Scanned/Finished Bin | Splice 11/19/19 | / | 11/20/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING (rolled plan -j3-) | | Scanned/Finished Bin | 1258850 |
To Be Scanned Bin | Splice 11/19/19 | / | 11/19/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1258672 |
Plan Coordinator | Splice 11/19/19 | / | 11/19/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1258639 |
Plumbing | Splice 11/19/19 | A | 11/19/2019 | SHANEN | SHANEN | Delta 5 revisions P1.0 removed fixture schedule to eliminate floor sink, keyed notes P1 & P2, revised plumbing plan | | Plumbing | 1258637 |
Plumbing | Splice 11/19/19 | / | 11/19/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1258620 |
Plumbing | Splice 11/19/19 | / | 11/19/2019 | | NELIDA | Location = Plumbing by NELIDA | | Plumbing | 1258508 |
Scanned/Finished Bin | Splice 10/30/19 | / | 11/8/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1255070 |
Electrical | Splice 10/30/19 | A | 11/8/2019 | BERTHA | BERTHA | Revised power, lighting and panel schedules. | | Electrical | 1255029 |
Resubmittal 1 | Splice 10/30/19 | / | 11/8/2019 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1254975 |
Electrical | Splice 10/30/19 | D | 11/6/2019 | BERTHA | BERTHA | 1. Comply with previous review comments - Remove all sheets without revisions. Cloud all revisions. 2. Cloud specific splice changes. 3. Revised panels have been provided without revised power and/or lighting plans.
Call for consultation. Bertha 719-327-2911
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1254175 |
Out to Review | Splice 10/30/19 | / | 11/6/2019 | SHELLEY | SHELLEY | walking | | Out to Review | 1254149 |
Construction | Splice 10/30/19 | D | 11/6/2019 | SHELLEY | SHELLEY | Need floor plan showing locations of post modifications (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1254147 |
Finished Bin | Splice 10/30/19 | / | 11/4/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1252687 |
Plan Coordinator | Splice 10/30/19 | / | 11/2/2019 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1252632 |
Electrical | Splice 10/30/19 | D | 11/2/2019 | SHELBY | SHELBY | Remove all sheets without revisions. Cloud all revisions. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1252631 |
Electrical | Splice 10/30/19 | / | 11/1/2019 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1252025 |
Plan Coordinator | Splice 10/30/19 | / | 11/1/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1252019 |
Plumbing | Splice 10/30/19 | A | 11/1/2019 | SHANEN | SHANEN | Delta 4 revisions added plumbing pages P1.0 and P2.0 | | Plumbing | 1252015 |
Plumbing | Splice 10/30/19 | / | 11/1/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1251972 |
Plumbing | Splice 10/30/19 | / | 10/30/2019 | | RITA | Location = Plumbing by RITA | | Plumbing | 1251120 |
Out to Review | Original | / | 8/1/2019 | RITA | RITA | Marvin 316-371-6580 | | Out to Review | 1219205 |
Scanned/Finished Bin | Original | / | 3/15/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1167950 |
To Be Scanned Bin | Original | / | 3/15/2019 | | NELIDA | Location = To Be Scanned Bin by NELIDA | | To Be Scanned Bin | 1167729 |
Fountain Waste Water | Original | A | 3/15/2019 | NELIDA | NELIDA | | | Fountain Waste Water | 1167722 |
Fountain Water | Original | A | 3/15/2019 | NELIDA | NELIDA | | | Fountain Water | 1167719 |
Fountain Fire | Original | A | 3/15/2019 | NELIDA | NELIDA | | | Fountain Fire | 1167717 |
Fountain Zoning | Original | A | 3/15/2019 | NELIDA | NELIDA | | | Fountain Zoning | 1167716 |
Out to Review | Original | / | 3/15/2019 | NELIDA | NELIDA | Alexandra Padilla 623-385-9156 | | Out to Review | 1167520 |
Finished Bin | Original | / | 10/31/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1125863 |
Plan Coordinator | Original | / | 10/31/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1125846 |
Electrical | Original | A | 10/31/2018 | SHELBY | SHELBY | | | Electrical | 1125844 |
Electrical | Original | / | 10/31/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1125835 |
Electrical | Original | / | 10/31/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1125799 |
Resubmittal 3 | Original | / | 10/31/2018 | SCANNING | SCANNING | Resubmittal #3 | | Resubmittal 3 | 1125798 |
Health Dept. | Original | N | 10/17/2018 | HEALTHDEPT | HEALTHDEPT | Not applicable per conversation with Alexandra Padilla | Aparikh | Health Dept. | 1120803 |
Health Dept. | Original | D | 10/12/2018 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions contact Environmental Health at 719-578-3278. | rnielsen | Health Dept. | 1119507 |
Finished Bin | Original | / | 10/11/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1119176 |
Health Dept. | Original | N | 10/11/2018 | HEALTHDEPT | HEALTHDEPT | Not applicable | Jzimmerman | Health Dept. | 1119102 |
Health Dept. | Original | / | 10/9/2018 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1118048 |
Plan Coordinator | Original | / | 10/9/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1117997 |
