Mechanical | Splice 03/19/19 | A | 3/19/2019 | DALEH | DALEH | per conversation with Architect Ross Smith it was ok to adjust O.S.A. on RTU schedule to meet code delta 14 | | Mechanical | 1168984 |
Out to Review | Splice 03/19/19 | / | 3/19/2019 | BECKYA | BECKYA | | | Out to Review | 1168950 |
Plumbing | Splice 02/19/19 | A | 2/21/2019 | SHANEN | SHANEN | Delta 11 revision water entry relocated. Delta 13 revisions floor drain installed for water entry and detail for lift station and discharge piping for floor drain. | | Plumbing | 1161129 |
Construction | Splice 02/19/19 | A | 2/20/2019 | SHELLEY | SHELLEY | Revised cover and specs. | | Construction | 1160611 |
Mechanical | Splice 02/19/19 | A | 2/19/2019 | DALEH | DALEH | | | Mechanical | 1160488 |
Electrical | Splice 02/19/19 | A | 2/19/2019 | BERTHA | BERTHA | Revised location of EF-5. Moved EF-5 from MedGas closet to roof. | | Electrical | 1160470 |
Plumbing | Splice 02/19/19 | D | 2/19/2019 | SHANEN | SHANEN | Sewage ejector to discharge to sanitary waste.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1160464 |
Out to Review | Splice 02/19/19 | / | 2/19/2019 | BECKYA | BECKYA | | | Out to Review | 1160436 |
CO Springs DRE | Splice 02/08/19 | A | 2/19/2019 | BECKYA | BECKYA | Per CAS Chris Staley 2/19/19 | | CO Springs DRE | 1160433 |
CO Springs Fire | Splice 02/08/19 | A | 2/11/2019 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1158010 |
Electrical | Splice 02/08/19 | A | 2/8/2019 | BERTHA | BERTHA | Revised panel schedule - removed monument sign. | | Electrical | 1157689 |
Out to Review | Splice 02/08/19 | / | 2/8/2019 | BECKYA | BECKYA | | | Out to Review | 1157665 |
Electrical | Splice 01/22/19 | A | 1/22/2019 | BERTHA | BERTHA | Added series rated combinations. | | Electrical | 1151513 |
Out to Review | Splice 01/22/19 | / | 1/22/2019 | BECKYA | BECKYA | | | Out to Review | 1151489 |
Construction | Splice 01/18/19 | A | 1/18/2019 | BPHILLIPS | BPHILLIPS | Removed beam from scope, provided revised assembly for lid. Revised lid detail in NO2 room. | | Construction | 1151021 |
Out to Review | Splice 01/18/19 | / | 1/18/2019 | BECKYA | BECKYA | | | Out to Review | 1151018 |
Scanned/Finished Bin | Original | / | 6/20/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1081796 |
To Be Scanned Bin | Original | / | 6/19/2018 | | MINDY | Location = To Be Scanned Bin by MINDY | | To Be Scanned Bin | 1081453 |
Mechanical | Original | A | 6/19/2018 | DALEH | DALEH | | | Mechanical | 1081430 |
Out to Review | Original | / | 6/19/2018 | MINDY | MINDY | Perri 217 273 4954 | | Out to Review | 1081369 |
CSU Contract Admin. | Original | A | 6/18/2018 | CSUAPPSPRM | CSUAPPSPRM | Development Charges and Fees paid. ZJS | zshearer | CSU Contract Admin. | 1080799 |
Finished Bin | Original | / | 6/15/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1080311 |
Water Division | Original | A | 6/15/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Water Division | 1080234 |
Waste Water Div | Original | A | 6/15/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Waste Water Div | 1080233 |
CSU Contract Admin. | Original | D | 6/15/2018 | CSUAPPSPRM | CSUAPPSPRM | Requires payment of Development Charges and Fees. ZJS | zshearer | CSU Contract Admin. | 1080031 |
CSU Utilities | Original | / | 6/14/2018 | | CSFIRE | Location = CSU Utilities by CSFIRE | rpeterson | CSU Utilities | 1079771 |
CO Springs Fire | Original | A | 6/14/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas | csfdit | CO Springs Fire | 1079770 |
Fire | Original | / | 6/7/2018 | | SCANNING | Location = Fire by SCANNING | | Fire | 1077059 |
Plan Coordinator | Original | / | 6/6/2018 | | RDCUSER | Location = Plan Coordinator by RDCUSER | | Plan Coordinator | 1077016 |
CO Springs DRE | Original | A | 6/6/2018 | RDCUSER | RDCUSER | Approved. Plans to Plan Coordinator (see full review) | | CO Springs DRE | 1077015 |
Zoning/Planning | Original | / | 5/31/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1074470 |
Plumbing | Original | A | 5/31/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1074419 |
Plumbing | Original | / | 5/30/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1074306 |
Plumbing | Original | / | 5/30/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1074305 |
Fire | Original | / | 5/30/2018 | | SCANNING | Location = Fire by SCANNING | | Fire | 1074120 |
Plan Coordinator | Original | / | 5/30/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1074093 |
Mechanical | Original | D | 5/30/2018 | JUSTINC | JUSTINC | Med gas room exhaust system to be provided with makeup air. Per 09' IMC 502.9.1 both exhaust and makeup air to be separate air streams and both enclosed within 1 hour shaft from room to exterior.
