Hazmat | Original | A | 6/5/2018 | CSFIRE | CSFIRE | Hazmat approved. Please read approval comments. CO2 system requires separate permit prior to installation. Fee covers plan review time. (see full review) | smanning | Hazmat | 1076485 |
Plumbing | Original | A | 6/5/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1076385 |
Mechanical | Original | A | 6/1/2018 | JUSTINC | JUSTINC | | | Mechanical | 1075573 |
Plumbing | Original | D | 5/31/2018 | TCRIPPEN | TCRIPPEN | schedule reads 1.5 ? for toilets plan reads 1" ? all so provide an water pipe size analysis date on plans (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1074538 |
Electronic Plan | Original | / | 5/31/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1074472 |
Construction | Original | A | 5/31/2018 | MICHAELA | MICHAELA | | | Construction | 1074428 |
Electrical | Original | A | 5/31/2018 | SHELBY | SHELBY | Re submittal of previously stamped sheets. | | Electrical | 1074413 |
Resubmittal 2 | Original | / | 5/31/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1074399 |
Hazmat | Original | D | 5/25/2018 | CSFIRE | CSFIRE | Plans disapproved. Please read disapproved comments. (see full review) | smanning | Hazmat | 1072663 |
CO Springs Fire | Original | A | 5/17/2018 | CSFIRE | CSFIRE | REFERENCE REVIEW REPORT ONLINE FOR COMMENTS (see full review) | csfdit | CO Springs Fire | 1069727 |
CO Springs Fire | Original | A | 5/17/2018 | CSFIRE | CSFIRE | REFERENCE REVIEW REPORT ONLINE FOR COMMENTS (see full review) | csfdit | CO Springs Fire | 1069726 |
Plumbing | Original | A | 5/9/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1066829 |
Electronic Plan | Original | / | 5/9/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1066785 |
Mechanical | Original | D | 5/9/2018 | JUSTINC | JUSTINC | Vented roof curbs only permitted when duct is to be installed within a 1 hour shaft. Provide a complete hood interlock schedule associated with makeup air and shutdown operations. Indicate ALL associated interlocks:Gas solenoid valvesMUA - KEF -1,2 RTU- 1,2 Provide refrigeration calculation for walkin cooler/freezer per IMC 1103.1 Indicate if within allowable limits per table if over allowable limits indicate on plan how protecting. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1066552 |
Electrical | Original | A | 5/9/2018 | SHELBY | SHELBY | | | Electrical | 1066513 |
Construction | Original | A | 5/9/2018 | MICHAELA | MICHAELA | | | Construction | 1066415 |
Resubmittal 1 | Original | / | 5/9/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1066337 |
Health Dept. | Original | A | 5/3/2018 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. AB | abrannon | Health Dept. | 1064337 |
Plumbing | Original | D | 3/23/2018 | TCRIPPEN | TCRIPPEN | P-2 what is the symbol outside of west wall?, Gas pipe and related Items to be on the M - pages per our web site, P - 4 remove gas Items, P - 5 separate drain lines required from each bowl on sinks see section 802.1.1 and 802.3.1 for receptor sizes (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1049874 |
Electronic Plan | Original | / | 3/23/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1049857 |
Hazmat | Original | D | 3/22/2018 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1049724 |
CO Springs Fire | Original | D | 3/22/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1049723 |
Mechanical | Original | D | 3/19/2018 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Verify code submitted per construction reviewer comments Add note: Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection. Provide refrigeration calculation for walkin cooler/freezer per IMC 1103.1 Indicate if within allowable limits per table if over allowable limits indicate on plan how protecting. It appears that the grease duct will be install using manafactured duct from Captive Aire. If this is correct provide additional Captive air sheets for sizing and routing of grease duct provided from Captive Aire. If grease duct is to be field fabricated indicate type of construction 16 gauge liquid tight etc. Also provide grease duct wrap detail. Indicate size and location of CO2 tanks. Verify with CSFD if within allowable limits. If over allowable limits indicate on plan how protecting. Indicate on page rooftop access location Provide a complete hood interlock schedule associated with makeup air and shutdown operations. Indicate ALL associated interlocks: Gas solenoid valves - MUA - KEF -1,2 - RTU- 1,2
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1048548 |
Water Division | Original | A | 3/14/2018 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Water Division | 1046982 |
Waste Water Div | Original | N | 3/14/2018 | CSUREVIEW | CSUREVIEW | No public utilities in the vicinity. RDS | rsolberg | Waste Water Div | 1046980 |
CO Springs DRE | Original | A | 3/14/2018 | RTEFERTILLER | RTEFERTILLER | Interior Finish Plans are largely consistent with approved development plan for the site (AR DP 16-00414-MM01) and can therefore be approved. Please note that the outdoor seating (tables and chairs) adjacent to the building are not approved at this time; a minor modification to the approved development will be necessary prior to Certificate of Occupancy to formally approve any outdoor seating beyond what is illustrated on the approved development plan. (see full review) | | CO Springs DRE | 1046675 |
Electrical | Original | A | 3/14/2018 | SHELBY | SHELBY | | | Electrical | 1046491 |
Health Dept. | Original | D | 3/13/2018 | HEALTHDEPT | HEALTHDEPT | Health department plan review is in process and not yet approved. For questions please contact 719-578-3199 option 3 | galvarez | Health Dept. | 1046139 |
Zoning/Planning | Original | / | 3/13/2018 | MPFITZSIMMONS | MPFITZSIMMONS | In Current Review by MFITZSIMMONS | | Zoning/Planning | 1046090 |
Construction | Original | D | 3/12/2018 | MICHAELA | MICHAELA | Revise code study form Choose which code is being complied with Provide specific structural plans for any require reinforcement at new RTU's Separate interior and exterior occupant load - combined required for plumbing fixture count. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1045881 |
Electronic Plan | Original | / | 3/12/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1045805 |
Enumeration | Original | A | 3/8/2018 | BRENT | BRENT | | | Enumeration | 1044788 |
Floodplain | Original | A | 3/6/2018 | KEITH | KEITH | fp#17025 | | Floodplain | 1043583 |
Floodplain | Original | / | 3/5/2018 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6419314041) | | Floodplain | 1043107 |