Construction | Splice 04/02/19 | A | 4/5/2019 | DANM | DANM | Add 2-ht shaftwall listed assembly located at elevators | | Construction | 1174989 |
Resubmittal 1 | Splice 04/02/19 | / | 4/5/2019 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 1174968 |
Construction | Splice 04/02/19 | D | 4/3/2019 | SHELLEY | SHELLEY | Provide floor plan showing location for this listing along with revised A0.4 designating a wall type for this wall. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1173809 |
Electrical | Splice 03/29/19 | A | 3/29/2019 | SHELBY | SHELBY | | | Electrical | 1172769 |
Plumbing | Splice 01/03/19 | A | 1/9/2019 | SHANEN | SHANEN | Added air admittance valve. Re-routed sump discharge line. | | Plumbing | 1148343 |
Resubmittal 1 | Splice 01/03/19 | / | 1/9/2019 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1148195 |
Plumbing | Splice 01/03/19 | D | 1/3/2019 | SHANEN | SHANEN | Missing engineers stamp and signature on all plumbing splice pages. Show drinking fountain and service sink on plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1146770 |
Electronic Plan | Splice 01/03/19 | / | 1/3/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1146647 |
Electrical | 10/1/18 | A | 10/11/2018 | SHELBY | SHELBY | As builts | | Electrical | 1119296 |
Resubmittal 2 | 10/1/18 | / | 10/11/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1118969 |
Electrical | 10/1/18 | D | 10/9/2018 | SHELBY | SHELBY | No electrical folder uploaded (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1118238 |
Plumbing | 10/1/18 | A | 10/5/2018 | TCRIPPEN | TCRIPPEN | new splice page redoing of interior space and reroute of plumbing to fixtures. | | Plumbing | 1116842 |
Electronic Plan | 10/1/18 | / | 10/5/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1116806 |
Construction | 10/1/18 | A | 10/4/2018 | SHELLEY | SHELLEY | Revised layout of units and office | | Construction | 1116746 |
Resubmittal 1 | 10/1/18 | / | 10/4/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1116583 |
Electrical | 10/1/18 | D | 10/3/2018 | SHELBY | SHELBY | Include revised retail detail. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1116181 |
Plumbing | 10/1/18 | D | 10/2/2018 | TCRIPPEN | TCRIPPEN | do to relocation of this area show the required drinking fountain on plan set. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1115917 |
Electronic Plan | 10/1/18 | / | 10/2/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1115899 |
Mechanical | 10/1/18 | A | 10/2/2018 | JUSTINC | JUSTINC | Revised retail area layout | | Mechanical | 1115633 |
Electronic Plan | 10/1/18 | / | 10/2/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1115615 |
Construction | 10/1/18 | D | 10/1/2018 | SHELLEY | SHELLEY | Several A pages missing stamp of design professional of record. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1115420 |
Mechanical | Splice 6/28/18 | A | 6/29/2018 | JUSTINC | JUSTINC | Gas revisions | | Mechanical | 1085356 |
CSU Contract Admin. | Original | A | 5/10/2018 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved, applicable development charges and fees paid 5/10/2018 MKL | mkluke | CSU Contract Admin. | 1067080 |
CSU Contract Admin. | Original | D | 5/8/2018 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved. Requires payment of development fees/charges. Please contact Development Services at 719-668-8111 for an estimate. AG | aguerin | CSU Contract Admin. | 1066191 |
Resubmittal 4 | Original | / | 5/3/2018 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1064496 |
CSU Contract Admin. | Original | D | 4/10/2018 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved. Requires payment of development charges/fees. LMP | lmpope | CSU Contract Admin. | 1055670 |
CO Springs DRE | Original | A | 3/29/2018 | KCARLEO | KCARLEO | All construction and development shall adhere to stamped approved development plan AR DP 17-00332 (see full review) | | CO Springs DRE | 1051702 |
Zoning/Planning | Original | / | 3/28/2018 | KCARLEO | KCARLEO | In Current Review by KCARLEO | | Zoning/Planning | 1051646 |
Elevators | Original | A | 3/28/2018 | ERIC | ERIC | ADDED CORRECTED E SHEETS | | Elevators | 1051218 |
Resubmittal 3 | Original | / | 3/28/2018 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1051168 |
Health Dept. | Original | N | 3/27/2018 | HEALTHDEPT | HEALTHDEPT | Construction activity permit is valid from 04/15/18 - 08/01/18. AB (719)578-3199 option 3 | abrannon | Health Dept. | 1050917 |
CSU Contract Admin. | Original | D | 3/27/2018 | CSUAPPSPRM | CSUAPPSPRM | Same comments as previous. ZJS | zshearer | CSU Contract Admin. | 1050820 |
CO Springs DRE | Original | D | 3/26/2018 | KCARLEO | KCARLEO | Need to include a copy of the stamped approved development plan. (see full review) | | CO Springs DRE | 1050315 |
Zoning/Planning | Original | / | 3/26/2018 | KCARLEO | KCARLEO | In Current Review by KCARLEO | | Zoning/Planning | 1050185 |
City Engr | Original | A | 3/23/2018 | JDAGNILLO | JDAGNILLO | | | City Engr | 1050146 |
Elevators | Original | D | 3/23/2018 | ERIC | ERIC | Page E0.0 Detail note #1 delete shunt trip breaker Page E2.0 Detail note #4 delete shunt trip (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1050079 |
Water Division | Original | A | 3/23/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. ERW | ewidrick | Water Division | 1049978 |
Waste Water Div | Original | A | 3/23/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. ERW | ewidrick | Waste Water Div | 1049976 |
Resubmittal 2 | Original | / | 3/23/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1049959 |
