Mechanical | Splice 4/3/18 | A | 4/3/2018 | TCRIPPEN | TCRIPPEN | new splice relocate thermostats, relocate sensor | | Mechanical | 1053259 |
Waste Water Div | Original | A | 1/19/2018 | GITA | GITA | | | Waste Water Div | 1030197 |
Water Division | Original | A | 1/19/2018 | GITA | GITA | | | Water Division | 1030196 |
Monument Zoning | Original | A | 1/19/2018 | GITA | GITA | | | Monument Zoning | 1030195 |
Tri-Lakes Fire | Original | A | 1/18/2018 | CSFIRE | CSFIRE | fees of $354.60 due - payable to City of Colorado Springs at Construction Services desk (see full review) | csfdit | Tri-Lakes Fire | 1029731 |
Mechanical | Original | A | 1/11/2018 | DALEH | DALEH | | | Mechanical | 1028179 |
Enumeration | Original | A | 1/11/2018 | AMY | AMY | SEE FLOOR PLAN WITH SUITE ON FRONT PAGE. | | Enumeration | 1028167 |
Plumbing | Original | A | 1/11/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1028164 |
Construction | Original | A | 1/11/2018 | MICHAELA | MICHAELA | | | Construction | 1028133 |
Out to Review | Original | / | 1/9/2018 | MINDY | MINDY | Chris 719 499 9141 | | Out to Review | 1027309 |
Fire | Original | / | 1/9/2018 | | SCANNING | Location = Fire by SCANNING | | Fire | 1027078 |
Plumbing | Original | D | 1/9/2018 | JUSTINC | JUSTINC | Comments from 1st review not addressed (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1027006 |
Plan Coordinator | Original | / | 1/9/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1027005 |
Mechanical | Original | D | 1/9/2018 | JUSTINC | JUSTINC | Comments from 1st review not addressed (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1027004 |
Mechanical | Original | / | 1/9/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1026951 |
Mechanical | Original | / | 1/8/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1026902 |
Plan Coordinator | Original | / | 1/8/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1026895 |
Construction | Original | D | 1/8/2018 | MICHAELA | MICHAELA | If laundry room will contain a single washer and dryer, residential style, rated walls wil not be required If not - address rating at existing wall Rated walls are fire barriers and must be continuous to the roof sheathing Still need 18" clear on the pull side of the Laundry door Walk-through with Michael only (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1026894 |
Construction | Original | / | 1/8/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1026841 |
Construction | Original | / | 1/8/2018 | | JANE | Location = Construction by JANE | | Construction | 1026796 |
Resubmittal 1 | Original | / | 1/8/2018 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 1026794 |
Out to Review | Original | / | 12/22/2017 | RITA | RITA | Colin 7169-499-3641 | | Out to Review | 1023674 |
Finished Bin | Original | / | 12/19/2017 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1022579 |
Plan Coordinator | Original | / | 12/19/2017 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1022474 |
Mechanical | Original | D | 12/19/2017 | JUSTINC | JUSTINC | Ducts shown penetrating rated fire barrier without protection. If intent is to use code section and exceptions then provide sheet notes indicating code sections and any exceptions used. Tag on floor plan at each penetration. OR provide dampers.
Please darken backgrounds. Too light for scanning.
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1022472 |
Mechanical | Original | / | 12/19/2017 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1022454 |
Mechanical | Original | / | 12/19/2017 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1022387 |
Plan Coordinator | Original | / | 12/18/2017 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1022352 |
Electrical | Original | A | 12/18/2017 | SHELBY | SHELBY | | | Electrical | 1022351 |
Electrical | Original | / | 12/18/2017 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1022203 |
Plumbing | Original | D | 12/13/2017 | TCRIPPEN | TCRIPPEN | High - low drinking fountain required, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1020866 |
Electrical | Original | / | 12/11/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1020045 |
Plan Coordinator | Original | / | 12/11/2017 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1020028 |
Construction | Original | D | 12/11/2017 | MICHAELA | MICHAELA | Laundry room greater that 100 sq. ft. must have a 1-hr. separation - provide assemblies for walls, door and glazing. Darken the background on the structural plans No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1020025 |
Construction | Original | / | 12/8/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1019894 |
Construction | Original | / | 12/5/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 1017858 |
Plan Coordinator | Original | / | 12/5/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1017849 |
Enumeration | Original | D | 12/5/2017 | AMY | AMY | CHANGE ALL PAGES TO SHOW SUITE NUMBER ASSIGNED #150 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1017848 |
Enumeration | Original | / | 12/5/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 1017841 |
Floodplain | Original | N | 11/30/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7125301002) | | Floodplain | 1016793 |