Construction | Splice 06/24/19 | A | 6/24/2019 | SHELLEY | SHELLEY | Revision 10 only - stud sizing on details. | | Construction | 1205790 |
Hazmat | Original | N | 4/24/2018 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1060995 |
CO Springs Fire | Original | N | 4/24/2018 | CSFIRE | CSFIRE | no fire final (see full review) | csfdit | CO Springs Fire | 1060994 |
Resubmittal 3 | Original | / | 4/19/2018 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1059396 |
Gas/Elec. Utils | Original | A | 4/13/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Gas/Elec. Utils | 1057237 |
Hazmat | Original | D | 4/13/2018 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1057171 |
CO Springs Fire | Original | D | 4/12/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1056890 |
CSU Contract Admin. | Original | A | 4/6/2018 | CSUAPPSPRM | CSUAPPSPRM | Development charges/fees paid. LMP | lmpope | CSU Contract Admin. | 1054880 |
Electrical | Original | A | 4/5/2018 | SHELBY | SHELBY | | | Electrical | 1054670 |
Plumbing | Original | A | 4/5/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1054415 |
City Engr | Original | A | 4/5/2018 | JDAGNILLO | JDAGNILLO | | | City Engr | 1054310 |
Mechanical | Original | A | 4/5/2018 | JUSTINC | JUSTINC | | | Mechanical | 1054303 |
Water Division | Original | A | 4/5/2018 | CSUREVIEW | CSUREVIEW | | ajuvera | Water Division | 1054260 |
Waste Water Div | Original | A | 4/5/2018 | CSUREVIEW | CSUREVIEW | | ajuvera | Waste Water Div | 1054257 |
Gas/Elec. Utils | Original | D | 4/5/2018 | CSUREVIEW | CSUREVIEW | Show electric meter location on the building elevations AJ | ajuvera | Gas/Elec. Utils | 1054256 |
Construction | Original | A | 4/4/2018 | DANM | DANM | | | Construction | 1054086 |
Electronic Plan | Original | / | 4/4/2018 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1054015 |
Enumeration | Original | A | 4/3/2018 | AMY | AMY | | | Enumeration | 1053090 |
Electronic Plan | Original | / | 4/3/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1053089 |
Resubmittal 2 | Original | / | 3/30/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1052640 |
Hazmat | Original | D | 1/11/2018 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1027854 |
CO Springs Fire | Original | D | 1/11/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1027852 |
City Engr | Original | D | 1/10/2018 | JDAGNILLO | JDAGNILLO | Include a copy of the Water Resources Engineering approved Grading and Erosion Control Plan in the electronic building permit set. jad | | City Engr | 1027505 |
Electrical | Original | A | 1/10/2018 | SHELBY | SHELBY | | | Electrical | 1027500 |
CO Springs DRE | Original | A | 1/10/2018 | DSEXTON | DSEXTON | Approved. DJS 1/10/2018 (see full review) | | CO Springs DRE | 1027397 |
Plumbing | Original | D | 1/9/2018 | TCRIPPEN | TCRIPPEN | remove items not used on this job back flow device required on water service (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1027305 |
Electronic Plan | Original | / | 1/9/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1027297 |
Zoning/Planning | Original | / | 1/9/2018 | DSEXTON | DSEXTON | In Current Review by DSEXTON | | Zoning/Planning | 1027271 |
CSU Contract Admin. | Original | D | 1/9/2018 | CSUAPPSPRM | CSUAPPSPRM | Requires Commercial Water Meter Sizing Form (https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information.ZJS | zshearer | CSU Contract Admin. | 1027141 |
Mechanical | Original | D | 1/9/2018 | JUSTINC | JUSTINC | Provide refrigeration calculations for the AC-2 units indicated on plan. Indicate if within allowable limits per 09' IMC 1103.1 If over allowable limits indicate on plan how protecting.