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1074092 |
Mechanical | Original | / | 5/30/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1074002 |
Mechanical | Original | / | 5/29/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1073298 |
Plan Coordinator | Original | / | 5/29/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1073265 |
Plumbing | Original | D | 5/29/2018 | TCRIPPEN | TCRIPPEN | water size analysis was removed it is required to be on plan set? rest okay (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1073264 |
Plumbing | Original | / | 5/29/2018 | | TCRIPPEN | Location = Plumbing by TCRIPPEN | | Plumbing | 1073247 |
Mechanical | Original | / | 5/25/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1072944 |
Plan Coordinator | Original | / | 5/25/2018 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1072905 |
Construction | Original | A | 5/25/2018 | DANM | DANM | | | Construction | 1072903 |
Construction | Original | / | 5/25/2018 | DANM | DANM | In Current Review by DANM | | Construction | 1072659 |
Construction | Original | / | 5/24/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1072574 |
Resubmittal 2 | Original | / | 5/24/2018 | SCANNING | SCANNING | Resubmittal #2 | | Resubmittal 2 | 1072573 |
Out to Review | Original | / | 5/16/2018 | JANE | JANE | Christopher 720 206 6931 | | Out to Review | 1069004 |
Finished Bin | Original | / | 5/8/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1065953 |
CSU Contract Admin. | Original | D | 5/8/2018 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate. AG
CWMSF available online at: https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf | aguerin | CSU Contract Admin. | 1065939 |
CSU Contract Admin. | Original | / | 5/8/2018 | | CSUREVIEW | Location = CSU Contract Admin. by CSUREVIEW | jnoble | CSU Contract Admin. | 1065903 |
Water Division | Original | D | 5/8/2018 | CSUREVIEW | CSUREVIEW | Comments still need to be addressed. Provide a copy of the approved CSU Construction and USP plans in the permit set. JPN | jnoble | Water Division | 1065902 |
Waste Water Div | Original | D | 5/8/2018 | CSUREVIEW | CSUREVIEW | Comments still need to be addressed. Provide a copy of the approved CSU Construction and USP plans in the permit set. JPN | jnoble | Waste Water Div | 1065900 |
Gas/Elec. Utils | Original | A | 5/8/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Gas/Elec. Utils | 1065896 |
City Engr | Original | A | 5/4/2018 | CSENGINEER | CSENGINEER | Plan set routed to CSU Utilities. jad | csengineer | City Engr | 1065224 |
Hazmat | Original | A | 5/4/2018 | CSFIRE | CSFIRE | Plans approved. Pleas read approval comments. Plans forwarded to Utilities. (see full review) | smanning | Hazmat | 1065209 |
Hazmat | Original | / | 5/4/2018 | | CSFIRE | Location = Hazmat by CSFIRE | rpeterson | Hazmat | 1065003 |
CO Springs Fire | Original | D | 5/4/2018 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1064998 |
Fire | Original | / | 4/13/2018 | | SDALSING | Location = Fire by SDALSING | | Fire | 1057416 |
CO Springs DRE | Original | D | 4/13/2018 | SDALSING | SDALSING | Denied: approved drainage report is required. Please submit final landscaping and irrigation plan to Connie Perry, Landscape Architect (these plans must be submitted directly to Connie). (see full review) | | CO Springs DRE | 1057414 |
CSU Contract Admin. | Original | / | 4/10/2018 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 1055787 |
Plumbing | Original | / | 4/9/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1055266 |
Plan Coordinator | Original | / | 4/9/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1055229 |
Mechanical | Original | D | 4/9/2018 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Verify how med gas ventilation system complies with 09' IFC 5306.2.2. No makeup air indicated? No fire sprinkler indicated? Provide duct wrap detail for med ventilation system. Showing wrap requirements.
