Out to Review | Splice 10/01/18 | / | 2/13/2019 | GITA | GITA | bobby | | Out to Review | 1158695 |
Scanned/Finished Bin | Splice 10/01/18 | / | 2/12/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1158238 |
To Be Scanned Bin | Splice 10/01/18 | / | 2/12/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1158237 |
Plan Coordinator | Splice 10/01/18 | / | 2/12/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1158221 |
Construction | Splice 10/01/18 | A | 2/12/2019 | MICHAELA | MICHAELA | Trusses | | Construction | 1158220 |
Construction | Splice 10/01/18 | / | 2/8/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1157716 |
Construction | Splice 10/01/18 | / | 2/8/2019 | JANE | JANE | Overtime approved for Construction by Bobby | | Construction | 1157609 |
Construction | Splice 10/01/18 | / | 2/8/2019 | | JANE | Location = Construction by JANE | | Construction | 1157602 |
Resubmittal 3 | Splice 10/01/18 | / | 2/8/2019 | JANE | JANE | Resubmittal #3 | | Resubmittal 3 | 1157601 |
Finished Bin | Splice 10/01/18 | / | 12/11/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1140399 |
Plan Coordinator | Splice 10/01/18 | / | 12/11/2018 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1140357 |
Construction | Splice 10/01/18 | D | 12/11/2018 | SHELLEY | SHELLEY | Same comment as previous review - address all questions and resubmit. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1140356 |
Construction | Splice 10/01/18 | / | 12/11/2018 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1140321 |
Construction | Splice 10/01/18 | / | 12/11/2018 | | JANE | Location = Construction by JANE | | Construction | 1140256 |
Resubmittal 2 | Splice 10/01/18 | / | 12/11/2018 | JANE | JANE | Resubmittal #2 | | Resubmittal 2 | 1140254 |
Construction | Splice 10/01/18 | D | 12/4/2018 | JANE | JANE | See previous comments - they were trying to resubmitthe same trusses. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1137651 |
Resubmittal 1 | Splice 10/01/18 | / | 12/4/2018 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 1137648 |
Finished Bin | Splice 10/01/18 | / | 10/1/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1115181 |
Plan Coordinator | Splice 10/01/18 | / | 10/1/2018 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1115154 |
Construction | Splice 10/01/18 | D | 10/1/2018 | SHELLEY | SHELLEY | PE shop stamp required on layout also; who is addressing question presented - resubmit once questions resolved; incorrect code cycle used - 2009 IBC required. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1115153 |
Construction | Splice 10/01/18 | / | 10/1/2018 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1115148 |
Construction | Splice 10/01/18 | / | 10/1/2018 | | RITA | Location = Construction by RITA | | Construction | 1115116 |
Out to Review | Original | / | 8/10/2018 | GITA | GITA | Matt (316) 681-3500 | | Out to Review | 1099093 |
Health Dept. | Original | A | 7/16/2018 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | Jzimmerman | Health Dept. | 1089839 |
Scanned/Finished Bin | Original | / | 7/16/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1089680 |
To Be Scanned Bin | Original | / | 7/13/2018 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 1089459 |
Fountain Zoning | Original | A | 7/13/2018 | RITA | RITA | per Gabby 07/13/18 | | Fountain Zoning | 1089458 |
Fountain Waste Water | Original | A | 7/13/2018 | RITA | RITA | per Stratmoor water 0712/18 | | Fountain Waste Water | 1089451 |
Fountain Water | Original | A | 7/13/2018 | RITA | RITA | per stratmoor waste water 07/12/18 | | Fountain Water | 1089450 |
Hazmat | Original | A | 7/13/2018 | RITA | RITA | per Fire Chief Michael Orr 07/13/18 | | Hazmat | 1089442 |
Fountain Fire | Original | A | 7/13/2018 | RITA | RITA | per michael Orr 06/27/18 | | Fountain Fire | 1089437 |
Out to Review | Original | / | 7/12/2018 | RITA | RITA | Kyle 316-209-5296 | | Out to Review | 1088968 |
Finished Bin | Original | / | 7/2/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1085751 |
Plan Coordinator | Original | / | 7/2/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1085747 |
Construction | Original | A | 7/2/2018 | MICHAELA | MICHAELA | | | Construction | 1085743 |
Construction | Original | / | 7/2/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1085728 |
Construction | Original | / | 7/2/2018 | | JANE | Location = Construction by JANE | | Construction | 1085713 |
Resubmittal 6 | Original | / | 7/2/2018 | JANE | JANE | Resubmittal #6 | | Resubmittal 6 | 1085712 |
Construction | Original | D | 6/20/2018 | MICHAELA | MICHAELA | Per Fountain fire. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1082181 |
Out to Review | Original | / | 6/18/2018 | LBENNETT | LBENNETT | | | Out to Review | 1080904 |
Construction | Original | A | 6/18/2018 | LBENNETT | LBENNETT | | | Construction | 1080900 |
Finished Bin | Original | / | 6/12/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1078597 |
Plan Coordinator | Original | / | 6/12/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1078590 |
Plumbing | Original | A | 6/12/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1078588 |
Plumbing | Original | / | 6/12/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1078549 |
Plumbing | Original | / | 6/11/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1078167 |
