Plumbing | Splice 10/10/19 Trusses And Plumbing | A | 10/10/2019 | SHANEN | SHANEN | Delta 3 revisions added 1" irrigation line P1.01 adjusted water entry detail, P1.02 adjusted plumbing plan | | Plumbing | 1244653 |
Construction | Splice 10/10/19 Trusses And Plumbing | A | 10/10/2019 | MICHAELA | MICHAELA | Trusses | | Construction | 1244557 |
Construction | Splice 08/22/19 | A | 10/9/2019 | MICHAELA | MICHAELA | | | Construction | 1243936 |
Electronic Plan | Splice 08/22/19 | / | 10/9/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1243935 |
Resubmittal 3 | Splice 08/22/19 | / | 10/8/2019 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1243567 |
Construction | Splice 08/22/19 | D | 10/7/2019 | MICHAELA | MICHAELA | Missing architectural page from last submittal. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1243177 |
Resubmittal 2 | Splice 08/22/19 | / | 10/7/2019 | SHELLEY | SHELLEY | Resubmittal #2 | | Resubmittal 2 | 1242989 |
CO Springs Fire | Splice 08/22/19 | A | 10/2/2019 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L ,Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1241863 |
Electrical | Splice 08/22/19 | A | 9/20/2019 | BERTHA | BERTHA | Revised plans to indicate service change - from 1200A to 800A | | Electrical | 1237789 |
Electronic Plan | Splice 08/22/19 | / | 9/20/2019 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1237732 |
Mechanical | Splice 08/22/19 | A | 9/19/2019 | DALEH | DALEH | approved as noted | | Mechanical | 1237117 |
Construction | Splice 08/22/19 | D | 9/19/2019 | MICHAELA | MICHAELA | Provide a roof framing plan locating the RTUs (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1237098 |
Electronic Plan | Splice 08/22/19 | / | 9/19/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1237090 |
Resubmittal 1 | Splice 08/22/19 | / | 9/19/2019 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1236993 |
CO Springs Fire | Splice 08/22/19 | D | 9/5/2019 | CSFIRE | CSFIRE | See CSFD Disapproval Comments at: http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp | wtaylor | CO Springs Fire | 1231659 |
CO Springs Fire | Splice 08/22/19 | A | 9/5/2019 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1231646 |
Electrical | Splice 08/22/19 | D | 8/23/2019 | BERTHA | BERTHA | Provide a complete splice set for electrical with all revisions clouded.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1227676 |
Construction | Splice 08/22/19 | D | 8/22/2019 | MICHAELA | MICHAELA | Provide architectural plans for the re-location of the mechanical room and structural plans that show the new location of the RTUs (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1227164 |
Mechanical | Splice 08/22/19 | D | 8/22/2019 | DALEH | DALEH | appears backgrounds are not matching with all departments ...Fire sprinkler room access revise structural sheets for changes in RTU sizes and locations (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1227052 |
Plumbing | Splice 01/30/19 | A | 1/30/2019 | SHANEN | SHANEN | Delta 2 revisions : Domestic water entry relocated, grease interceptor relocated, relocated grease and waste line, added underground drains for future fixtures, relocated roof and overflow drains. | | Plumbing | 1154195 |
Out to Review | Splice 01/30/19 | / | 1/30/2019 | BECKYA | BECKYA | | | Out to Review | 1154163 |
CSU Contract Admin. | Original | A | 11/15/2018 | CSUAPPSPRM | CSUAPPSPRM | Development charges/fees paid. LMP | lmpope | CSU Contract Admin. | 1131068 |
CSU Contract Admin. | Original | / | 11/15/2018 | CSUAPPSPRM | CSUAPPSPRM | | lmpope | CSU Contract Admin. | 1131062 |
Electrical | Original | A | 10/22/2018 | SHELBY | SHELBY | | | Electrical | 1122206 |
CSU Contract Admin. | Original | D | 10/19/2018 | CSUAPPSPRM | CSUAPPSPRM | Same comment as 10/16/18. AG | aguerin | CSU Contract Admin. | 1121805 |
Resubmittal 3 | Original | / | 10/17/2018 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1120716 |
CSU Contract Admin. | Original | D | 10/16/2018 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved for 1.5" meter. Applicable development fees/charges due. Call our office at 719-668-8111 for additional information. AG | aguerin | CSU Contract Admin. | 1120502 |