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1055228 |
Mechanical | Original | / | 4/9/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1055184 |
Mechanical | Original | / | 4/6/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1054731 |
Plan Coordinator | Original | / | 4/5/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1054673 |
Electrical | Original | A | 4/5/2018 | SHELBY | SHELBY | | | Electrical | 1054672 |
Electrical | Original | / | 4/4/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1053717 |
Plan Coordinator | Original | / | 4/4/2018 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1053673 |
Construction | Original | D | 4/4/2018 | DANM | DANM | Stamp and sign Page 3 of Code Study Form Provide stamp and seal on COMcheck clarification letter or include on Sheet A203 Exterior wall insulation values on COMcheck report still do not seem to match drawings - sections and details show R-19 batt insulation vs. R-13 cavity insulation on report Provide Soils Report referenced on Sheet S000 as part of this submittal Walk-through review OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1053672 |
Construction | Original | / | 4/4/2018 | DANM | DANM | In Current Review by DANM | | Construction | 1053601 |
Construction | Original | / | 3/29/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1052105 |
Plan Coordinator | Original | / | 3/29/2018 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1052073 |
Enumeration | Original | A | 3/29/2018 | BRENT | BRENT | Tax schedule number and legal to change. | | Enumeration | 1052072 |
Enumeration | Original | / | 3/29/2018 | | NELIDA | Location = Enumeration by NELIDA | | Enumeration | 1051698 |
Resubmittal 1 | Original | / | 3/29/2018 | NELIDA | NELIDA | Resubmittal #1 3/29/18 | | Resubmittal 1 | 1051697 |
Out to Review | Original | / | 2/2/2018 | GITA | GITA | 7202066931 Christopher | | Out to Review | 1034186 |
Finished Bin | Original | / | 1/31/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1033366 |
Health Dept. | Original | N | 1/31/2018 | HEALTHDEPT | HEALTHDEPT | Plan review is not needed - Not applicable. GA 578-3295 | galvarez | Health Dept. | 1033317 |
Health Dept. | Original | / | 1/25/2018 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1031964 |
City Engr | Original | D | 1/25/2018 | CSENGINEER | CSENGINEER | Include a copy of the approved Development Plan in the building permit set. Plan set route to RBD. pvm | csengineer | City Engr | 1031893 |
Water Division | Original | D | 1/25/2018 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with any questions. | ajuvera | Water Division | 1031734 |
Waste Water Div | Original | D | 1/25/2018 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with any questions. | ajuvera | Waste Water Div | 1031733 |
Gas/Elec. Utils | Original | D | 1/25/2018 | CSUREVIEW | CSUREVIEW | Provide approved Development Plan in the RBD plan set. Show proposed gas and electric meter location on building elevation plans. | ajuvera | Gas/Elec. Utils | 1031732 |
CO Springs Fire | Original | D | 1/23/2018 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A
Plans routed back to CSFD prior to corrections. All previous disapproval comments apply. JAH (see full review) | csfdit | CO Springs Fire | 1030743 |
City Engr | Original | / | 1/19/2018 | | SCANNING | Location = City Engr by SCANNING | | City Engr | 1030116 |
Water Division | Original | D | 1/19/2018 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg | mgackle | Water Division | 1030046 |
Waste Water Div | Original | D | 1/19/2018 | CSUREVIEW | CSUREVIEW | Requires approved Development Plan, and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. mjg | mgackle | Waste Water Div | 1030044 |
Gas/Elec. Utils | Original | D | 1/19/2018 | CSUREVIEW | CSUREVIEW | Show the gas and electric meter locations on the elevation plan views to make sure gas regulator vent is at least 3ft away from any electric meter socket and openings like windows, doors, and garage doors. mjg | mgackle | Gas/Elec. Utils | 1030042 |
Hazmat | Original | D | 1/18/2018 | CSFIRE | CSFIRE | Plans disapproved. Please read disapproval comments. Plans forwarded to utilities (see full review) | smanning | Hazmat | 1029858 |
Hazmat | Original | / | 1/16/2018 | | CSFIRE | Location = Hazmat by CSFIRE | wtaylor | Hazmat | 1028857 |
CO Springs Fire | Original | D | 1/16/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1028855 |
Fire | Original | / | 1/11/2018 | | SDALSING | Location = Fire by SDALSING | | Fire | 1028067 |
CO Springs DRE | Original | D | 1/11/2018 | SDALSING | SDALSING | No approved DP yet. SRD per CAS (see full review) | | CO Springs DRE | 1028066 |
Zoning/Planning | Original | / | 1/10/2018 | | CSUAPPSPRM | Location = Zoning/Planning by CSUAPPSPRM | mkluke | Zoning/Planning | 1027635 |
CSU Contract Admin. | Original | D | 1/10/2018 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees.