Plan Coordinator | Original | / | 6/11/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1078116 |
Electrical | Original | A | 6/11/2018 | BERTHA | BERTHA | | | Electrical | 1078114 |
Electrical | Original | / | 6/7/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1077135 |
Electrical | Original | / | 6/4/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1075964 |
Plan Coordinator | Original | / | 6/4/2018 | | SCANNING | Location = Plan Coordinator by SCANNING | | Plan Coordinator | 1075937 |
Construction | Original | D | 6/4/2018 | MICHAELA | MICHAELA | Pages C-1 and A1.1 are not stamped Walk OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1075933 |
Construction | Original | / | 6/4/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1075920 |
Construction | Original | / | 6/4/2018 | | RITA | Location = Construction by RITA | | Construction | 1075904 |
Resubmittal 5 | Original | / | 6/4/2018 | RITA | RITA | Resubmittal #5 | | Resubmittal 5 | 1075903 |
Finished Bin | Original | / | 5/18/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1070128 |
Plan Coordinator | Original | / | 5/18/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1070105 |
Construction | Original | D | 5/18/2018 | MICHAELA | MICHAELA | Reassemble the plan set per the drawing index with all corrected pages replaced Leave all the red lined, marked up pages loose on the top of the re-assembled plan set We will not do this for you. Soils report is missing - make sure all pages are included (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1070104 |
Construction | Original | / | 5/16/2018 | | MINDY | Location = Construction by MINDY | | Construction | 1069330 |
Resubmittal 4 | Original | / | 5/16/2018 | MINDY | MINDY | Resubmittal #4 | | Resubmittal 4 | 1069329 |
Out to Review | Original | / | 5/16/2018 | MATTHEWM | MATTHEWM | Pending resubmittal | | Out to Review | 1069315 |
Finished Bin | Original | / | 5/7/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1065348 |
Plan Coordinator | Original | / | 5/7/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1065344 |
Plumbing | Original | D | 5/7/2018 | TCRIPPEN | TCRIPPEN | Per comments on 4- 16- 18 We still an water pipe size analysis data on plans you can email a stamped copy and I can add it to the plan set, tcrippen@pprbd.org (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1065343 |
Plumbing | Original | / | 5/4/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1065192 |
Plumbing | Original | / | 5/3/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1064610 |
Plan Coordinator | Original | / | 5/3/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1064589 |
Electrical | Original | D | 5/3/2018 | SHELBY | SHELBY | 1. Provide panel C schedule ( This panel schedule must appear on the electrical drawing, with available fault current and withstand rating clearly indicated). See https://www.pprbd.org/Downloads/CommercialHandout/Com%20Elect%20reqs.pdf for complete requirements.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1064588 |
Electrical | Original | / | 5/3/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1064366 |
Electrical | Original | / | 5/2/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1063850 |
Plan Coordinator | Original | / | 5/2/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1063814 |
Construction | Original | D | 5/2/2018 | MICHAELA | MICHAELA | Assemble the plan per the Drawing Index - include all the pages Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1063813 |
Construction | Original | / | 5/1/2018 | | MATTHEWM | Location = Construction by MATTHEWM | | Construction | 1063727 |
Resubmittal 3 | Original | / | 5/1/2018 | MATTHEWM | MATTHEWM | Resubmittal #3 | | Resubmittal 3 | 1063726 |
Out to Review | Original | / | 4/30/2018 | NELIDA | NELIDA | Kyle 316-209-5296 | | Out to Review | 1063019 |
Finished Bin | Original | / | 4/16/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1057684 |
Plan Coordinator | Original | / | 4/16/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1057655 |
Plumbing | Original | D | 4/16/2018 | TCRIPPEN | TCRIPPEN | still missing pipe material schedule for drain waste and vents. need an water pipe size analysis data on plans . (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1057654 |
Plumbing | Original | / | 4/16/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1057646 |
Plumbing | Original | / | 4/16/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1057544 |
Mechanical | Original | A | 4/13/2018 | JUSTINC | JUSTINC | | | Mechanical | 1057516 |
Plan Coordinator | Original | / | 4/13/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1057513 |
Electrical | Original | D | 4/13/2018 | JUSTINC | JUSTINC | Please address previous review comments 1, 2, and 3. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1057511 |
Mechanical | Original | / | 4/13/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1057480 |
Mechanical | Original | / | 4/13/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1057355 |
Plan Coordinator | Original | / | 4/13/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1057354 |
Construction | Original | D | 4/13/2018 | MICHAELA | MICHAELA | Reassemble the plan with the soils report and structural pages included Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1057349 |
Construction | Original | / | 4/13/2018 | | GITA | Location = Construction by GITA | | Construction | 1057257 |
