Out to Review | Original | / | 2/22/2018 | GITA | GITA | ken 3034676827 | | Out to Review | 1039928 |
Scanned/Finished Bin | Original | / | 2/7/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1035445 |
To Be Scanned Bin | Original | / | 2/6/2018 | | JANE | Location = To Be Scanned Bin by JANE | | To Be Scanned Bin | 1035142 |
Hazmat | Original | A | 2/1/2018 | JANE | JANE | | | Hazmat | 1034141 |
County Fire | Original | A | 2/1/2018 | JANE | JANE | | | County Fire | 1034140 |
Finished Bin | Original | / | 1/24/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1031474 |
County Zoning | Original | N | 1/24/2018 | DSDRANGEL | DSDRANGEL | | | County Zoning | 1031438 |
Zoning/Planning | Original | / | 1/23/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1030825 |
Plan Coordinator | Original | / | 1/23/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1030757 |
Electrical | Original | / | 1/22/2018 | | SHELBY | Location = Electrical by SHELBY | | Electrical | 1030737 |
Electrical | Original | N | 1/22/2018 | SHELBY | SHELBY | | | Electrical | 1030736 |
Finished Bin | Original | / | 1/8/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1026774 |
Plan Coordinator | Original | / | 1/8/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1026652 |
Electrical | Original | D | 1/8/2018 | SHELBY | SHELBY | 1. Scope of work is unclear. If scope is to add load include a load summary and complete panel schedule see https://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202016.pdf for panel schedule required information.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1026651 |
Electrical | Original | / | 1/8/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1026628 |
Electrical | Original | / | 12/29/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1025030 |
Plan Coordinator | Original | / | 12/29/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1025014 |
Enumeration | Original | A | 12/29/2017 | BRENT | BRENT | plan pages corrected to show the correct address | | Enumeration | 1025013 |
Enumeration | Original | / | 12/29/2017 | | MINDY | Location = Enumeration by MINDY | | Enumeration | 1024952 |
Resubmittal 1 | Original | / | 12/29/2017 | MINDY | MINDY | Resubmittal #1 | | Resubmittal 1 | 1024951 |
Finished Bin | Original | / | 11/30/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1016772 |
County Zoning | Original | D | 11/30/2017 | DSDRANGEL | DSDRANGEL | MUST CONTACT EPC PLANNING PRIOR TO APPROVAL | | County Zoning | 1016768 |
Zoning/Planning | Original | / | 11/30/2017 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1016569 |
Plan Coordinator | Original | / | 11/29/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1016535 |
Electrical | Original | D | 11/29/2017 | SHELBY | SHELBY | 1. Clearly specify new VS existing ( MMBS cabinet shown as new and existing on E-2 ). 2. Provide complete panel schedule. See https://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202016.pdf. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1016534 |
Electrical | Original | / | 11/29/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1016496 |
Electrical | Original | / | 11/20/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1014199 |
Plan Coordinator | Original | / | 11/20/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1014186 |
Mechanical | Original | N | 11/20/2017 | JUSTINC | JUSTINC | | | Mechanical | 1014185 |
Electrical | Original | / | 11/20/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electrical | 1014184 |
Electrical | Original | / | 11/15/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1013443 |
Plan Coordinator | Original | / | 11/15/2017 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1013410 |
Construction | Original | N | 11/15/2017 | BPHILLIPS | BPHILLIPS | | | Construction | 1013409 |
Construction | Original | / | 11/15/2017 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1013405 |
Construction | Original | / | 11/13/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 1012196 |
Plan Coordinator | Original | / | 11/13/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1012190 |
Enumeration | Original | D | 11/13/2017 | BRENT | BRENT | The assigned address for this cell site is 18604 Oil Well Rd. Code study form and plan pages need to be updated to show this address. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1012184 |
Floodplain | Original | N | 11/13/2017 | BRENT | BRENT | | | Floodplain | 1012180 |
Enumeration | Original | / | 11/9/2017 | | NELIDA | Location = Enumeration by NELIDA | | Enumeration | 1011919 |