Electrical | Splice 03/19/19 | A | 3/21/2019 | BERTHA | BERTHA | Revised electrical plans and one-line. New 75kva transformer. Verify 240.21 | | Electrical | 1169844 |
Construction | Splice 03/19/19 | A | 3/21/2019 | MICHAELA | MICHAELA | Minor architectural revisions | | Construction | 1169827 |
Construction | Splice 03/19/19 | D | 3/19/2019 | DANM | DANM | Only one listing allowed for rated partition Walk-through review ok (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1169021 |
Electrical | Splice 03/19/19 | D | 3/19/2019 | BERTHA | BERTHA | 1. Provide feeder schedule. 2. Provide location of new 75KVA transformer.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1168993 |
Plumbing | Splice 03/19/19 | A | 3/19/2019 | SHANEN | SHANEN | Delta 2 revisions see notes 11, 12, and 13. | | Plumbing | 1168949 |
Out to Review | Splice 03/19/19 | / | 3/19/2019 | BECKYA | BECKYA | | | Out to Review | 1168928 |
Construction | Splice 01/16/19 | A | 1/17/2019 | MICHAELA | MICHAELA | Add micro piles | | Construction | 1150815 |
Construction | Splice 01/16/19 | D | 1/16/2019 | SHELLEY | SHELLEY | Adding micropiles, need soils report. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1150070 |
Out to Review | Splice 01/16/19 | / | 1/16/2019 | BECKYA | BECKYA | | | Out to Review | 1150061 |
Out to Review | Original | / | 12/31/2018 | GITA | GITA | Hayden | | Out to Review | 1145757 |
Scanned/Finished Bin | Original | / | 12/27/2018 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1145260 |
To Be Scanned Bin | Original | / | 12/26/2018 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1144507 |
Plan Coordinator | Original | / | 12/21/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1144331 |
Mechanical | Original | A | 12/21/2018 | JUSTINC | JUSTINC | | | Mechanical | 1144329 |
Mechanical | Original | / | 12/20/2018 | | JANE | Location = Mechanical by JANE | | Mechanical | 1143940 |
Electrical | Original | A | 12/20/2018 | SHELBY | SHELBY | | | Electrical | 1143921 |
Plumbing | Original | A | 12/20/2018 | SHANEN | SHANEN | OK | | Plumbing | 1143882 |
Electrical | Original | D | 12/19/2018 | BERTHA | BERTHA | Comply with previous review comment #2.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1143507 |
Construction | Original | A | 12/19/2018 | MICHAELA | MICHAELA | | | Construction | 1143499 |
Out to Review | Original | / | 12/5/2018 | NELIDA | NELIDA | Hayden 719-396-4333 | | Out to Review | 1137801 |
Finished Bin | Original | / | 12/4/2018 | | GITA | Location = Finished Bin by GITA | | Finished Bin | 1137552 |
Hazmat | Original | N | 12/3/2018 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1136819 |
CO Springs Fire | Original | N | 12/3/2018 | CSFIRE | CSFIRE | Minor remodel of Fitness/Office area and ceiling wall finishes in conference rooms. NO FIRE FINAL REQUIRED. (see full review) | wtaylor | CO Springs Fire | 1136817 |
Fire | Original | / | 11/20/2018 | | SCANNING | Location = Fire by SCANNING | | Fire | 1132456 |
Plan Coordinator | Original | / | 11/20/2018 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1132444 |
Plumbing | Original | D | 11/20/2018 | TCRIPPEN | TCRIPPEN | A Alternate method variance is required to use one drinking fountain with bottle filler any questions please call Tim at 719 - 327 - 2947. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1132443 |
Plumbing | Original | / | 11/20/2018 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Plumbing | 1132442 |
Plumbing | Original | / | 11/12/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1129675 |
Plan Coordinator | Original | / | 11/12/2018 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1129667 |
Mechanical | Original | D | 11/12/2018 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Per the construction reviewer comments there are questions regarding rated assemblies. No mechanical review can be completed until these issues have been addressed. Mechanical engineer to verify with architect on which assemblies are to be protected.
NO WALK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1129666 |
Mechanical | Original | / | 11/12/2018 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1129661 |
Mechanical | Original | / | 11/9/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1129134 |
Plan Coordinator | Original | / | 11/9/2018 | | ERIC | Location = Plan Coordinator by ERIC | | Plan Coordinator | 1129123 |
Elevators | Original | N | 11/9/2018 | ERIC | ERIC | No elevator | | Elevators | 1129122 |
Elevators | Original | / | 11/8/2018 | | SCANNING | Location = Elevators by SCANNING | | Elevators | 1128818 |
Plan Coordinator | Original | / | 11/8/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1128731 |
Construction | Original | D | 11/8/2018 | MICHAELA | MICHAELA | Revise code study for accessory use Clarify why one wall is rated and where ratings occur Notes seem to be missing on toilet room enlarged plan When walls are rated add IBC description Walk-through with Michael only
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1128730 |
Construction | Original | / | 11/7/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1128111 |
Construction | Original | / | 11/1/2018 | | RITA | Location = Construction by RITA | | Construction | 1126388 |
Health Dept. | Original | N | 10/30/2018 | HEALTHDEPT | HEALTHDEPT | Not applicable | Aparikh | Health Dept. | 1125670 |
Out to Review | Original | / | 10/29/2018 | RDCUSER | RDCUSER | | | Out to Review | 1125144 |
CO Springs DRE | Original | N | 10/29/2018 | RDCUSER | RDCUSER | INTERIOR REMODEL ONLY, NO CHANGE OF USE (see full review) | | CO Springs DRE | 1125143 |
Water Division | Original | N | 10/29/2018 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | Water Division | 1125139 |
Waste Water Div | Original | N | 10/29/2018 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | Waste Water Div | 1125138 |
Electrical | Original | D | 10/29/2018 | BERTHA | BERTHA | 1. Provide 2015 IECC 2. Provide compliance with 408.3.2 - 2015 IECC 3. Provide Keyed Note #3 sheets E-102, E-103...etc. 4. Provide panel and circuit for all new and relocated devices.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1125111 |
Enumeration | Original | N | 10/29/2018 | BRENT | BRENT | | | Enumeration | 1125060 |
Out to Review | Original | / | 10/29/2018 | JANE | JANE | Darlene walking | | Out to Review | 1125038 |
Floodplain | Original | N | 10/29/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6318303005) | | Floodplain | 1125033 |