- Not Set - | Splice 01/17/19 | / | 1/29/2020 | | SCANNING | Location = Plans have been disposed of -J3- | | - Not Set - | 1281048 |
- Not Set - | Splice 01/17/19 | / | 10/4/2019 | JLANE | JLANE | EXPIRED PLANS : Plans over 180 days old. They will be disposed of if not picked up by 10/31/19 - by JLANE - by JLANE | | - Not Set - | 1242982 |
Plumbing | Splice 02/11/19 | A | 2/11/2019 | SHANEN | SHANEN | Delta 5 revisions per 11/30/18 inspector comments. | | Plumbing | 1157947 |
Finished Bin | Splice 01/17/19 | / | 1/17/2019 | | RITA | Location = Finished Bin by RITA | | Finished Bin | 1150870 |
Mechanical | Splice 01/17/19 | A | 1/17/2019 | JUSTINC | JUSTINC | Revised condensate | | Mechanical | 1150860 |
Out to Review | Splice 01/17/19 | / | 1/17/2019 | BECKYA | BECKYA | | | Out to Review | 1150831 |
Electrical | Original | A | 9/10/2018 | SHELBY | SHELBY | | | Electrical | 1107957 |
Enumeration | Original | A | 8/31/2018 | BRENT | BRENT | | | Enumeration | 1105940 |
Electronic Plan | Original | / | 8/31/2018 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1105933 |
Resubmittal 5 | Original | / | 8/30/2018 | BECKYA | BECKYA | Resubmittal #5 | | Resubmittal 5 | 1105405 |
Electrical | Original | D | 8/14/2018 | SHELBY | SHELBY | Please address previous review comment 2 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1099703 |
Enumeration | Original | A | 8/6/2018 | BRENT | BRENT | | | Enumeration | 1097118 |
Electronic Plan | Original | / | 8/6/2018 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1097117 |
Resubmittal 4 | Original | / | 8/6/2018 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1097113 |
Electrical | Original | D | 7/27/2018 | SHELBY | SHELBY | 1. Comply 110.26 NEC for relocated panel 202A. 2. Show location of ' Plaza Service Equipment'. 3. Due to additional loads added after initial review provide load summary for 'PLAZA Service Equipment". (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1093780 |
Mechanical | Original | A | 7/25/2018 | JUSTINC | JUSTINC | | | Mechanical | 1093323 |
Enumeration | Original | A | 7/25/2018 | BRENT | BRENT | | | Enumeration | 1093279 |
Resubmittal 3 | Original | / | 7/25/2018 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1093255 |
Plan Coordinator | Original | D | 7/25/2018 | BECKYA | BECKYA | Disapprove all remaining departments to allow plan to be resubmitted - Reviewer comments not address with this resubmittal. Please upload Revised Electrical and Mechanical drawings. Revised Mechanical and Electrical plans must be submitted before a new review can be conducted. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 1092933 |
Resubmittal 2 | Original | / | 7/25/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1092928 |
Mechanical | Original | D | 7/23/2018 | DALEH | DALEH | ventilation schedule ? (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1092038 |
CO Springs DRE | Original | A | 7/20/2018 | MPFITZSIMMONS | MPFITZSIMMONS | (see full review) | | CO Springs DRE | 1091831 |
CO Springs DRE | Original | A | 7/20/2018 | MPFITZSIMMONS | MPFITZSIMMONS | Plan meets the Form-Based Code standards (see full review) | | CO Springs DRE | 1091828 |
Hazmat | Original | N | 7/19/2018 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1091380 |
CO Springs Fire | Original | A | 7/19/2018 | CSFIRE | CSFIRE | REFERENCE REVIEW REPORT ONLINE FOR INSPECTION RELATED COMMENTS (see full review) | csfdit | CO Springs Fire | 1091378 |
Electrical | Original | D | 7/19/2018 | SHELBY | SHELBY | 1. The supply side bonding jumper for the 75 KVA transformer secondary is incorrect. 2. The GEC for the 75 KVA transformer is incorrect.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1091092 |
Waste Water Div | Original | A | 7/19/2018 | CSUREVIEW | CSUREVIEW | No external utility work. MLW | mlwilliams | Waste Water Div | 1091086 |
Water Division | Original | A | 7/19/2018 | CSUREVIEW | CSUREVIEW | Backflow exists - will be surveyed next year per Holly. MLW | mlwilliams | Water Division | 1091085 |
Zoning/Planning | Original | / | 7/18/2018 | MPFITZSIMMONS | MPFITZSIMMONS | In Current Review by MPFITZSIMMONS | | Zoning/Planning | 1091027 |
Plumbing | Original | A | 7/18/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1090899 |
Electronic Plan | Original | / | 7/18/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1090892 |
Construction | Original | A | 7/18/2018 | MICHAELA | MICHAELA | | | Construction | 1090825 |
Electronic Plan | Original | / | 7/18/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1090822 |
Enumeration | Original | A | 7/18/2018 | BRENT | BRENT | | | Enumeration | 1090763 |
Resubmittal 1 | Original | / | 7/16/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1089645 |
Plan Coordinator | Original | D | 7/16/2018 | BECKYA | BECKYA | Disapprove all remaining departments to allow plan to be resubmitted (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 1089606 |
Mechanical | Original | D | 7/16/2018 | DALEH | DALEH | no review until floor plan has been decided on no review no walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1089589 |
Construction | Original | D | 7/13/2018 | MICHAELA | MICHAELA | Provide one floor plan for construction Alternates are not permitted
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1089292 |
Electronic Plan | Original | / | 7/13/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1089256 |
Enumeration | Original | A | 7/13/2018 | AMY | AMY | SEE ADDRESSING FLOOR PLAN A1.04 | | Enumeration | 1089198 |
Electronic Plan | Original | / | 7/13/2018 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1089151 |
Floodplain | Original | N | 7/9/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418301020) | | Floodplain | 1087261 |