MECHONE, INC. | HV | R | 09/26/2024 | NEED UNIT HEATER INSTALL INSTRUCTIONS FOR UNIT HEATER PROVIDED AT TIME OF INSPECTION. | MARKB | MARKB | | HV | R | 8224465 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 09/26/2024 | FINAL PENDING - Need to provide 3rd party test report for ground source system per 2021 imc code section 1210.10 for system covered prior to inspection. BUILDING SUPPLY/RETURN PIPING INSULATION COMPLETE. | MARKB | MARKB | | H= | P | 8224464 |
OLSON PLUMBING & HEATING COMPANY | H= | P | 08/08/2024 | THIS INSPECTION FOR BDA PAGE #15, PLAN PAGE M-401--- ALL HYDRONIC PIPING INSTALLED AS PER APPROVED PLANS. SYSTEM UNDER OPERATING PRESSURE WITH NO VISIBLE LEAKS. OK TO INSULATE. | BILLS | BILLS | | H= | P | 8173746 |
OLSON PLUMBING & HEATING COMPANY | H= | L | 08/02/2024 | CALL AHEAD NOT ANSWERING PHONE. WAITED ON SITE BUT COULD NOT MAKE CONTACT. | MARKB | MARKB | | H= | L | 8168416 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 07/24/2024 | THIS INSPECTION WAS FOR BDA PAGE 13 PLAN PAGE M-103 / PRESSURE TEST OK AT ROOF FOR GWS/R PIPING / PIPING INSTALLED PER PLAN / OK FOR SUPPORT / OK TO INSULATE | MICHAELM | MICHAELM | | HWP | P | 8157815 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 07/22/2024 | THIS INSPECTION FOR BDA PAGE #11 PLAN PAGE M-101--- PRESSURE TEST OK FOR VENTILATORS #12, 13, AND 14,, CLASSROOMS #7, 8, AND 9. FROM VENTILATORS TO RTU (EXCEPT FOR THE BRANCHES TO MUSIC/BAND ROOM #13. | BILLS | BILLS | | HWP | P | 8154257 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 07/16/2024 | THIS INSPECTION FOR BDA PAGE #12,, PLAN PAGE M-102--- PRESSURE TESTS (2) OK. INSTALLED AS PER APPROVED PLANS. INSPECTION FOR LINES FROM VENTILATORS TO TIE-INS AT ROOF FOR VENTILATORS #01, 02, 03, 04-A, 04-B, FAN COILS #01 AND 02. (CLASSROOMS #1, 2, 3, KINDERGARTEN #24, AND MAIN OFFICE). | BILLS | BILLS | | HWP | P | 8148308 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 07/11/2024 | THIS INSPECTION FOR BDA PAGES #12 AND #13, PLAN PAGES M-102 AND M-103--- PRESSURE TEST AND PIPING TO VENTILATORS #5, 6, AND 7 (CLASSROOMS #4, 5, AND 6)OK. | BILLS | BILLS | | HWP | P | 8144427 |
MECHONE, INC. | HD | P | 06/28/2024 | VAV'S 2.01, 2.02, 2.03, AND 2.04 ALL OK. OK TO WRAP. MEZZANINE-- ALL SUPPLY, RETURN, AND OUTSIDE AIR OK EXCEPT THE WEST SUPPLY AIR TRANSITION AT WALL AND OUTSIDE AIR TRANSITION TO LOUVER. OK TO WRAP. AREA "B"-- NEED PLAN SPLICE BY FINAL FOR CHANGE IN RETURN AIR PIPE SIZING (12" TO 2-8" X2) AND CHANGES TO SUPPLY AIRS (10" TO 8" @ TEACHERS LOUNGE) AND ADDED 6" @ TEACHERS LOUNGE). ALL INSTALLED PIPING OK TO WRAP. | BILLS | BILLS | | HD | P | 8133189 |
OLSON PLUMBING & HEATING COMPANY | HWP | P | 06/19/2024 | PRESSURE TEST OK ON 3 UNIT VENTILATORS | MICHAELM | MICHAELM | | HWP | P | 8123009 |