Elevators | Elevator Feeder Revision | N | 11/9/2018 | ERIC | ERIC | No changes to elevator---electrical only | | Elevators | 1129108 |
Scanned/Finished Bin | Elevator Feeder Revision | / | 11/8/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1129087 |
Electrical | Elevator Feeder Revision | A | 11/8/2018 | BERTHA | BERTHA | Revised for elevator door controller. | | Electrical | 1128942 |
Electrical | Elevator Feeder Revision | D | 11/6/2018 | SHELBY | SHELBY | 1. Indicate elevator horsepower. 2. Show "existing 175 amp feeder" size. 3. Show length of elevator tap. 4. Show tap location and new controller/disconnect location on floor plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1127765 |
Electrical | Original | A | 7/18/2018 | SHELBY | SHELBY | | | Electrical | 1091044 |
Elevators | Original | A | 7/12/2018 | ROBERTV | ROBERTV | Elevator Modernizations to Existing Elevators | | Elevators | 1088877 |
Construction | Original | A | 7/12/2018 | DANM | DANM | | | Construction | 1088696 |
Electronic Plan | Original | / | 7/6/2018 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1087173 |
Resubmittal 1 | Original | / | 7/6/2018 | SHELLEY | SHELLEY | Resubmittal #1 | | Resubmittal 1 | 1087016 |
Hazmat | Original | N | 6/25/2018 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1083175 |
CO Springs Fire | Original | N | 6/25/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1083174 |
CO Springs Fire | Original | N | 6/25/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1083172 |
Plumbing | Original | N | 6/18/2018 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit. | | Plumbing | 1080918 |
Mechanical | Original | A | 6/18/2018 | JUSTINC | JUSTINC | | | Mechanical | 1080722 |
Electronic Plan | Original | / | 6/18/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1080682 |
Electrical | Original | D | 6/18/2018 | SHELBY | SHELBY | Provide Elevator detail showing all required branch circuits. feeders and disconnects. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1080662 |
CO Springs DRE | Original | N | 6/18/2018 | SDALSING | SDALSING | Elevator work - interior remodel, No change of use and no exterior work permitted at this time (see full review) | | CO Springs DRE | 1080600 |
Elevators | Original | D | 6/15/2018 | ROBERTV | ROBERTV | 1) A110, A111, A115 - Need elevator shop drawings as referenced or plans and entire scope of work from elevator contractor performing work
2) E111, E121 - New FCU must be connected to panel supplied by Generator Emergency Power. Elevator Pit Line Voltage equipment must be installed a minimum of 30" off pit floor and be minimum NEMA 3R rated when fire sprinklers are present per AHJ.
3) FP121 - New Heat Detectors in elevator pits must flash hat inside car when activated.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1080317 |
Water Division | Original | N | 6/15/2018 | CSUREVIEW | CSUREVIEW | No new water service outside of building. JPN | jnoble | Water Division | 1080141 |
Waste Water Div | Original | N | 6/15/2018 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. JPN | jnoble | Waste Water Div | 1080140 |
Zoning/Planning | Original | / | 6/15/2018 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1080076 |
Construction | Original | D | 6/15/2018 | DANM | DANM | Discrepancy on Sheet G003 as to which year of IBC is being used Clarify 2-hr rating shown on Sheet A601
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1080071 |
Electronic Plan | Original | / | 6/14/2018 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1079915 |
Enumeration | Original | A | 6/14/2018 | BRENT | BRENT | | | Enumeration | 1079901 |
Floodplain | Original | N | 6/7/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7327101001) | | Floodplain | 1077072 |