Out to Review | Original | A | 9/9/2005 | SEAN | SEAN | Charles Lowery / Jose Amaya | | Out to Review | 23779 |
Construction | Original | A | 9/9/2005 | SEAN | SEAN | | | Construction | 23755 |
Construction | Original | / | 9/9/2005 | ANGELA | ANGELA | | | Construction | 23754 |
Mechanical | Original | A | 9/7/2005 | KYE | KYE | TO CONSTRUCTION AS OF 9/9 FROM CONTRACTOR | | Mechanical | 23770 |
Mechanical | Original | / | 9/2/2005 | OWEN | OWEN | | | Mechanical | 23769 |
Out to Review | Original | A | 8/29/2005 | JEREMY | JEREMY | to Kye 9-2-05--og/Jose with JE Dunn | | Out to Review | 23778 |
Mechanical | Original | D | 8/29/2005 | KYE | KYE | M3.12A: Rated shafts for grease ducts may not change to fire wrap for contiuation due to the requirement for the shaft to be vented at the roof curb. M3.17: Label all hoods, Provide hood schedule, provide side elevation of grease hoods showing hood height vs. ceiling showing fire wrap or shaft termination point. "Sequence of operation" is unclear. Is "The supply fan" MUA-101? Note E. states the outdoor damper will close at temperature drop. MUA-101 is 100% outside air. M8.01: Label exhaust fan details as to number and location, unclear on which ones are for grease duct as no curb ventilation shown. FS4.1/4.2 Show firedampers for grease duct and capture jet fans. Grease duct may not be damperd, may need fire/smoke damper for capture jet fan duct depending on shaft/wrap location. Ceiling is not a R/A plenum, unsure where capture jet fans are pulling air from. | | Mechanical | 23773 |
Mechanical | Original | D | 8/29/2005 | KYE | KYE | Some of the rated seperations have been relocated since the last plan review, check all pages where highlights are crossed by ductwork, primarily the green highlights. Pink highlights are a smoke partition and DO NOT require a damper. M1.02: The outside air calculations are incorrect as shown, they must be figured by the occupant count as shown in table 403.3, not the architectural occupancy figures. M1.04: Fan schedule shows BF-101 in the pharmacy, unable to locate, should be EF-101 in central plant? M3.10CP: Type/amount of refrigerant exceeds allowable in Table 1103.1 requiring a machinery room that complies with Section IMC ie: Section 606, 03 International Fire Code. M3.11A: Biolab still does not have enough outside air. Table 403.3 for labs requires 1,113 cfm of OSA. Diffusers from AHU-103 total 3,520, 14.7% of is only 517.4 cfm of OSA. Cut sheets for fume hoods are not marked as to which model is used, is there only one hood? | | Mechanical | 23772 |
Plumbing | Original | A | 8/29/2005 | KYE | KYE | | | Plumbing | 23780 |
Construction | Original | D | 8/29/2005 | SEAN | SEAN | See plans for comments. | | Construction | 23759 |
Health Dept. | Original | A | 8/22/2005 | HEALTHDEPT | HEALTHDEPT | Approved as corrected in plan review dated 8/22/05. +Please contact LP at (719)578-3132 with questions. | | Health Dept. | 23765 |
Construction | Original | D | 8/16/2005 | TIMC | TIMC | Still missing code study for Central Plant Building. Wall types for soiled linen, storage rooms, etc., need to be shown as fire barriers. Fire partitions should only be show for elevator lobbies. See previous review showing where 2-hr fire barrier walls are required at mechanical rooms in basement. See previous review comments for non-rated fire partitions that are required in corridors on all floor levels. Door schedule is missing required ratings on numerous doors. Exits from mechanical penthouse are required to go into a stair enclosure with stairs not ladder, need to extend stair enclosure to penthouse. Address other comments as noted on plans. No walk-thru. | | Construction | 23768 |
Out to Review | Original | A | 8/12/2005 | JEREMY | JEREMY | at table to add mech drawings and return for revisions | | Out to Review | 23777 |
Out to Review | Original | A | 8/3/2005 | JOHNJ | JOHNJ | charels lowry revised contruction// to finish bin as mech. & plumbing to be revised// to finish bin , re run after mech.&plum is revised | | Out to Review | 23776 |
Hazmat/High Pil | Original | A | 8/3/2005 | OWEN | OWEN | sjb--7-28-05 | | Hazmat/High Pil | 23764 |
Fire | Original | D | 8/3/2005 | CSFIRE | CSFIRE | vlc--8-2-05; to Fin. Bin 8-3-05 | | Fire | 23762 |
Out to Review | Original | A | 7/22/2005 | OWEN | OWEN | jose handcarried to HAZMAT 7-22; 303-880-0013 | | Out to Review | 23775 |
Elevators | Original | A | 6/28/2005 | TOM | TOM | to Fire 7-1-05--og/ Under 2005 pprbc no variance required for machine roomless type Section 310.4.1 (Davel)--contact elevator inspector for additional warning signs for seperate machine room disconnects & controllers | | Elevators | 23761 |
Plumbing | Original | D | 6/14/2005 | KYE | KYE | See plan for comments. | | Plumbing | 23781 |
Mechanical | Original | D | 6/14/2005 | KYE | KYE | See plan for comments, too many to list. | | Mechanical | 23771 |
Construction | Original | D | 6/1/2005 | TIMC | TIMC | Provide code study for Central Plant building. Provide occupant load sheet (like rated wall sheets) showing occupant loading for each room. Missing info on door schedule. 2 exits required from mechanical penthouse per 1018. Address other comments as noted on plans. No walk-thru. | | Construction | 23758 |
Construction | Original | D | 5/13/2005 | TIMC | TIMC | Fire and Smoke barries/walls are still not correct per 03' IBC, see plans for explanation. All corridor walls are required to be constructed as smoke partitions per 407.3. Plans need to indicate which way the smoke barriers go when they intersect with fire barrier walls. This is crucial to both construction and mechanical reviews, as it effects the location of dampers and rated doors, therefore plans con not be reviewed any further until this is shown clearly on plans. No further review performed. No walk-thru. | | Construction | 23757 |
Out to Review | Original | A | 5/4/2005 | SHELLEY | SHELLEY | charles lowery - plans remaining in building | | Out to Review | 23774 |
Construction | Original | D | 3/28/2005 | TIMC | TIMC | Termanology for Fire rated construction is incorrect. Please review Table 302.1.1, Section 407, and Chapter 7 for correct termanology. This is essential to review and no further review can be performed until this is corrected. | | Construction | 23756 |
Electrical | Original | A | 3/16/2005 | JERRY | JERRY | | | Electrical | 23760 |
Health Dept. | Original | D | 3/10/2005 | HEALTHDEPT | HEALTHDEPT | Health Department Plan Review required for RFE facilities. +Call LP at (719)578-3132 with questions. | | Health Dept. | 23767 |
Health Dept. | Original | D | 3/1/2005 | OWEN | OWEN | LBP--2/28/05 Construction activity permit required. | | Health Dept. | 23766 |
Water Division | Original | D | 3/1/2005 | OWEN | OWEN | WTD--2/28/05 See stamp | | Water Division | 23783 |
Waste Water Div | Original | D | 3/1/2005 | OWEN | OWEN | WTD--2/28/05 See stamp | | Waste Water Div | 23782 |
Gas/Elec. Utils | Original | A | 3/1/2005 | OWEN | OWEN | WTD--2/28/05 See stamp | | Gas/Elec. Utils | 23763 |