CO Springs Fire | Original | A | 10/9/2018 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 1118288 |
Electrical | Original | D | 10/9/2018 | SHELBY | SHELBY | Please address previous review comment 1. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1118241 |
Water Division | Original | A | 10/8/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Water Division | 1117743 |
Waste Water Div | Original | A | 10/8/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. JPN | jnoble | Waste Water Div | 1117742 |
Gas/Elec. Utils | Original | A | 10/8/2018 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final meter/service/transformer locations. Please submit the Electric Load Data Form, the Application for Gas & Electric Line Extension, and the Application for Gas Service Line Approval. The forms can be found at: https://www.csu.org/Pages/development-files-forms.aspx Contact Kennedy Knutson at 719-668-5572 with any gas/electric questions. JPN | jnoble | Gas/Elec. Utils | 1117740 |
CSU Contract Admin. | Original | D | 10/8/2018 | CSUAPPSPRM | CSUAPPSPRM | Same comment as 09/11/18. LMP | lmpope | CSU Contract Admin. | 1117326 |
City Engr | Original | A | 10/8/2018 | JDAGNILLO | JDAGNILLO | | | City Engr | 1117285 |
Construction | Original | A | 10/5/2018 | MICHAELA | MICHAELA | | | Construction | 1117018 |
Enumeration | Original | A | 10/5/2018 | BRENT | BRENT | Address change has been performed. Not yet updated in Assessor | | Enumeration | 1116892 |
Electronic Plan | Original | / | 10/5/2018 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1116888 |
Resubmittal 2 | Original | / | 10/2/2018 | SHELLEY | SHELLEY | Resubmittal #2 | | Resubmittal 2 | 1115843 |
CO Springs Fire | Original | D | 9/12/2018 | CSFIRE | CSFIRE | previous comments not addressed: include signed/approved water/utility plans with submittal; need enumerations approval prior to CSFD approval (see full review) | csfdit | CO Springs Fire | 1109372 |
CSU Contract Admin. | Original | D | 9/11/2018 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. BML
CWMSF available online at: https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf | bmludiker | CSU Contract Admin. | 1108492 |
Water Division | Original | D | 9/10/2018 | CSUREVIEW | CSUREVIEW | Need approved water and wastewater utility plans submitted in the RBD plan set AJ 9/10/18 | ajuvera | Water Division | 1108279 |
Waste Water Div | Original | D | 9/10/2018 | CSUREVIEW | CSUREVIEW | Need approved water and wastewater utility plans submitted in the RBD plan set AJ 9/10/18 | ajuvera | Waste Water Div | 1108278 |
Gas/Elec. Utils | Original | D | 9/10/2018 | CSUREVIEW | CSUREVIEW | Need to show the gas and electric meter locations on the building elevations on the development plan. The gas meter needs to be 3' DIA away from any door or window opening AJ 9/10/18 | ajuvera | Gas/Elec. Utils | 1108274 |
City Engr | Original | D | 9/10/2018 | JDAGNILLO | JDAGNILLO | Include a copy of the Water Resources Engineering Division approved Grading & Erosion Control Plan. jad | | City Engr | 1107986 |
Electrical | Original | D | 9/10/2018 | SHELBY | SHELBY | 1. Please show method of 240.87 NEC compliance. 2. Specify fully rated or series rated. If series rated provide manufacturers listing of series rated components. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1107908 |
Construction | Original | A | 9/7/2018 | MICHAELA | MICHAELA | | | Construction | 1107655 |
Electronic Plan | Original | / | 9/7/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1107645 |
Enumeration | Original | D | 9/7/2018 | BRENT | BRENT | The tax schedule number, address and legal description shown on both the code study form and page A0 are incorrect. The address shown on the end tabs of the architectural and structural plan pages is incorrect. Show secondary addressing for the maximum number of tenant spaces the buidling will hold on page A1.0. The secondary addressing shown on page P1.02 does not conform to RBD guidelines.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1107425 |