Mechanical | Original | N | 10/9/2018 | JUSTINC | JUSTINC | Per note #6 on sheet A1.0 grills will be relocated and cleaned with no new ducts to be installed. | | Mechanical | 1117994 |
Mechanical | Original | / | 10/9/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1117980 |
Mechanical | Original | / | 10/9/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1117806 |
Plan Coordinator | Original | / | 10/9/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1117799 |
Electrical | Original | D | 10/9/2018 | BERTHA | BERTHA | Provide indication that "Documentation per 408.3.2 2015 IECC will be provided." Remove reference to contractor providing documentation.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1117798 |
Electrical | Original | / | 10/8/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1117583 |
Electrical | Original | / | 10/8/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1117418 |
Plan Coordinator | Original | / | 10/8/2018 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1117407 |
Construction | Original | A | 10/8/2018 | SHELLEY | SHELLEY | NEW SET PROVIDED, RE-REVIEW IN ALL DEPARTMENTS REQUIRED. | | Construction | 1117406 |
Construction | Original | / | 10/8/2018 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1117396 |
Construction | Original | / | 10/5/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1117188 |
Resubmittal 2 | Original | / | 10/5/2018 | SCANNING | SCANNING | Resubmittal #2 | | Resubmittal 2 | 1117187 |
Finished Bin | Original | / | 10/1/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1115358 |
Plan Coordinator | Original | / | 10/1/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1115334 |
Electrical | Original | A | 10/1/2018 | SHELBY | SHELBY | | | Electrical | 1115333 |
Electrical | Original | / | 10/1/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1115128 |
Electrical | Original | / | 9/28/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1115074 |
Plan Coordinator | Original | / | 9/28/2018 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1115061 |
Construction | Original | D | 9/28/2018 | DANM | DANM | Response letter states that AD sheets are replaced but the same incorrect sheets are in the submittal Walk-through review OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1115060 |
Construction | Original | / | 9/28/2018 | DANM | DANM | In Current Review by DANM | | Construction | 1115057 |
Construction | Original | / | 9/28/2018 | | NELIDA | Location = Construction by NELIDA | | Construction | 1115043 |
Resubmittal 1 | Original | / | 9/28/2018 | NELIDA | NELIDA | Resubmittal #1 9/28/18 | | Resubmittal 1 | 1115042 |
Finished Bin | Original | / | 9/19/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1111545 |
Plan Coordinator | Original | / | 9/19/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1111532 |
Plumbing | Original | N | 9/19/2018 | TCRIPPEN | TCRIPPEN | Per RBC105.2 plumbing permit not required to replace fixtures issue no permit. | | Plumbing | 1111531 |
Plumbing | Original | / | 9/19/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1111526 |
Plumbing | Original | / | 9/18/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1111249 |
Plan Coordinator | Original | / | 9/18/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1110991 |
Mechanical | Original | A | 9/18/2018 | JUSTINC | JUSTINC | Mechanical approval for relocated supply and return air grills see not 6 on sheet A1.0 | | Mechanical | 1110990 |
Mechanical | Original | / | 9/18/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1110950 |
Mechanical | Original | / | 9/17/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1110653 |
Plan Coordinator | Original | / | 9/17/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1110623 |
Electrical | Original | D | 9/17/2018 | BERTHA | BERTHA | 1. Provide 2015 IECC. 2. Provide compliance with C408.3.2 - 2015 IECC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1110621 |
Electrical | Original | / | 9/17/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1110445 |
Electrical | Original | / | 9/7/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1107421 |
Plan Coordinator | Original | / | 9/7/2018 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1107414 |
Construction | Original | D | 9/7/2018 | DANM | DANM | ADA not enforced - provide ICC A117.1 - 2009 standards on Sheets AD.0 & AD.1 Walk-through review OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1107413 |
Construction | Original | / | 9/7/2018 | DANM | DANM | In Current Review by DANM | | Construction | 1107270 |
Construction | Original | / | 9/6/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1107191 |
Plan Coordinator | Original | / | 9/6/2018 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1107179 |
Enumeration | Original | N | 9/6/2018 | BRENT | BRENT | | | Enumeration | 1107178 |
Enumeration | Original | / | 9/6/2018 | BRENT | BRENT | In Current Review by BRENT | | Enumeration | 1107174 |
Floodplain | Original | N | 8/31/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6513314025) | | Floodplain | 1105779 |