Scanned/Finished Bin | Const, Mech, Elect - 10/12/2018 | / | 10/15/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1119976 |
Out to Review | Splice 8/17/18 | / | 10/15/2018 | SCANNING | SCANNING | | | Out to Review | 1119975 |
Electrical | Const, Mech, Elect - 10/12/2018 | A | 10/12/2018 | SHELBY | SHELBY | | | Electrical | 1119572 |
Out to Review | Const, Mech, Elect - 10/12/2018 | / | 10/12/2018 | DANM | DANM | | | Out to Review | 1119559 |
Construction | Const, Mech, Elect - 10/12/2018 | A | 10/12/2018 | DANM | DANM | Remove scope of work from 2nd floor | | Construction | 1119558 |
Mechanical | Const, Mech, Elect - 10/12/2018 | A | 10/12/2018 | JUSTINC | JUSTINC | Revised to remove mechanical scope of work indicated on sheet M2.1 | | Mechanical | 1119550 |
To Be Scanned Bin | Splice 8/17/18 | / | 8/20/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1101340 |
Plan Coordinator | Splice 8/17/18 | / | 8/20/2018 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1101316 |
Construction | Splice 8/17/18 | A | 8/20/2018 | SHELLEY | SHELLEY | All doors to match note. Floor plan revisions on second floor. Damper framing approved by DJM 8/14/18. | | Construction | 1101315 |
Construction | Splice 8/17/18 | / | 8/20/2018 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1101302 |
Construction | Splice 8/17/18 | / | 8/17/2018 | | BECKYA | Location = Construction by BECKYA | | Construction | 1101052 |
Resubmittal 1 | Splice 8/17/18 | / | 8/17/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1101044 |
Electrical | Splice 8/17/18 | A | 8/17/2018 | BERTHA | BERTHA | Revised plans to show new lighting in "no work" area. | | Electrical | 1101007 |
Construction | Splice 8/17/18 | D | 8/17/2018 | BPHILLIPS | BPHILLIPS | Provide revised door schedule to reflect updated scope. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1100936 |
Mechanical | Splice 8/17/18 | A | 8/17/2018 | DALEH | DALEH | delta 4 | | Mechanical | 1100932 |
Out to Review | Splice 8/17/18 | / | 8/17/2018 | BECKYA | BECKYA | | | Out to Review | 1100909 |
Electrical | Splice 6/25/18 | A | 6/29/2018 | BERTHA | BERTHA | Revised for as-built conditions. | | Electrical | 1085333 |
Electrical | Splice 6/25/18 | D | 6/25/2018 | SHELBY | SHELBY | 1. Engineers stamp missing. 2. Cloud only specific changes. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1083280 |
Mechanical | Splice 6/25/18 | A | 6/25/2018 | JUSTINC | JUSTINC | Revised for as-built conditions | | Mechanical | 1083269 |
Out to Review | Splice 6/25/18 | / | 6/25/2018 | BECKYA | BECKYA | | | Out to Review | 1083255 |
To Be Scanned Bin | Original | / | 6/5/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1076417 |
Plan Coordinator | Original | / | 6/5/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1076410 |
Plumbing | Original | A | 6/5/2018 | TCRIPPEN | TCRIPPEN | see M 3.3 for plumbing work small scope of work | | Plumbing | 1076407 |
Plumbing | Original | / | 6/5/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1076384 |
Plumbing | Original | / | 6/5/2018 | | JUSTINC | Location = Plumbing by JUSTINC | | Plumbing | 1076383 |
Mechanical | Original | A | 6/5/2018 | JUSTINC | JUSTINC | | | Mechanical | 1076382 |
Out to Review | Original | / | 6/5/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Out to Review | 1076318 |
Resubmittal 1 | Original | / | 6/5/2018 | NELIDA | NELIDA | Resubmittal #1 6/5/18 | | Resubmittal 1 | 1076299 |
Out to Review | Original | / | 6/1/2018 | RITA | RITA | Darlene 719-352+-4231 | | Out to Review | 1075449 |
Finished Bin | Original | / | 5/31/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1074891 |
Plumbing | Original | N | 5/31/2018 | SCANNING | SCANNING | 05/25/2918 TCC | | Plumbing | 1074892 |
Plan Coordinator | Original | / | 5/31/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1074870 |
Mechanical | Original | D | 5/31/2018 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Indicate on plan ALL new work in bold line weights. Indicate All existing in light line weights.. Indicate on plan points of connection and how much duct is to be replaced? Please clearly define scope of work. Clarify how protecting ducts indicated as penetrating rated fire partions without dampers? SEE PLANS FOR LOCATIONS
NO WALK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1074868 |
Mechanical | Original | / | 5/31/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1074662 |
Mechanical | Original | / | 5/30/2018 | | GITA | Location = Mechanical by GITA | | Mechanical | 1074226 |
Water Division | Original | N | 5/30/2018 | CSUREVIEW | CSUREVIEW | No new water service outside of building. JPN | jnoble | Water Division | 1074212 |
Waste Water Div | Original | N | 5/30/2018 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. JPN | jnoble | Waste Water Div | 1074211 |
Construction | Original | A | 5/30/2018 | SHELLEY | SHELLEY | | | Construction | 1074158 |
Electrical | Original | A | 5/29/2018 | SHELBY | SHELBY | | | Electrical | 1073658 |
Hazmat | Original | N | 5/29/2018 | CSFIRE | CSFIRE | | fdjah74 | Hazmat | 1073455 |
CO Springs Fire | Original | A | 5/29/2018 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A (see full review) | csfdit | CO Springs Fire | 1073454 |
Out to Review | Original | / | 5/29/2018 | RDCUSER | RDCUSER | | | Out to Review | 1073410 |
CO Springs DRE | Original | N | 5/29/2018 | RDCUSER | RDCUSER | INTERIOR REMODEL ONLY, NO CHANGE OF USE (see full review) | | CO Springs DRE | 1073409 |
Out to Review | Original | / | 5/29/2018 | JANE | JANE | Darlene walking | | Out to Review | 1073403 |
Mechanical | Original | / | 5/29/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1073360 |
Plan Coordinator | Original | / | 5/29/2018 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1073332 |
Construction | Original | D | 5/29/2018 | SHELLEY | SHELLEY | Clarify code requirement for rated corridors and rated dropped ceilings - does not appear to be required; provide listed assemblies for all rated construction; provide wall type A1; Clarify wall type at conference room; key notes are indicated but not shown on R1.1 and legend appears incomplete; see plans. walk ok. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1073331 |
Construction | Original | / | 5/29/2018 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1073306 |
Construction | Original | / | 5/25/2018 | | NELIDA | Location = Construction by NELIDA | | Construction | 1073138 |
Electrical | Original | D | 5/25/2018 | BERTHA | BERTHA | Provide verification that there is no fire/smoke damage to panels in damaged spaces.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1073098 |
Out to Review | Original | / | 5/25/2018 | BRENT | BRENT | | | Out to Review | 1073071 |
Enumeration | Original | A | 5/25/2018 | BRENT | BRENT | | | Enumeration | 1073070 |
Floodplain | Original | N | 5/25/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5400000211) | | Floodplain | 1073059 |