF | JERRYF | | H= | P | 8071425 |
HVAC SOLUTIONS, INC. | H= | P | 04/22/2024 | PARTIAL PENDING THE FOLLOWING - TAB REPORT AND VERIFY CONTROLS (CONTRACTOR TO ATTACH PICTURES OF CONTROLS TO TAB REPORT NOTE / ALL SA / RA GRILLES / FINAL CONNECTIONS ARE COMPLETE / | JERRYF | JERRYF | | H= | P | 8060398 |
HARMON - BONDED PLUMBING & HEATING, INC. | H= | C | 04/22/2024 | NOTE / ALL FINAL CONNECTIONS / INSULATION / CONTROLS ARE COMPLETE / | JERRYF | JERRYF | | H= | C | 8060396 |
HARMON - BONDED PLUMBING & HEATING, INC. | HWP | P | 03/20/2024 | THIS INSPECTION WAS FOR HWP. AT FUTURE INSPECTION VERIFY BALANCING AND SOLENOID VALVES. NOTE HWP (((OK))) OK TO INSULATE | NICKE | NICKE | | HWP | P | 8027782 |
HVAC SOLUTIONS, INC. | HD | P | 03/18/2024 | NEED SOMEONE TO TO CLAIM HWP / CHILLED PIPING ON PERMIT ASAP (WORK IS ALREADY IN PROGRESS) NOTE / ABOVE CEILING SA / RA / MAINS / RUN OUTS / OK / | JERRYF | JERRYF | | HD | P | 8025080 |