Health Dept. | Original | D | 2/2/2018 | HEALTHDEPT | HEALTHDEPT | Air quality construction activity permit required. Contact 578-3199 option #3 for more information regarding construction activity permits. AP 578-3278 | Aparikh | Health Dept. | 1034512 |
Electrical | Original | A | 2/1/2018 | SHELBY | SHELBY | | | Electrical | 1033819 |
City Engr | Original | D | 1/31/2018 | PMORRIS | PMORRIS | Include a copy of the approved Development Plan and a copy of the Water Resources Engineering Division approved Grading & Erosion Control Plan. | | City Engr | 1033278 |
CSU Contract Admin. | Original | D | 1/31/2018 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted: Requires Commercial Water Meter Sizing Form (https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. MKL | mkluke | CSU Contract Admin. | 1033263 |
CO Springs Fire | Original | A | 1/30/2018 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A (see full review) | csfdit | CO Springs Fire | 1032939 |
Plumbing | Original | A | 1/30/2018 | TCRIPPEN | TCRIPPEN | okay. | | Plumbing | 1032872 |
Electronic Plan | Original | / | 1/30/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1032789 |
Elevators | Original | D | 1/29/2018 | ERIC | ERIC | Elevators are Machineroom-less hydraulic type Please provide and incorporate elevator submittals into plan set Electrical shunt trip protection not allowed per CSFD
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1032625 |
Electronic Plan | Original | / | 1/29/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1032583 |
Gas/Elec. Utils | Original | A | 1/29/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. ERW | ewidrick | Gas/Elec. Utils | 1032533 |
Water Division | Original | D | 1/29/2018 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. ERW | ewidrick | Water Division | 1032527 |
Waste Water Div | Original | D | 1/29/2018 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. ERW | ewidrick | Waste Water Div | 1032526 |
CO Springs DRE | Original | D | 1/29/2018 | MBINGMAN | MBINGMAN | Same comment - upload stamped approved development plan and recorded plat. MRB per KAC (see full review) | | CO Springs DRE | 1032424 |
Construction | Original | A | 1/29/2018 | MICHAELA | MICHAELA | | | Construction | 1032388 |
Enumeration | Original | A | 1/26/2018 | BRENT | BRENT | Final plat has been recorded. | | Enumeration | 1032276 |
Resubmittal 1 | Original | / | 1/24/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1031578 |
Hazmat | Original | N | 12/29/2017 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1024934 |
CO Springs Fire | Original | D | 12/29/2017 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1024933 |
Mechanical | Original | A | 12/20/2017 | JUSTINC | JUSTINC | | | Mechanical | 1023152 |
Electrical | Original | D | 12/18/2017 | SHELBY | SHELBY | 1. label each component of the building service on floor plan ( C/T cabinet, etc). 2. Show all required elevator branch circuits and disconnects on floor plan and panel schedules. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1022085 |
City Engr | Original | D | 12/15/2017 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Water Resources Engineering approved Grading and Erosion Control Plan in the electronic building permit set. jad | | City Engr | 1021767 |
Water Division | Original | D | 12/15/2017 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. RDS | rsolberg | Water Division | 1021678 |
Waste Water Div | Original | D | 12/15/2017 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, approved CSU mainline Construction Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. RDS | rsolberg | Waste Water Div | 1021676 |
Gas/Elec. Utils | Original | D | 12/15/2017 | CSUREVIEW | CSUREVIEW | Show the gas and electric meter locations on the elevation plan views, and contact the gas/electric field engineer, Todd Sturtevant (719)668-3556 to coordinate the gas and electric services. | rsolberg | Gas/Elec. Utils | 1021674 |
Health Dept. | Original | D | 12/14/2017 | HEALTHDEPT | HEALTHDEPT | Air quality construction activity permit required for > 1 acre. Contact (719)578-3199 option #3. AB (719)352-1842 | abrannon | Health Dept. | 1021541 |
Plumbing | Original | D | 12/14/2017 | TCRIPPEN | TCRIPPEN | Provide GPM at each roof drain for sizing (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1021336 |
CSU Contract Admin. | Original | D | 12/14/2017 | CSUAPPSPRM | CSUAPPSPRM | Requires Commercial Water Meter Sizing Form (https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. ZJS | zshearer | CSU Contract Admin. | 1021304 |
Electronic Plan | Original | / | 12/14/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1021302 |
CO Springs DRE | Original | D | 12/14/2017 | MBINGMAN | MBINGMAN | Please upload a copy of the stamped approved development plan and recorded plat. MRB per KAC. (see full review) | | CO Springs DRE | 1021284 |
Zoning/Planning | Original | / | 12/14/2017 | KCARLEO | KCARLEO | In Current Review by KCARLEO | | Zoning/Planning | 1021283 |
Construction | Original | D | 12/13/2017 | MICHAELA | MICHAELA | Revise codes on structural plans Correct stair section on metal building plans Add Pf and Pg for snow loads See plan (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1021273 |
Electronic Plan | Original | / | 12/13/2017 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1021142 |
Enumeration | Original | D | 12/11/2017 | BRENT | BRENT | Final plat has not yet been recorded. Enumerations approval pending receipt in our office of a copy of the final recorded plat. Code study form should show current tax schedule number and legal description. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1020353 |
Floodplain | Original | N | 12/11/2017 | BRENT | BRENT | | | Floodplain | 1020352 |