Scanned/Finished Bin | Original | / | 4/18/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1058755 |
To Be Scanned Bin | Original | / | 4/18/2018 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 1058656 |
Mechanical | Original | A | 4/18/2018 | JUSTINC | JUSTINC | | | Mechanical | 1058647 |
Out to Review | Original | / | 4/18/2018 | RITA | RITA | Sarah 303-256-4015 | | Out to Review | 1058582 |
Finished Bin | Original | / | 4/18/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1058535 |
Hazmat | Original | A | 4/17/2018 | CSFIRE | CSFIRE | Plans approved. Please read approval comments. Plans forwarded to RBD. (see full review) | smanning | Hazmat | 1058446 |
CO Springs Fire | Original | N | 4/11/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1056535 |
Electrical | Original | A | 4/11/2018 | SHELBY | SHELBY | | | Electrical | 1056468 |
Construction | Original | N | 4/11/2018 | SHELLEY | SHELLEY | No construction work - penetration of mechanical system using damper. | | Construction | 1056452 |
Out to Review | Original | / | 2/13/2018 | MINDY | MINDY | To Kathy Farina via Fed Ex 847-942-6786 | | Out to Review | 1037141 |
Finished Bin | Original | / | 1/17/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1029373 |
Hazmat | Original | D | 1/17/2018 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1029369 |
Hazmat | Original | / | 1/17/2018 | | SCANNING | Location = Hazmat by SCANNING | | Hazmat | 1029222 |
CO Springs Fire | Original | D | 1/16/2018 | CSFIRE | CSFIRE | reference review report within plans for comments (see full review) | csfdit | CO Springs Fire | 1028626 |
Fire | Original | / | 1/9/2018 | | KHYLLESTED | Location = Fire by KHYLLESTED | | Fire | 1027376 |
CO Springs DRE | Original | A | 1/9/2018 | KHYLLESTED | KHYLLESTED | Meets all requirements per file number AR CM3 17-00589. (see full review) | | CO Springs DRE | 1027375 |
Zoning/Planning | Original | / | 1/8/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1026779 |
Plan Coordinator | Original | / | 1/8/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1026648 |
Electrical | Original | D | 1/8/2018 | SHELBY | SHELBY | 1. Provide complete one line see https://www.pprbd.org/plancheck/PLCK%20Com%20Elec%20List%202016.pdf (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1026647 |
Electrical | Original | / | 1/8/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1026631 |
Mechanical | Original | D | 12/29/2017 | TCRIPPEN | TCRIPPEN | address constructions notes on M-1 first (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1025005 |
Plumbing | Original | N | 12/29/2017 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit | | Plumbing | 1024997 |
Electrical | Original | / | 12/29/2017 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1024931 |
Plan Coordinator | Original | / | 12/29/2017 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1024919 |
Construction | Original | D | 12/29/2017 | SHELLEY | SHELLEY | Need clarification on exhaust through roof - unrated chase is 3 stories max, is this a rated shaft? Existing opening into shaft? How is shaft penetration being protected? Walk ok. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1024917 |
Construction | Original | / | 12/29/2017 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1024895 |
Construction | Original | / | 12/29/2017 | | SCANNING | Location = Construction by SCANNING | | Construction | 1024821 |
Plan Coordinator | Original | / | 12/29/2017 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1024788 |
Enumeration | Original | A | 12/29/2017 | AMY | AMY | ORIGINAL PERMIT HISTORY WITH CINGULAR PERMIT C24314 | | Enumeration | 1024786 |
Enumeration | Original | / | 12/29/2017 | AMY | AMY | In Current Review by AMY | | Enumeration | 1024782 |
Floodplain | Original | N | 12/22/2017 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418218011) | | Floodplain | 1023624 |