Electrical | Splice 02/19/19 | A | 2/19/2019 | BERTHA | BERTHA | Splice to address inspector's comments - added lighting. | | Electrical | 1160384 |
Construction | 11/1/18 | A | 11/1/2018 | MICHAELA | MICHAELA | Note walls not rated per IBC | | Construction | 1126374 |
Construction | 11-1-18 Non-structural Walls | A | 11/1/2018 | MICHAELA | MICHAELA | | | Construction | 1126201 |
Electrical | Splice 10/25/18 | A | 10/25/2018 | BERTHA | BERTHA | Removed service upgrade portion - Revised one-line, site and floor plans to indicate existing Panel A. | | Electrical | 1124065 |
Construction | Splice 10/23/18 | A | 10/23/2018 | DANM | DANM | Fire rated walls revised listed assemblies | | Construction | 1122625 |
Out to Review | Splice 10/23/18 | / | 10/23/2018 | BECKYA | BECKYA | | | Out to Review | 1122624 |
Mechanical | Splice 10/19/18 | A | 10/19/2018 | JUSTINC | JUSTINC | Revised duct layout | | Mechanical | 1122070 |
Out to Review | Splice 10/19/18 | / | 10/19/2018 | BECKYA | BECKYA | | | Out to Review | 1122045 |
Construction | Splice 10/18/18 | A | 10/18/2018 | MICHAELA | MICHAELA | | | Construction | 1121601 |
Out to Review | Splice 10/18/18 | / | 10/18/2018 | BECKYA | BECKYA | | | Out to Review | 1121404 |
High Pile | Original | N | 8/31/2018 | CSFIRE | CSFIRE | High Pile N/A. No high pile present per plans. (see full review) | smanning | High Pile | 1105982 |
Resubmittal 3 | Original | / | 8/30/2018 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1105281 |
High Pile | Original | D | 8/28/2018 | CSFIRE | CSFIRE | High Pile plans disapproved. Please read disapproved comments. (see full review) | smanning | High Pile | 1104694 |
Hazmat | Original | A | 8/28/2018 | CSFIRE | CSFIRE | Plans approved. Please read approval comments. (see full review) | smanning | Hazmat | 1104692 |
CO Springs Fire | Original | A | 8/27/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1103822 |
CO Springs Fire | Original | A | 8/27/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1103821 |
Mechanical | Original | A | 8/21/2018 | JUSTINC | JUSTINC | | | Mechanical | 1102179 |
Electrical | Original | A | 8/15/2018 | SHELBY | SHELBY | See 6/25/18 release | | Electrical | 1100146 |
Construction | Original | A | 8/15/2018 | DANM | DANM | Minor change to door schedule | | Construction | 1100121 |
Resubmittal 2 | Original | / | 8/15/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1100107 |
High Pile | Original | D | 7/13/2018 | CSFIRE | CSFIRE | High Pile Plans disapproved. Please read disapproved comments. (see full review) | smanning | High Pile | 1089190 |
Hazmat | Original | D | 7/13/2018 | CSFIRE | CSFIRE | Hazmat plan disapproved. Please read disapproved comments. (see full review) | smanning | Hazmat | 1089189 |
CO Springs Fire | Original | D | 6/29/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1085045 |
CO Springs DRE | Original | A | 6/28/2018 | LTHELEN | LTHELEN | ok to permit per AR DP 99-006610A1(02) (see full review) | | CO Springs DRE | 1084920 |
Mechanical | Original | D | 6/26/2018 | JUSTINC | JUSTINC | Plan indicates office as part of this scope which should also be included with ventilation schedule
Per the 1st review need to indicate on plan location of fire dampers to be installed. Need to verify dampers are listed for the assembly they will penetrate. Indicate dampers in existing ductwork shown penetrating rated fire barrier. Indicate all new fire damper locations (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1083774 |
Electronic Plan | Original | / | 6/26/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1083758 |
CO Springs DRE | Original | D | 6/26/2018 | KHYLLESTED | KHYLLESTED | Please request a pre-application meeting with a planner to discuss amending the development plan: https://coloradosprings.gov/planning-and-development/webform/pre-application-meeting-request (see full review) | | CO Springs DRE | 1083623 |
Zoning/Planning | Original | / | 6/25/2018 | KHYLLESTED | KHYLLESTED | In Current Review by KHYLLESTED | | Zoning/Planning | 1083439 |
Electrical | Original | A | 6/25/2018 | BERTHA | BERTHA | Re-approved. Background revisions. | | Electrical | 1083396 |
Construction | Original | A | 6/25/2018 | DANM | DANM | | | Construction | 1083286 |
Electronic Plan | Original | / | 6/25/2018 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1083267 |
Resubmittal 1 | Original | / | 6/25/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1083100 |
Hazmat | Original | D | 5/7/2018 | CSFIRE | CSFIRE | | fdjah74 | Hazmat | 1065373 |
CO Springs Fire | Original | D | 5/7/2018 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A
See plan review comments. (see full review) | csfdit | CO Springs Fire | 1065369 |
CO Springs DRE | Original | D | 4/26/2018 | KHYLLESTED | KHYLLESTED | Please request a pre-application meeting with a planner to discuss amending the development plan: https://coloradosprings.gov/planning-and-development/webform/pre-application-meeting-request (see full review) | | CO Springs DRE | 1062046 |
Mechanical | Original | D | 4/24/2018 | JUSTINC | JUSTINC | Relocate all FP pages to their own tab Indicate ducts, size and routing for all new ductwork from main to grill locations. Provide ventilation schedule per 09' IMC 403.3
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1061254 |
Water Division | Original | N | 4/23/2018 | CSUREVIEW | CSUREVIEW | No new water being approved AJ | ajuvera | Water Division | 1060680 |
Waste Water Div | Original | N | 4/23/2018 | CSUREVIEW | CSUREVIEW | No new wastewater being approved AJ | ajuvera | Waste Water Div | 1060679 |
Zoning/Planning | Original | / | 4/23/2018 | KHYLLESTED | KHYLLESTED | In Current Review by KHYLLESTED | | Zoning/Planning | 1060372 |
Plumbing | Original | N | 4/21/2018 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit | | Plumbing | 1060318 |
Electrical | Original | A | 4/20/2018 | SHELBY | SHELBY | | | Electrical | 1060224 |
Construction | Original | D | 4/20/2018 | DANM | DANM | Note 'M' occupancy as most restrictive for allowable area Specify only one UL listing for same wall Clarify why rated construction is being proposed if Code Study Form and cover sheet are indicating non-separated mixed uses Provide accessible area at Point of Sale station
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1060205 |
Electronic Plan | Original | / | 4/20/2018 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1059976 |
Enumeration | Original | A | 4/20/2018 | BRENT | BRENT | | | Enumeration | 1059827 |
Floodplain | Original | N | 4/17/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6424008008) | | Floodplain | 1058231 |