Out to Review | Original | / | 10/4/2017 | RITA | RITA | Jason 719-357-0851 | | Out to Review | 1000971 |
Finished Bin | Original | / | 10/3/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1000762 |
Plan Coordinator | Original | / | 10/3/2017 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1000715 |
Plumbing | Original | D | 10/3/2017 | TCRIPPEN | TCRIPPEN | Alternates not allowed, future work not reviewed , provide details of black water dump stations see metal dump station on web with foot pedal and concrete pad show hose bib as well , sand/oil interceptor required for floor drains in shop area not show on plan, see section 403.4 of the 2015 IPC rest rooms to be in a public utilization area not service bays, Gas pipe and related items to be on the M-pages per our web site.show water entry room with water meter back flow device and floor drain, provide an water pipe size analysis data on plans, schedule all materials to be used on this job and types copper , cast iron, pex tepid water required for eye wash ///// no walk through plans to be resubmitted only /////. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1000713 |
Plumbing | Original | / | 9/25/2017 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 998297 |
Plan Coordinator | Original | / | 9/25/2017 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 998283 |
Mechanical | Original | D | 9/25/2017 | DALEH | DALEH | provide a balance schedule provide an interlock schedule provide a ventilation schedule per IMC 09 table 403.3 see plans for complete red lines return red lines with next review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 998282 |
Mechanical | Original | / | 9/25/2017 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 998270 |
Mechanical | Original | / | 9/25/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 998252 |
Plan Coordinator | Original | / | 9/25/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 998190 |
Electrical | Original | D | 9/25/2017 | SHELBY | SHELBY | 1. Specify major or minor repair garage ( 511.2 NEC). 2. Show method of compliance with 511.3, and 511.3(E)(1) NEC. 3. T2 feeder equipment ground sized incorrectly. 4. T2 GEC sized incorrectly. 5. P2 feeder sized incorrectly. 6. Show SCA and AIC at and for all electrical gear in this scope. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 998189 |
Electrical | Original | / | 9/22/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 997804 |
Electrical | Original | / | 9/21/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 997662 |
Plan Coordinator | Original | / | 9/21/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 997650 |
Construction | Original | D | 9/21/2017 | DANM | DANM | Slab number on IECC Commercial Certificate should reflect the perimeter and not the area Provide full set of engineered metal building drawings Structure should be designed to the 2009 IBC and the ASCE 7-05 Reference attached Soils Report on Sheet S100 Alternates not allowed as shown on building elevations Clarify how IBC 1210 Surrounding Materials is being met in restrooms No walk-through review allowed
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 997649 |
Construction | Original | / | 9/21/2017 | DANM | DANM | In Current Review by DANM | | Construction | 997584 |
Construction | Original | / | 9/20/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 997134 |
Plan Coordinator | Original | / | 9/20/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 997075 |
Floodplain | Original | N | 9/20/2017 | AMY | AMY | FLOODPLAIN ON THE LOT BUT NOT IN THE LOCATION OF WORK. | | Floodplain | 997077 |
Enumeration | Original | A | 9/20/2017 | AMY | AMY | COMMENTS MAY CHANGE, FOUNTAIN BUCKSLIP PROPOSAL REVIEW IS NOT DUE BACK UNTIL OCTOBER 2, 2017. | | Enumeration | 997074 |
Enumeration | Original | / | 9/19/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 996722 |