Resubmittal 2 | Original | / | 4/13/2018 | GITA | GITA | Resubmittal #2 | | Resubmittal 2 | 1057256 |
Out to Review | Original | / | 3/30/2018 | NELIDA | NELIDA | Kyle 316-209-5296 | | Out to Review | 1052537 |
Finished Bin | Original | / | 3/19/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1048546 |
Plan Coordinator | Original | / | 3/19/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1048539 |
Plumbing | Original | D | 3/19/2018 | TCRIPPEN | TCRIPPEN | provide scuppers and sizes plus GPM for each scupper on P -pages, need DWV material called out on plans still need an approved occupant load for fixture count. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1048537 |
Plumbing | Original | / | 3/19/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1048349 |
Plumbing | Original | / | 3/16/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1048141 |
Plan Coordinator | Original | / | 3/16/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1047949 |
Mechanical | Original | D | 3/16/2018 | DALEH | DALEH | darken up backgrounds respond to walls needing to be of non combustible material on drawings walk ok (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1047948 |
Mechanical | Original | / | 3/16/2018 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1047922 |
Mechanical | Original | / | 3/16/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1047850 |
Plan Coordinator | Original | / | 3/16/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1047802 |
Electrical | Original | A | 3/16/2018 | SHELBY | SHELBY | Please address previous review comments 1, 2, and 3. | | Electrical | 1047801 |
Electrical | Original | / | 3/15/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1047395 |
Electrical | Original | / | 3/14/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1046673 |
Plan Coordinator | Original | / | 3/14/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1046627 |
Construction | Original | D | 3/14/2018 | MICHAELA | MICHAELA | Kitchen occupant load must be part of total Occupant load will exceed 100 and a sprinkler system will be required Panic hardware must be indicated on plan Walk-through Ok (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1046625 |
Construction | Original | / | 3/14/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1046602 |
Construction | Original | / | 3/13/2018 | | JANE | Location = Construction by JANE | | Construction | 1046165 |
Resubmittal 1 | Original | / | 3/13/2018 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 1046164 |
Out to Review | Original | / | 2/20/2018 | GITA | GITA | 7193215004 Jesse | | Out to Review | 1039185 |
Finished Bin | Original | / | 1/12/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1028502 |
Plan Coordinator | Original | / | 1/12/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1028238 |
Mechanical | Original | D | 1/12/2018 | DALEH | DALEH | darken up backgrounds provide freezer/cooler calcs co2 tanks? see note about VB construction and hoods see plans for complete red lines no walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1028237 |
Mechanical | Original | / | 1/11/2018 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1027914 |
Mechanical | Original | / | 1/11/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1027779 |
Plan Coordinator | Original | / | 1/10/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1027771 |
Electrical | Original | D | 1/10/2018 | SHELBY | SHELBY | 1. Provide panel C schedule. 2. Show available fault current on one line. 3.Provide IECC calculation for electrical ( 2009). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1027770 |
Electrical | Original | / | 1/10/2018 | | TCRIPPEN | Location = Electrical by TCRIPPEN | | Electrical | 1027483 |
Plumbing | Original | D | 1/10/2018 | TCRIPPEN | TCRIPPEN | P 1- see section 802.1.1 separate drains required from each bowl , need an approved occupant load for fixture count, P 2 - all gas piping and related items to be on the M pages per our web site. ///// no walk through must be resubmitted \\\\\ (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1027482 |
Plumbing | Original | / | 1/10/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1027429 |
Plumbing | Original | / | 1/10/2018 | | TCRIPPEN | Location = Plumbing by TCRIPPEN | | Plumbing | 1027428 |
Electrical | Original | / | 1/9/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1027017 |
Plan Coordinator | Original | / | 1/9/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1026968 |
Construction | Original | D | 1/9/2018 | MICHAELA | MICHAELA | As designed the occupant load for this structure will exceed 100 - a sprinkler system will be required Revise door hardware to include panic devices at all egress doors Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1026967 |
Construction | Original | / | 1/8/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1026764 |
Construction | Original | / | 1/5/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1026335 |
Plan Coordinator | Original | / | 1/5/2018 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1026309 |
Enumeration | Original | A | 1/5/2018 | BRENT | BRENT | | | Enumeration | 1026308 |
Floodplain | Original | N | 1/3/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6504412016) | | Floodplain | 1025554 |