- Not Set - | Splice 03/08/19 - | / | 1/29/2020 | | SCANNING | Location = Plans have been disposed of -J3- | | - Not Set - | 1281005 |
- Not Set - | Splice 03/08/19 - | / | 10/7/2019 | JLANE | JLANE | EXPIRED PLAN - Plan is over 180 days old. Plans are expired and will be disposed of if not picked up by 10/31/19 - by JLANE | | - Not Set - | 1243425 |
Scanned/Finished Bin | Splice 03/08/19 - | / | 3/15/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1167902 |
To Be Scanned Bin | Splice 03/08/19 - | / | 3/15/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1167594 |
Plan Coordinator | Splice 03/08/19 - | / | 3/15/2019 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1167561 |
Electrical | Splice 03/08/19 - | A | 3/15/2019 | SHELBY | SHELBY | | | Electrical | 1167560 |
Electrical | Splice 03/08/19 - | / | 3/15/2019 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1167541 |
Electrical | Splice 03/08/19 - | / | 3/11/2019 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1166552 |
Plan Coordinator | Splice 03/08/19 - | / | 3/11/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1166534 |
Construction | Splice 03/08/19 - | A | 3/11/2019 | MICHAELA | MICHAELA | Drawing revision at shower | | Construction | 1166533 |
Construction | Splice 03/08/19 - | / | 3/8/2019 | | JANE | Location = Construction by JANE | | Construction | 1166414 |
Electrical | Original | A | 9/12/2018 | SHELBY | SHELBY | Per RL | | Electrical | 1109093 |
Electrical | Original | D | 9/12/2018 | SHELBY | SHELBY | Please provide 2015 IECC (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1109050 |
Resubmittal 4 | Original | / | 9/5/2018 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1106400 |
CO Springs Fire | Original | A | 9/4/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas | csfdit | CO Springs Fire | 1106296 |
CO Springs Fire | Original | A | 9/4/2018 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1106292 |
Electrical | Original | D | 8/24/2018 | SHELBY | SHELBY | Please include IECC calculation. For 2017 RBC-2015 IECC. For 2011 RBC-2009 IECC. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1103430 |
Construction | Original | A | 8/24/2018 | MICHAELA | MICHAELA | | | Construction | 1103383 |
Resubmittal 3 | Original | / | 8/24/2018 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1103319 |
Electrical | Original | D | 8/23/2018 | SHELBY | SHELBY | 1. 2017 RBC necessitates 2015 IECC. See comment 1 7/20/18. ( IECC provided is 2009). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1103223 |
Resubmittal 2 | Original | / | 8/23/2018 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1102877 |
Electrical | Original | D | 8/14/2018 | SHELBY | SHELBY | 1. IECC calculation is missing from re submittal. 2. Panel LN SSBJ is sized incorrectly. ( See 250.102(c) NEC and previous review comment # 4. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1099708 |
Mechanical | Original | A | 8/14/2018 | JUSTINC | JUSTINC | | | Mechanical | 1099701 |
Mechanical | Original | D | 8/7/2018 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Comment from first review not addressed. Plan submitted to the 2015 IMC 2015 IFGC. Plan indicates 2009. Revise to indicate correct code years. Provide refrigeration calculation for minisplit unit per 15" IMC 1103.1 Verify if within allowable limits or indicate how protecting
SEE PLAN FOR ALL COMMENTS
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1097496 |
Resubmittal 1 | Original | / | 8/6/2018 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1097218 |
Hazmat | Original | N | 7/27/2018 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1093939 |
CO Springs Fire | Original | A | 7/27/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1093934 |
CO Springs DRE | Original | A | 7/25/2018 | MBINGMAN | MBINGMAN | Interior Finish - Office. Use and parking okay per DP. (see full review) | | CO Springs DRE | 1092893 |
Mechanical | Original | D | 7/24/2018 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Indicate on plan points of connection to existing duct work. (TYP.)Indicate new work with bold line weights.Indicate existing with light or dashed line weights. Clarify system layout? No drops from RTU's shown? No schedule tag indicated for return air grills? (TYP.) Clarify what are other RTU's serving Plan submitted to the 2015 IMC revise plans to match the correct code year submitted
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1092503 |
Plumbing | Original | A | 7/23/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1091969 |
Zoning/Planning | Original | / | 7/20/2018 | MBINGMAN | MBINGMAN | In Current Review by MBINGMAN | | Zoning/Planning | 1091780 |
Electrical | Original | D | 7/20/2018 | SHELBY | SHELBY | 1. 2017 RBC necessitates 2015 IECC. 2. Provide load calculation for building service. 3. Show transformer GEC size on one line. 4. Panel LN Supply Side Bonding Jumper sized incorrectly. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1091742 |
Water Division | Original | N | 7/20/2018 | CSUREVIEW | CSUREVIEW | NO COMMENTS | ajuvera | Water Division | 1091655 |
Waste Water Div | Original | N | 7/20/2018 | CSUREVIEW | CSUREVIEW | NO COMMENTS | ajuvera | Waste Water Div | 1091654 |
Construction | Original | A | 7/20/2018 | MICHAELA | MICHAELA | | | Construction | 1091555 |
Electronic Plan | Original | / | 7/18/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1091011 |
Enumeration | Original | A | 7/18/2018 | BRENT | BRENT | | | Enumeration | 1090772 |
Floodplain | Original | N | 7/16/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6233108051) | | Floodplain | 1089621 |