Mechanical | Splice 04/30/19 | A | 4/30/2019 | JUSTINC | JUSTINC | Revised interlocks and makeup air sequence | | Mechanical | 1184799 |
Electrical | Splice 04/22/19 | A | 4/22/2019 | BERTHA | BERTHA | Revised feeder schedule, Panels A and B series rated, provided series rated listing, revised UH's disconnects. | | Electrical | 1181392 |
Out to Review | Splice 04/22/19 | / | 4/22/2019 | BECKYA | BECKYA | | | Out to Review | 1181377 |
Electrical | Splice 01/04/19 | A | 1/4/2019 | BERTHA | BERTHA | Added UH's. | | Electrical | 1147114 |
Mechanical | Splice 01/04/19 | A | 1/4/2019 | JUSTINC | JUSTINC | | | Mechanical | 1147093 |
Out to Review | Splice 01/04/19 | / | 1/4/2019 | BECKYA | BECKYA | | | Out to Review | 1147086 |
CO Springs Fire | Splice 12/21/18 | A | 12/21/2018 | CSFIRE | CSFIRE | Splice brought in to counter. This splice indicates removal of 2 hr fire rated wall between units. The splice also indicates removal of fire alarm. Fire alarm is not required at this time due to interior occupant load does not exceed 300 at this time. In the event OL exceeds 300 for the A occupancies in the building it will drive fire alarm requirement. | fdjah74 | CO Springs Fire | 1144260 |
Construction | Splice 12/21/18 | A | 12/21/2018 | BPHILLIPS | BPHILLIPS | Removed rating from clouded wall. Non-separated uses. | | Construction | 1144242 |
Out to Review | Splice 12/21/18 | / | 12/21/2018 | BECKYA | BECKYA | | | Out to Review | 1144194 |
Out to Review | Original | / | 12/5/2018 | JANE | JANE | nadia | | Out to Review | 1138296 |
Scanned/Finished Bin | Original | / | 12/3/2018 | | GITA | Location = Scanned/Finished Bin by GITA | | Scanned/Finished Bin | 1137001 |
Hazmat | Original | N | 12/3/2018 | CSFIRE | CSFIRE | This is a deferred submittal. | rpeterson | Hazmat | 1136973 |
Hazmat | Original | D | 11/30/2018 | CSFIRE | CSFIRE | See attached comments, address and resubmit. Plans forwarded to RBD. (see full review) | smitty91 | Hazmat | 1136171 |
CO Springs Fire | Original | A | 11/28/2018 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1135465 |
Mechanical | Original | A | 11/27/2018 | JUSTINC | JUSTINC | | | Mechanical | 1134632 |
Electrical | Original | A | 11/27/2018 | SHELBY | SHELBY | | | Electrical | 1134614 |
Construction | Original | A | 11/27/2018 | DANM | DANM | | | Construction | 1134535 |
Waste Water Div | Original | A | 11/9/2018 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | Waste Water Div | 1129269 |
Health Dept. | Original | A | 11/7/2018 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | rnielsen | Health Dept. | 1128258 |
Out to Review | Original | / | 10/30/2018 | GITA | GITA | Nadia | | Out to Review | 1125658 |
Finished Bin | Original | / | 10/18/2018 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1121517 |
Health Dept. | Original | D | 10/18/2018 | HEALTHDEPT | HEALTHDEPT | Health department plan review is in process and not yet approved. For questions please contact 719-578-3199 option 3 | Aparikh | Health Dept. | 1121389 |
Health Dept. | Original | / | 10/16/2018 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1120363 |
Hazmat | Original | D | 10/15/2018 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1120004 |
CO Springs Fire | Original | D | 10/15/2018 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1120003 |
Fire | Original | / | 10/9/2018 | | SDALSING | Location = Fire by SDALSING | | Fire | 1118311 |
CO Springs DRE | Original | A | 10/9/2018 | SDALSING | SDALSING | interior finish - no exterior work or signage permitted at this time. (see full review) | | CO Springs DRE | 1118310 |
Zoning/Planning | Original | / | 10/4/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1116340 |
Waste Water Div | Original | D | 10/3/2018 | CSUREVIEW | CSUREVIEW | Need to show the existing grease interceptor size on the plumbing plans AJ | ajuvera | Waste Water Div | 1116177 |
Water Division | Original | N | 10/3/2018 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | Water Division | 1116175 |
Gas/Elec. Utils | Original | N | 10/3/2018 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | Gas/Elec. Utils | 1116174 |
CSU Utilities | Original | / | 10/3/2018 | | CSUAPPSPRM | Location = CSU Utilities by CSUAPPSPRM | zshearer | CSU Utilities | 1116097 |
CSU Contract Admin. | Original | N | 10/3/2018 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees for permit. ZS | zshearer | CSU Contract Admin. | 1116095 |
CSU Contract Admin. | Original | / | 10/3/2018 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 1115941 |
Plan Coordinator | Original | / | 10/2/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1115783 |
Plumbing | Original | A | 10/2/2018 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1115782 |
Plumbing | Original | / | 10/2/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1115535 |
Plan Coordinator | Original | / | 10/2/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1115524 |
Mechanical | Original | D | 10/2/2018 | DALEH | DALEH | change all notes to reflect 2015 codes RTU layout does not match shell drawings co2 tank location ? label all hoods label all exhaust fans see balance schedule see plans for complete red lines no walk
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1115522 |
Mechanical | Original | / | 10/1/2018 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1115474 |
Mechanical | Original | / | 10/1/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1115152 |
Plan Coordinator | Original | / | 10/1/2018 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1115150 |
Electrical | Original | D | 10/1/2018 | BERTHA | BERTHA | 1. Provide footprint (site plan) showing all electrical service equipment and disconnects serving the structure 2. Provide 2015 IECC 3. Provide compliance with C408.3.2 - 2015 IECC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1115149 |
Electrical | Original | / | 9/28/2018 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1114745 |
Electrical | Original | / | 9/27/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1114564 |
Plan Coordinator | Original | / | 9/27/2018 | | ERIC | Location = Plan Coordinator by ERIC | | Plan Coordinator | 1114549 |
Elevators | Original | N | 9/27/2018 | ERIC | ERIC | | | Elevators | 1114548 |
Elevators | Original | / | 9/27/2018 | | SCANNING | Location = Elevators by SCANNING | | Elevators | 1114405 |
Plan Coordinator | Original | / | 9/27/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1114401 |
Construction | Original | D | 9/27/2018 | MICHAELA | MICHAELA | Clarify 1-hr. walls referenced in Code Data Walk OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1114400 |
Construction | Original | / | 9/27/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1114332 |
Construction | Original | / | 9/25/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1113650 |
Plan Coordinator | Original | / | 9/25/2018 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1113548 |
Enumeration | Original | A | 9/25/2018 | AMY | AMY | SUITE 190, SEE FRONT PAGE FOR ALL SUITE NUMBERING. | | Enumeration | 1113547 |
Enumeration | Original | / | 9/24/2018 | AMY | AMY | In Current Review by AMY | | Enumeration | 1113383 |
Floodplain | Original | N | 9/24/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5318220018) | | Floodplain | 1113295 |