Please contact Utilities Development Services at 719-668-8111 or cca@csu.org for questions, assistance or to request an estimate. MKL
CWMSF available online at: https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf | mkluke | CSU Contract Admin. | 1027633 |
CSU Contract Admin. | Original | / | 1/9/2018 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 1027201 |
Plan Coordinator | Original | / | 1/9/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1027138 |
Mechanical | Original | D | 1/9/2018 | JUSTINC | JUSTINC | Provide refrigeration calculation for minisplit system. Indicate if within allowable limits per 09' IMC 1103.1. If over allowable limits indicate on plan how protecting. Relocate all gas associated work to (M) sheets for review Add note: - Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection. Clarify how providing makeup air to E.F located in laundry. Clarify how providing makeup air to clothes dryer? Provide additional clarifications on how complying with 09' IMC 502.9.1 and 09' IFC 5306 - 5306.4 for MED GAS STORAGE Provide section view detail of ventilation system in MED GAS closet
MECHANICAL REVIEW INCOMPLETE NO WALK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1027137 |
Mechanical | Original | / | 1/9/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1027096 |
Mechanical | Original | / | 1/9/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1027080 |
Plan Coordinator | Original | / | 1/8/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1026927 |
Electrical | Original | D | 1/8/2018 | SHELBY | SHELBY | Show available fault current at all panels. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1026926 |
Electrical | Original | / | 1/8/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1026721 |
Plumbing | Original | D | 12/28/2017 | TCRIPPEN | TCRIPPEN | P102 see red lines missing sizes need clarification on notes see red lines where is water entry room and water meter? trap primers clarify gas piping to be on M pages per our web site. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1024563 |
Electrical | Original | / | 12/28/2017 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electrical | 1024448 |
Electrical | Original | / | 12/27/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1024265 |
Plan Coordinator | Original | / | 12/27/2017 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1024250 |
Construction | Original | D | 12/27/2017 | DANM | DANM | Provide architectural site plan showing distances to all property lines A006 - UL listings are not legible Interior restroom elevations do not show requirements of IBC 1210 Surrounding Materials are being met Note Medical Gas room fire rating for other than IBC Exterior wall insulation values on COMcheck do not seem to match building sections - clarify Provide engineering for metal awnings including framing plan and all sizes/connections or indicate if deferred submittal Provide Soils Report referenced on Sheet S000 as part of submittal No walk-through review allowed
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1024249 |
Construction | Original | / | 12/27/2017 | DANM | DANM | In Current Review by DANM | | Construction | 1024113 |
Construction | Original | / | 12/22/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 1023719 |
Plan Coordinator | Original | / | 12/22/2017 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1023712 |
Enumeration | Original | D | 12/22/2017 | BRENT | BRENT | include a site plan showing access to the parcel, location of building and trash enclosure on parcel with road names labeled. Code study form is missing legal description. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1023711 |
Enumeration | Original | / | 12/21/2017 | | NELIDA | Location = Enumeration by NELIDA | | Enumeration | 1023438 |
Finished Bin | Original | / | 12/15/2017 | NELIDA | NELIDA | Plan placed in Finished Bin until estimated job valuation and plan review fee are received. Project Coordinator will be notified. | | Finished Bin | 1021785 |
Floodplain | Original | N | 12/15/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5317100038) | | Floodplain | 1021784 |