Scanned/Finished Bin | Original | / | 10/20/2017 | | JESSICAM | Location = Scanned/Finished Bin by JESSICAM | | Scanned/Finished Bin | 1005767 |
To Be Scanned Bin | Original | / | 10/19/2017 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 1005703 |
Out to Review | Original | / | 10/19/2017 | MBINGMAN | MBINGMAN | Out to Teri | | Out to Review | 1005691 |
CO Springs DRE | Original | A | 10/19/2017 | MBINGMAN | MBINGMAN | UV & CU do not affect this request. CR's do regulate that no outdoor storage or unenlcosed activity in the rear of the businesses will occur - inserted with BP. Parking is for commercial center. Consistent with zoning and dp requirements. (see full review) | | CO Springs DRE | 1005690 |
Construction | Original | A | 10/19/2017 | DANM | DANM | | | Construction | 1005656 |
Electrical | Original | A | 10/18/2017 | SHELBY | SHELBY | | | Electrical | 1005338 |
Construction | Original | D | 10/18/2017 | SHELLEY | SHELLEY | Exceeds common path of 75', two exits required and must comply. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1005320 |
Out to Review | Original | / | 10/18/2017 | AMY | AMY | | | Out to Review | 1005311 |
Enumeration | Original | A | 10/18/2017 | AMY | AMY | 2849 E FOUNTAIN BLVD | | Enumeration | 1005310 |
Enumeration | Original | / | 10/18/2017 | | AMY | Location = Enumeration by AMY | | Enumeration | 1005288 |
Mechanical | Original | N | 10/18/2017 | JUSTINC | JUSTINC | Mechanical has been provided for reference and to show engineers ventilation Test and balance report to be provided to mechanical engineer. | | Mechanical | 1005283 |
Hazmat | Original | N | 10/5/2017 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1001662 |
Hazmat | Original | / | 10/2/2017 | | SCANNING | Location = Hazmat by SCANNING | | Hazmat | 1000369 |
Water Division | Original | A | 10/2/2017 | CSUREVIEW | CSUREVIEW | Backflow device ok. RDS | rsolberg | Water Division | 1000351 |
Waste Water Div | Original | A | 10/2/2017 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Waste Water Div | 1000350 |
CO Springs Fire | Original | A | 9/29/2017 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 999928 |
Fire | Original | / | 9/22/2017 | | GSANDERS | Location = Fire by GSANDERS | | Fire | 997697 |
CO Springs DRE | Original | D | 9/22/2017 | GSANDERS | GSANDERS | Will be re-reviewed when Enumerations comments are addressed. Parking is at commercial center standards and meets the DP requirements. (see full review) | | CO Springs DRE | 997696 |
Zoning/Planning | Original | / | 9/19/2017 | GSANDERS | GSANDERS | In Current Review by GSANDERS | | Zoning/Planning | 996719 |
Zoning/Planning | Original | / | 9/19/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 996698 |
Plan Coordinator | Original | / | 9/19/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 996693 |
Plumbing | Original | A | 9/19/2017 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 996692 |
Plumbing | Original | / | 9/18/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 996430 |
Plan Coordinator | Original | / | 9/18/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 996326 |
Mechanical | Original | D | 9/18/2017 | JUSTINC | JUSTINC | Plan indicates change of occupancy
Provide complete mechanical drawings indicating duct routing, duct sizes, CFM, ventilation schedule, equipment schedule, etc...
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 996325 |
Mechanical | Original | / | 9/18/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 996310 |
Mechanical | Original | / | 9/15/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 996094 |
Plan Coordinator | Original | / | 9/15/2017 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 996042 |
Electrical | Original | D | 9/15/2017 | BERTHA | BERTHA | Provide electrical.
Specify heights of all existing and new electrical devices. Indicate compliance with 210.8 NEC and ANSI 117.1.”
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 996041 |
Electrical | Original | / | 9/13/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 995330 |
Enumeration | Original | / | 9/13/2017 | | SCANNING | Location = Enumeration by SCANNING | | Enumeration | 995322 |
Electrical | Original | / | 9/13/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 995218 |
Plan Coordinator | Original | / | 9/13/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 995206 |
Construction | Original | D | 9/13/2017 | DANM | DANM | Per IBC 1104.5 accessible route shall not pass through storage for rear exit Walk-through review OK (Note: Any work to adjacent space will require an Interior Finish since no Cert. of Occ exists)
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 995205 |
Construction | Original | / | 9/13/2017 | DANM | DANM | In Current Review by DANM | | Construction | 995095 |
Construction | Original | / | 9/12/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 994949 |
Plan Coordinator | Original | / | 9/12/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 994876 |
Floodplain | Original | N | 9/12/2017 | AMY | AMY | FLOODPLAIN ON THE PROPERTY BUT NOT ON THE BUILDING | | Floodplain | 994879 |
Enumeration | Original | D | 9/12/2017 | AMY | AMY | PERMIT HISTORY ON THIS BUILDING INDICATING SEPARATION OF SPACE HAS NOT BEEN SEEN IN OVER 20 YEARS, PLEASE SHOW TO DATE THE SEPARATION OF SPACE PER TENANT FROM THE OUTSIDE OF THE BUILDING FROM END TO END WITH ALL ADDRESSING LABELED. WHAT IS SHOWN ON PAGE LSP1.1 IS NOT DEPICTED CORRECTLY. CLOUD THIS SCOPE OF WORK FOR THIS PLAN. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 994875 |
Enumeration | Original | / | 9/12/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 994857 |