Only indicate scope of work associated with this permit
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1027062 |
Water Division | Original | D | 1/9/2018 | CSUREVIEW | CSUREVIEW | Requires approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg | mgackle | Water Division | 1027035 |
Waste Water Div | Original | D | 1/9/2018 | CSUREVIEW | CSUREVIEW | Requires approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg | mgackle | Waste Water Div | 1027034 |
Gas/Elec. Utils | Original | D | 1/9/2018 | CSUREVIEW | CSUREVIEW | Show the gas and electric meter locations on the elevation plan views to make sure gas regulator vent is at least 3ft away from any electric meter socket and openings like windows, doors, and garage doors. mjg | mgackle | Gas/Elec. Utils | 1027033 |
Construction | Original | D | 1/9/2018 | DANM | DANM | Door labels shown on Door Schedule do not match floor plan - prefix letter should be 'A' not 'CH'
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1027008 |
Electronic Plan | Original | / | 1/8/2018 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1026804 |
Enumeration | Original | A | 1/5/2018 | AMY | AMY | | | Enumeration | 1026116 |
Electronic Plan | Original | / | 1/5/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1026111 |
Resubmittal 1 | Original | / | 1/3/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1025603 |
Hazmat | Original | D | 11/15/2017 | CSFIRE | CSFIRE | | fdjah74 | Hazmat | 1013098 |
CO Springs Fire | Original | D | 11/15/2017 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A (see full review) | csfdit | CO Springs Fire | 1013097 |
CO Springs DRE | Original | D | 11/8/2017 | DSEXTON | DSEXTON | Disapprove. The Building Permit package does not include a copy of the approved PUD development plan. DJS 11/8/2017 (see full review) | | CO Springs DRE | 1011138 |
Electrical | Original | D | 11/7/2017 | BERTHA | BERTHA | 1. Remove all information not reflecting this scope of work. 2. Complete re review is necessary. 3. Eighteen plans in this series 101449, 101450, 101451, 101452, 101453, 101456, 101461, 101463, 101466, 101467, 101475, 101476, 101477, 101481, 101482, 101483, 101484, 101485
Refer to https://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202016.pdf
Call for consultation: Bertha 719-327-2911 or Shelby 719-327-2974
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1010805 |
Water Division | Original | D | 11/7/2017 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. Show location of amenity building on plans. RDS | rsolberg | Water Division | 1010767 |
Waste Water Div | Original | D | 11/7/2017 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. Show location of amenity building on plans. RDS | rsolberg | Waste Water Div | 1010766 |
Gas/Elec. Utils | Original | D | 11/7/2017 | CSUREVIEW | CSUREVIEW | Verify location of amenity building. If served with utilities show proposed gas and electric meters on building elevations. RDS | rsolberg | Gas/Elec. Utils | 1010765 |
Mechanical | Original | D | 11/7/2017 | JUSTINC | JUSTINC | Plan submitted is for parcel building and pavillions no indication of amenity building? Verify submittal.
MECHANICAL REVIEW INCOMPLETE
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1010658 |
Health Dept. | Original | N | 11/6/2017 | HEALTHDEPT | HEALTHDEPT | Plan review is not needed - Not applicable. JZ 719-575-8966 | Jzimmerman | Health Dept. | 1010406 |
CSU Contract Admin. | Original | D | 11/6/2017 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal and approval of Commercial Water Meter Sizing Form (CWMSF) and payment of development charges/fees. CWMSF available at https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf. Contact Customer Contract Administration at 719-668-8111 for more information. LMP | lmpope | CSU Contract Admin. | 1010377 |
Zoning/Planning | Original | / | 11/6/2017 | DSEXTON | DSEXTON | In Current Review by DSEXTON | | Zoning/Planning | 1010146 |
Plumbing | Original | D | 11/6/2017 | TCRIPPEN | TCRIPPEN | Need to schedule piping material to be used on this job. missing notes for numbers on plumbing layout page, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1010124 |
City Engr | Original | D | 11/3/2017 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Water Resources Engineering approved Grading and Erosion Control Plan in the electronic building permit set. jad | | City Engr | 1009925 |
Construction | Original | D | 11/3/2017 | DANM | DANM | Incorrect building area shown on Code Study Form Remove all details, sheets and assemblies that are not related to the Amenity Bldg scope of work for architectural & structural Several sheets appear to be missing from the submittal Door Schedule should include only those doors that are part of the Amenity Bldg ID sheets should be stamped and sealed - appears to incomplete Provide stamped interior elevations of restroom showing compliance for surrounding materials per IBC 1210 IECC 2009 enforced
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1009820 |
Electronic Plan | Original | / | 10/27/2017 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1007722 |
Enumeration | Original | D | 10/26/2017 | AMY | AMY | ON ARCHITECTURAL PAGE A-100 HIGHLIGHT OR PLACE AN ARROW TOWARDS THE AREA OF WORK AND LABEL ADDRESS FOR 7 BAY GARAGE STRUCTURAL PAGES S-104CH-ALL BUILDINGS THAT DO NOT APPLY TO THIS PLAN SHOULD BE CROSSED OUT OR REMOVED. ON CODE STUDY FORM CHANGE TO SPECIFIC WORK BEING COMPLETED WITH THIS PLAN-MAINTENANCE BUILDING. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1007291 |
Electronic Plan | Original | / | 10/26/2017 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1007282 |
Floodplain | Original | N | 10/23/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6220001012) | | Floodplain | 1006108 |