Electrical | Splice 06/04/21 | A | 6/4/2021 | BERTHA | BERTHA | Splice to address inspector's comments. | | Electrical | 1511447 |
Electronic Plan | Splice 06/04/21 | / | 6/4/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1511419 |
Electrical | Splice 08/26/20 | A | 8/27/2020 | BERTHA | BERTHA | Removed Panel L5D1 and replaced with L5D3 - see summary of changes. | | Electrical | 1374037 |
Electronic Plan | Splice 08/26/20 | / | 8/27/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1374022 |
Electrical | Splice 02/08/19 | A | 2/6/2020 | SHELBY | SHELBY | | | Electrical | 1283827 |
Electrical | Splice 02/08/19 | D | 12/30/2019 | SHELBY | SHELBY | 1. Load summary does not match panel schedule. 2. Breakers for coolers are incorrect ( see inspector comments). 3. Show panel L5D1 on floor plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1270765 |
Electrical | Splice 02/08/19 | D | 10/22/2019 | BERTHA | BERTHA | Plans still depict Panel L5D1 - Electrical contractor has indicated that L5D1 does not exist.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1248397 |
Resubmittal 1 | Splice 02/08/19 | / | 10/22/2019 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1248344 |
Electrical | Splice 02/08/19 | D | 2/13/2019 | BERTHA | BERTHA | 1. Provide plans with appropriate panel reference per inspector's comments. 2. Provide specific clouding for all splice changes.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1158833 |
Out to Review | Splice 02/08/19 | / | 2/8/2019 | JANE | JANE | wALKING | | Out to Review | 1157763 |
Health Dept. | Original | A | 8/24/2018 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | rnielsen | Health Dept. | 1103723 |
CO Springs DRE | Original | A | 8/14/2018 | RTEIXEIRA2 | RTEIXEIRA2 | APPROVED BY ZONING. THE APPROVED AMENDED SITE PLAN WAS ATTACHED TO THE BUILDING PERMIT SET OF PLANS. THIS AMENDMENT WAS APPROVED BY HANNAH. (see full review) | | CO Springs DRE | 1099752 |
Electrical | Original | A | 8/14/2018 | SHELBY | SHELBY | | | Electrical | 1099656 |
CO Springs DRE | Original | D | 8/13/2018 | RTEIXEIRA2 | RTEIXEIRA2 | DISAPPROVED. THE APPLICANT MUST SUBMIT A PRE-APPLICATION REQUEST FORM TO MEET WITH A PLANNER. (see full review) | | CO Springs DRE | 1099181 |
Zoning/Planning | Original | / | 8/10/2018 | RTEIXEIRA2 | RTEIXEIRA2 | In Current Review by RTEIXEIRA | | Zoning/Planning | 1099027 |
Construction | Original | A | 8/10/2018 | DANM | DANM | Appear to be no changes on the drawings from original submittal | | Construction | 1098795 |
Enumeration | Original | A | 8/10/2018 | AMY | AMY | | | Enumeration | 1098751 |
Electronic Plan | Original | / | 8/10/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1098750 |
Resubmittal 2 | Original | / | 8/8/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1098123 |
CO Springs DRE | Original | D | 7/12/2018 | RTEIXEIRA2 | RTEIXEIRA2 | DISAPPROVED. THE APPLICANT MUST SUBMIT A PRE-APPLICATION MEETING TO MEET WITH A CITY PLANNER AT LAND USE REVIEW DIVISION. NO PLANS HAVE BEEN REVIEWED FOR THE EXTERIOR SITE CHANGES. (see full review) | | CO Springs DRE | 1088912 |
Zoning/Planning | Original | / | 7/11/2018 | RTEIXEIRA2 | RTEIXEIRA2 | In Current Review by RTEIXEIRA | | Zoning/Planning | 1088458 |
Electrical | Original | D | 7/11/2018 | SHELBY | SHELBY | Please address previous review comment 1 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1088314 |
Enumeration | Original | A | 7/11/2018 | AMY | AMY | | | Enumeration | 1088311 |
Resubmittal 1 | Original | / | 7/10/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1087723 |
CO Springs DRE | Original | D | 6/25/2018 | RTEIXEIRA2 | RTEIXEIRA2 | DENIED. THE BUILDING PERMIT SITE PLANS DO NOT HAVE THE APPROVED AMENDED DEVELOPMENT PLAN SITE PLANS ATTACHED TO THE BUILDING PERMIT SET OF PLANS. IF THE APPLICANT DID NOT MEET WITH A CITY PLANNER ON THIS PROPOSAL, PLEASE SUBMIT A PRE-APPLICATION REQUEST FORM TO CITY PLANNING. (see full review) | | CO Springs DRE | 1083413 |
Hazmat | Original | N | 6/25/2018 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1083184 |
CO Springs Fire | Original | N | 6/25/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1083183 |
Water Division | Original | N | 6/19/2018 | CSUREVIEW | CSUREVIEW | AJ 6/19/18 | ajuvera | Water Division | 1081159 |
Waste Water Div | Original | N | 6/19/2018 | CSUREVIEW | CSUREVIEW | AJ 6/19/18 | ajuvera | Waste Water Div | 1081158 |
Plumbing | Original | N | 6/18/2018 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit. | | Plumbing | 1080926 |
Mechanical | Original | N | 6/18/2018 | JUSTINC | JUSTINC | No new mechanical scope indicated | | Mechanical | 1080925 |
Electrical | Original | D | 6/18/2018 | SHELBY | SHELBY | 1. Verify circuit loading prior to plan submittal ( see note 16.470). 2. Provide complete electrical see https://www.pprbd.org/Downloads/CommercialHandout/Com%20Elect%20reqs.pdf. ( panel schedules, load calculation etc). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1080671 |
Zoning/Planning | Original | / | 6/15/2018 | RTEIXEIRA2 | RTEIXEIRA2 | In Current Review by RTEIXEIRA | | Zoning/Planning | 1080396 |
Construction | Original | A | 6/15/2018 | DANM | DANM | | | Construction | 1080318 |
Electronic Plan | Original | / | 6/15/2018 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1080266 |
Electronic Plan | Original | / | 6/15/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1080265 |
Enumeration | Original | A | 6/14/2018 | BRENT | BRENT | | | Enumeration | 1079934 |
Floodplain | Original | N | 6/14/2018 | BRENT | BRENT | Floodplain on parcel, not near area of work | | Floodplain | 1079933 |
Floodplain | Original | / | 6/7/2018 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7424113010) | | Floodplain | 1077371 |