Scanned/Finished Bin | Original | / | 8/22/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1102815 |
To Be Scanned Bin | Original | / | 8/22/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1102595 |
Plan Coordinator | Original | / | 8/22/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1102534 |
Plumbing | Original | A | 8/22/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1102533 |
Plumbing | Original | / | 8/21/2018 | | NELIDA | Location = Plumbing by NELIDA | | Plumbing | 1102280 |
Resubmittal 2 | Original | / | 8/21/2018 | NELIDA | NELIDA | Resubmittal #2 8/21/18 | | Resubmittal 2 | 1102187 |
Out to Review | Original | / | 8/21/2018 | NELIDA | NELIDA | Joni | | Out to Review | 1102178 |
Finished Bin | Original | / | 8/21/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1102121 |
Water Division | Original | A | 8/21/2018 | CSUREVIEW | CSUREVIEW | No comments. | ajuvera | Water Division | 1101806 |
Waste Water Div | Original | A | 8/21/2018 | CSUREVIEW | CSUREVIEW | No comments. | ajuvera | Waste Water Div | 1101805 |
CSU Utilities | Original | / | 8/20/2018 | | CSFIRE | Location = CSU Utilities by CSFIRE | rpeterson | CSU Utilities | 1101662 |
Hazmat | Original | N | 8/20/2018 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1101661 |
CO Springs Fire | Original | A | 8/20/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1101660 |
Fire | Original | / | 8/8/2018 | | PTHAYER | Location = Fire by PDUYAO | | Fire | 1098169 |
CO Springs DRE | Original | A | 8/8/2018 | PTHAYER | PTHAYER | Approved interior remodel - no exterior remodel at this time. No change in use. (see full review) | | CO Springs DRE | 1098168 |
Zoning/Planning | Original | / | 8/7/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1097621 |
Plan Coordinator | Original | / | 8/7/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1097618 |
Plumbing | Original | D | 8/7/2018 | TCRIPPEN | TCRIPPEN | what type of material can be used for drain waste and vent, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1097617 |
Plumbing | Original | / | 8/6/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1097022 |
Plan Coordinator | Original | / | 8/6/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1096989 |
Electrical | Original | A | 8/6/2018 | BERTHA | BERTHA | | | Electrical | 1096988 |
Electrical | Original | / | 8/3/2018 | | RITA | Location = Electrical by RITA. Electrical pages changed out. | | Electrical | 1096470 |
Plumbing | Original | / | 8/1/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1095330 |
Plan Coordinator | Original | / | 8/1/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1095323 |
Mechanical | Original | A | 8/1/2018 | JUSTINC | JUSTINC | | | Mechanical | 1095322 |
Mechanical | Original | / | 7/31/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1095087 |
Mechanical | Original | / | 7/31/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1094738 |
Plan Coordinator | Original | / | 7/30/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1094643 |
Electrical | Original | D | 7/30/2018 | BERTHA | BERTHA | 1. Provide panel and circuit number on all electrical equipment - new and relocated - see General Note 3 sheet E-102 2. Provide one-line diagram. 3. Provide service load summary.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1094642 |
Electrical | Original | / | 7/30/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1094358 |
Electrical | Original | / | 7/27/2018 | | NELIDA | Location = Electrical by NELIDA | | Electrical | 1094000 |
Resubmittal 1 | Original | / | 7/27/2018 | NELIDA | NELIDA | Resubmittal #1 7/27/18 | | Resubmittal 1 | 1093999 |
Out to Review | Original | / | 7/27/2018 | NELIDA | NELIDA | Joni 719-393-2987 | | Out to Review | 1093998 |
Plumbing | Original | D | 7/25/2018 | TCRIPPEN | TCRIPPEN | Provide a plumbing page for the new break room sink (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1093084 |
Electrical | Original | / | 7/25/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1092961 |
Plan Coordinator | Original | / | 7/25/2018 | | LBENNETT | Location = Plan Coordinator by LBENNETT | | Plan Coordinator | 1092930 |
Construction | Original | A | 7/25/2018 | LBENNETT | LBENNETT | | | Construction | 1092929 |
Construction | Original | / | 7/24/2018 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Construction | 1092641 |
Construction | Original | / | 7/23/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1092394 |
Enumeration | Original | A | 7/23/2018 | BRENT | BRENT | | | Enumeration | 1092306 |
Plan Coordinator | Original | / | 7/23/2018 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1092304 |
Floodplain | Original | N | 7/23/2018 | BRENT | BRENT | Floodplain on parcel, not near area of work | | Floodplain | 1092303 |
Enumeration | Original | / | 7/23/2018 | BRENT | BRENT | In Current Review by BRENT | | Enumeration | 1092301 |
Enumeration | Original | / | 7/20/2018 | | JANE | Location = Enumeration by JANE | | Enumeration | 1091790 |
Finished Bin | Original | / | 7/18/2018 | NELIDA | NELIDA | pending plan review fee | | Finished Bin | 1090802 |
Floodplain | Original | / | 7/18/2018 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7326201002) | | Floodplain | 1090801 |