Electronic Plan | Original | / | 9/7/2018 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1107416 |
Resubmittal 1 | Original | / | 8/29/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1104773 |
Canceled Plans | Original | / | 7/10/2018 | ADMIN | ADMIN | Electronic Plan automatically cancelled due to inactivity. | | Canceled Plans | 1087630 |
CO Springs DRE | Original | A | 1/23/2018 | DSEXTON | DSEXTON | Approved. DJS 1/23/2018 (see full review) | | CO Springs DRE | 1030894 |
Zoning/Planning | Original | / | 1/19/2018 | DSEXTON | DSEXTON | In Current Review by DSEXTON | | Zoning/Planning | 1029998 |
Electrical | Original | D | 1/18/2018 | SHELBY | SHELBY | 1. Specify/show C/T compartment dimensions. Comply CSU specifications. 2. Show method of 240.87 NEC compliance. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1029941 |
Mechanical | Original | A | 1/18/2018 | DALEH | DALEH | | | Mechanical | 1029854 |
Electronic Plan | Original | / | 1/18/2018 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1029850 |
Hazmat | Original | N | 1/18/2018 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1029823 |
CO Springs Fire | Original | D | 1/18/2018 | CSFIRE | CSFIRE | REFERENCE REVIEW REPORT ONLINE FOR COMMENTS (see full review) | csfdit | CO Springs Fire | 1029822 |
City Engr | Original | D | 1/18/2018 | JDAGNILLO | JDAGNILLO | Include a copy of the Water Resources Engineering approved Grading and Erosion Control Plan in the electronic building permit set. jad | | City Engr | 1029787 |
Health Dept. | Original | N | 1/18/2018 | HEALTHDEPT | HEALTHDEPT | Not applicable. Shell and core only. AB (719)352-1842 | abrannon | Health Dept. | 1029580 |
Gas/Elec. Utils | Original | D | 1/18/2018 | CSUREVIEW | CSUREVIEW | Show the gas and electric meter locations on the elevation plan views to make sure gas regulator vent is at least 3ft away from any electric meter socket and openings like windows, doors, and garage doors. Contact the CSU Field Engineer, Ben Schmitt (719-668-4462) to coordinate the gas and electric services. ERW | ewidrick | Gas/Elec. Utils | 1029569 |
Water Division | Original | D | 1/18/2018 | CSUREVIEW | CSUREVIEW | Requires approved CSU mainline Construction Plan and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. ERW | ewidrick | Water Division | 1029567 |
Waste Water Div | Original | D | 1/18/2018 | CSUREVIEW | CSUREVIEW | Requires approved CSU mainline Construction Plan and approved Utility Service Plan. Contact Utilities Development Services at 668-8111 with questions. ERW | ewidrick | Waste Water Div | 1029566 |
CSU Contract Admin. | Original | D | 1/18/2018 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
CWMSF available online at: https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
MKL | mkluke | CSU Contract Admin. | 1029502 |
Plumbing | Original | A | 1/18/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1029485 |
Electronic Plan | Original | / | 1/18/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1029476 |
Construction | Original | D | 1/17/2018 | MICHAELA | MICHAELA | Code study and plan have different types of construction - clarify Attic space at front requires access Wrong soils report submitted
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1029411 |
Electronic Plan | Original | / | 1/17/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1029272 |
Enumeration | Original | D | 1/11/2018 | BRENT | BRENT | The tax schedule number and legal description on the code study form and page A0 is incorrect. The address shown on the end tabs of the architectural and structural pages is incorrect. Secondary addressing shown on pages A1.0 and P1.02 does not follow our secondary addressing guidelines. Secondary addressing guidelines are available on our webstie www.pprbd.org->addressing->secondary addressing guide. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1028126 |
Floodplain | Original | N | 1/10/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6204404106) | | Floodplain | 1027409 |